14
Slim Relay
G3RV
●
Mounting
<SSR Mounting Pitch (Panel Mountin)>
<Relations between SSR and duct (Depth of duct)>
<Ventilation Outside the Control Panel>
*
If the air inlet or air outlet has a lter, clean the lter regularly to
prevent it from cogging to ensure an e cient ow of air.
*
Do no locate any objects around the air inlet or air outlet, otherwise
the objects may obstruct the proper ventilation of the control panel.
*
A heat exchanger, if used, should be located in front the G3RVs to
ensure the eciency or the heat exchanger.
*
Please reduce the ambient temperature of G3RVs. The rated load
current of a G3RV is measured at an ambient temperature of 25°C.
*
A G3RV uses semiconductor in the output element.
This causes the temperature inside the control panel to increase
due to heating resulting from the passeage of electrical current
through the load. To the restrict heating, attach a fan to the
ventilation outlet or air inlet of the control panel to ventilate the
panel. This will reduce the ambient temperature of the G3RVs and
thus increase reliability.
(Generally, each 10°C reduction in temperature will double the
expected life.)
●
EMI
•
This is a class A product. In residential areas it may cause redio
interference, in which case the user may be required to take
adequate measures to reduce interference.
Suitability for Use
OMRON shall not be responsible for conformity with any standards,
codes, or regulations that apply to the combination of the products in
the customer's application or use of the product.
Take all necessary steps to determine the suitability of the product
for the systems, machines, and equipment with which it will be used.
Know and observe all prohibitions of use applicable to this product.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS
RISKTO LIFE OR PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A
WHOLE HAS BEEN DESIGNEDTOADDRESSTHE RISKS, ANDTHATTHE OMRON
PRODUCT IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE
WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
See also Product catalog for Warranty and Limitation of Liability.
Duct
60mm min.
80mm min.
30mm min.
SSR
Vertical
direction
Counter measure(1)
Duct Depth
Counter measure(2)
Duct or air flow
obstruction
The depth
of SSR
SSR
SSR
SSR
Vertical
direction
Duct or air flow obstruction
Duct or air flow
obstruction
Duct or air flow obstruction
The recommended width is
1/2 as large as the depth of
SSR or less
Duct or air flow
obstruction
Air flow
Duct or air flow
obstruction
Do not surrounded the SSR
with the duct in the depth
direction, or otherwise the
heat radiation of the S5R
will be adversely affected.
If the height of the ducts
can not be lowered, place
the SSR or a metal base so
that they are not
surrounded by the ducts.
Use a short duct in
the depth direction.
Metal
base
SSR
SSR
SSR
Air inlet
Be aware of air flow
Duct
Ventllation
outlet
In the interest of product improvement, specifications are subject to change without notice.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
Cat. No. J180-E1-01