Slim Relay

 

G3RV

Mounting

<SSR Mounting Pitch (Panel Mountin)>

<Relations between SSR and duct (Depth of duct)>

<Ventilation Outside the Control Panel>

*

If the air inlet or air outlet has a lter, clean the lter regularly to 
prevent it from cogging to ensure an e cient ow of air.

*

Do no locate any objects around the air inlet or air outlet, otherwise 
the objects may obstruct the proper ventilation of the control panel.

*

A heat exchanger, if used, should be located in front the G3RVs to 
ensure the eciency or the heat exchanger.

*

Please reduce the ambient temperature of G3RVs. The rated load 
current of a G3RV is measured at an ambient temperature of 25°C.

*

A G3RV uses semiconductor in the output element. 
This causes the temperature inside the control panel to increase 
due to heating resulting from the passeage of electrical current 
through the load. To the restrict heating, attach a fan to the 
ventilation outlet or air inlet of the control panel to ventilate the 
panel. This will reduce the ambient temperature of the G3RVs and 
thus increase reliability. 
(Generally, each 10°C reduction in temperature will double the 
expected life.)

EMI

This is a class A product. In residential areas it may cause redio 
interference, in which case the user may be required to take 
adequate measures to reduce interference.

Suitability for Use

OMRON shall not be responsible for conformity with any standards, 
codes, or regulations that apply to the combination of the products in 
the customer's application or use of the product.

Take all necessary steps to determine the suitability of the product 
for the systems, machines, and equipment with which it will be used. 

Know and observe all prohibitions of use applicable to this product.

NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS

RISKTO LIFE OR PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A

WHOLE HAS BEEN DESIGNEDTOADDRESSTHE RISKS, ANDTHATTHE OMRON

PRODUCT IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE

WITHIN THE OVERALL EQUIPMENT OR SYSTEM.

See also Product catalog for Warranty and Limitation of Liability.

Duct

60mm min.

80mm min.

30mm min.

SSR

Vertical 
direction

Counter measure(1)

Duct Depth

Counter measure(2)

Duct or air flow 
obstruction

The depth 
of SSR

SSR

SSR

SSR

Vertical 
direction

Duct or air flow obstruction

Duct or air flow 
obstruction

Duct or air flow obstruction

The recommended width is 
1/2 as large as the depth of 
SSR or less

Duct or air flow 
obstruction

Air flow 

Duct or air flow 
obstruction

Do not surrounded the SSR
with the duct in the depth 
direction, or otherwise the 
heat radiation of the S5R 
will be adversely affected.

If the height of the ducts 
can not be lowered, place 
the SSR or a metal base so 
that they are not 
surrounded by the ducts.

Use a short duct in 
the depth direction.

Metal 
base

SSR

SSR

SSR

Air inlet

Be aware of air flow

Duct

Ventllation 
outlet

In the interest of product improvement, specifications are subject to change without notice.

ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.

To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.

Cat. No. J180-E1-01

Summary of Contents for G3RV

Page 1: ...G3RV SL Classification Enclosure rating Input voltage Type of connection Contact form SPST Plug in terminals General purpose Unsealed AC DC Screw terminals G3RV SL700 Push in terminals G3RV SL500 Inp...

Page 2: ...VDC 12 mA 21 6V 24 VAC DC 20 mA 21 mA 11 mA 21 6V 48 VAC DC 10 mA 11 mA 6 mA 43 2V 110 VAC 7 5 mA 8 2 mA 99V 230 VAC 7 3 mA 8 6 mA 207V Rated voltage Rated current Must operate voltage Must release vo...

Page 3: ...icing or condensation Operating 30 55 C with no icing or condensation Ambient humidity 45 85 RH Weight Approx 38 g Pollution degree 2 Degree of protection according to IEC 60529 IP20 Rated Impulse Wit...

Page 4: ...e Current Non repetitive Non repetitive Keep the inrush current to half the rated value if it occurs repetitively The values shown by the solid line are for non repetitive inrush currents Mounting Dis...

Page 5: ...tion Connection P2RVC 8 O F PLC Output Interface for 8x G2RV SL700 G3RV SL700 series PNP type Ribbon cable connector 10 Pole IEC603 1 Input Rated voltage 30 VAC VDC max Current capacity 0 5 A per chan...

Page 6: ...Green DC12V AC Yes 2A at 100 to 240VAC G3RV 202S DC12 G3RV SL700 500 A DC12 DC24V G3RV 202S DC24 G3RV SL700 500 A DC24 AC DC24V G3RV SL700 500 A AC DC24 AC DC48V G3RV SL700 500 A AC DC48 AC110V G3RV...

Page 7: ...minimum order Red R Blue S Black B P2RVM 030 3 60 pcs box minimum order P2RVM 040 4 60 pcs box minimum order P2RVM 100 10 20 pcs box minimum order P2RVM 200 20 20 pcs box minimum order Max current EN...

Page 8: ...n P2RV S 50 plates Provides isolation between adjacent relays to achieve 400 V isolation Five M2 5 6 6 2 max 99 2 7 1 88 9 26 1 47 2 70 9 83 106 7 max 92 7 max 35 Input circuit 24 V DC Terminal Arrang...

Page 9: ...ew Other Input Voltage Terminal Arrangement Internal Connections Top View 12 V DC Terminal Arrangement Internal Connections Top View 6 2 max 99 2 88 9 7 1 24 6 46 69 8 82 9 106 7 max 97 4 max 35 G3RV...

Page 10: ...tool Applicable Wires Applicable Wire Sizes G3RV SL700 Series Box clamp technology G3RV SL500 Series Push in technology Tightening torque G3RV SL700 Series 0 4Nm 2 5 dia 3 0 mm max Cannot be used Fla...

Page 11: ...conductor into the connection hole No other tools are required Note In case of wiring stranded wires without ferrules screwdriver should be inserted before inserting the wire Screwdriver should be re...

Page 12: ...e to connect cables properly if the screwdriver is inserted incorrectly General Precautions Do not use the product if it has been dropped on the ground Dropping the product may adversely affect perfor...

Page 13: ...Induction will be generated and cause malfunction or damages Be sure to conduct wiring with the power supply turned OFF Touching the terminals when they are charged may occationally result in minor el...

Page 14: ...ducts in the customer s application or use of the product Take all necessary steps to determine the suitability of the product for the systems machines and equipment with which it will be used Know an...

Reviews: