Slim Relay

 G3RV

3

Characteristics

Approved Standards

UL 508 (File No. E64562)

IEC/TUV (EN 62314)

Item

G3RV-SL700/500-A

G3RV-SL700/500-AL

G3RV-SL700/500-D

Output ON voltage drop

1.6 V rms max.

0.9 V max.

Leakage current

5 mA max. (at 200 VAC 50/60Hz)

10 µA max. (at 24VDC)

Insulation resistance

100 M

Ω

 min. (at 500 VDC)

Dielectric strength

AC2500V 50/60 Hz for 1 min between input and output

Vibration resistance

Malfunction: 10 to 55 to 10 Hz, 0.7-mm single amplitude

Shock resistance

300m/s

2

Ambient temperature

Storage: -30~+100°C (with no icing or condensation)

Operating: -30~+55°C (with no icing or condensation)

Ambient humidity

45~85%RH

Weight

Approx. 38 g

Pollution degree

2

Degree of protection according 
to IEC 60529

IP20

Rated Impulse Withstand 
Voltage

4.0kV / III

Load category 

LC-A

DC-12

Overload Current Profile

1.5Ie 1.1Ue

5s ON, 10s OFF, 10cycles

Rated insulation Voltage

240V

Model

Input ratings

Contact ratings

G3RV-SL700/500-D Series

12, 24 VDC
24, 48 VAC/DC
110, 230 VAC

24 VDC 3 A (Resistive Load) at 25°C

G3RV-SL700/500-A(L) Series

12, 24 VDC
24, 48 VAC/DC
110, 230 VAC

240 VAC 2 A (Resistive Load) at 25°C

Input ratings

Contact ratings

12, 24 VDC
24, 48 VAC/DC
110, 230 VAC

24 VDC 3 A (Resistive Load)

12, 24 VDC
24, 48 VAC/DC
110, 230 VAC

240 VAC 2 A (Resistive Load)

Summary of Contents for G3RV

Page 1: ...G3RV SL Classification Enclosure rating Input voltage Type of connection Contact form SPST Plug in terminals General purpose Unsealed AC DC Screw terminals G3RV SL700 Push in terminals G3RV SL500 Inp...

Page 2: ...VDC 12 mA 21 6V 24 VAC DC 20 mA 21 mA 11 mA 21 6V 48 VAC DC 10 mA 11 mA 6 mA 43 2V 110 VAC 7 5 mA 8 2 mA 99V 230 VAC 7 3 mA 8 6 mA 207V Rated voltage Rated current Must operate voltage Must release vo...

Page 3: ...icing or condensation Operating 30 55 C with no icing or condensation Ambient humidity 45 85 RH Weight Approx 38 g Pollution degree 2 Degree of protection according to IEC 60529 IP20 Rated Impulse Wit...

Page 4: ...e Current Non repetitive Non repetitive Keep the inrush current to half the rated value if it occurs repetitively The values shown by the solid line are for non repetitive inrush currents Mounting Dis...

Page 5: ...tion Connection P2RVC 8 O F PLC Output Interface for 8x G2RV SL700 G3RV SL700 series PNP type Ribbon cable connector 10 Pole IEC603 1 Input Rated voltage 30 VAC VDC max Current capacity 0 5 A per chan...

Page 6: ...Green DC12V AC Yes 2A at 100 to 240VAC G3RV 202S DC12 G3RV SL700 500 A DC12 DC24V G3RV 202S DC24 G3RV SL700 500 A DC24 AC DC24V G3RV SL700 500 A AC DC24 AC DC48V G3RV SL700 500 A AC DC48 AC110V G3RV...

Page 7: ...minimum order Red R Blue S Black B P2RVM 030 3 60 pcs box minimum order P2RVM 040 4 60 pcs box minimum order P2RVM 100 10 20 pcs box minimum order P2RVM 200 20 20 pcs box minimum order Max current EN...

Page 8: ...n P2RV S 50 plates Provides isolation between adjacent relays to achieve 400 V isolation Five M2 5 6 6 2 max 99 2 7 1 88 9 26 1 47 2 70 9 83 106 7 max 92 7 max 35 Input circuit 24 V DC Terminal Arrang...

Page 9: ...ew Other Input Voltage Terminal Arrangement Internal Connections Top View 12 V DC Terminal Arrangement Internal Connections Top View 6 2 max 99 2 88 9 7 1 24 6 46 69 8 82 9 106 7 max 97 4 max 35 G3RV...

Page 10: ...tool Applicable Wires Applicable Wire Sizes G3RV SL700 Series Box clamp technology G3RV SL500 Series Push in technology Tightening torque G3RV SL700 Series 0 4Nm 2 5 dia 3 0 mm max Cannot be used Fla...

Page 11: ...conductor into the connection hole No other tools are required Note In case of wiring stranded wires without ferrules screwdriver should be inserted before inserting the wire Screwdriver should be re...

Page 12: ...e to connect cables properly if the screwdriver is inserted incorrectly General Precautions Do not use the product if it has been dropped on the ground Dropping the product may adversely affect perfor...

Page 13: ...Induction will be generated and cause malfunction or damages Be sure to conduct wiring with the power supply turned OFF Touching the terminals when they are charged may occationally result in minor el...

Page 14: ...ducts in the customer s application or use of the product Take all necessary steps to determine the suitability of the product for the systems machines and equipment with which it will be used Know an...

Reviews: