G3PA
4
■
Characteristics
Item
G3PA-
210B(L)-VD
G3PA-
220B(L)-VD
G3PA-
240B(L)-VD
G3PA-
260B(L)-VD
G3PA-
420B-VD
G3PA-
420B-VD-2
G3PA-
430B-VD
G3PA-
430B-VD-2
G3PA-
450B-VD-2
Operate time 1/2 of load power source cycle + 1 ms max. (DC Input, -B models)
1 1/2 of load power source cycle + 1 ms max. (AC Input)
1 ms max. (-BL models)
Release time 1/2 of load power source cycle + 1 ms max. (DC Input)
1 1/2 of load power source cycle + 1 ms max. (AC Input)
Output ON
voltage drop
1.6 V (RMS) max.
1.8 V (RMS) max.
Leakage
current
5 mA max. (at 100 VAC)
10 mA max. (at 200 VAC)
10 mA max. (at 100 VAC)
20 mA max. (at 200 VAC)
20 mA max.
(at 400 VAC)
20 mA max.
(at 480 VAC)
20 mA max.
(at 400 VAC)
20 mA max. (at 480 VAC)
I
2
t
260 A
2
s
1,260 A
2
s
260 A
2
s
1,800 A
2
s
1,800 A
2
s
1,800 A
2
s
Insulation
resistance
100 M
Ω
min. (at 500 VDC)
Dielectric
strength
4,000 VAC, 50/60 Hz for 1 min
Vibration
resistance
Destruction: 10 to 55 to 10 Hz, 0.375–mm single amplitude (Mounted to DIN track)
Shock
resistance
Destruction: 300 m/s
2
(mounted to DIN track)
Ambient
temperature
Operating: –30
°
C to 80
°
C (with no icing or condensation)
Storage:
–30
°
C to 100
°
C (with no icing or condensation)
Certified
standards
UL508, CSA C22.2 (No.14, No.950), EN60950-1 File No.
5915ÜG
UL508,
CSA C22.2
(No.14),
EN60947-4-3
File No.
6642ÜG
UL508,
CSA C22.2
(No.14),
EN60947-4-3
File No.
133127ÜG
UL508,
CSA C22.2
(No.14),
EN60947-4-3
File No.
6642ÜG
UL508, CSA C22.2
(No.14), EN60947-4-3
File No. 133127ÜG
EMC
Emission: EN55011 Group 1 Class A
Immunity: EN61000-6-2
Ambient
humidity
Operating: 45% to 85%
Weight
Approx.
260 g
Approx.
340 g
Approx.
460 g
Approx.
900 g
Approx.
290 g
Approx.
290 g
Approx.
410 g
Approx.
410 g
Approx.
900 g