G3PA

14

Safety Precautions

Precautions for Correct Use

Please observe the following precautions to prevent failure to 
operate, malfunction, or undesirable effect on product performance. 

Load Connection

For an AC load, use a power supply rated at 50 or 60 Hz.
The maximum operating frequency is 10 Hz.
The G3PA-(VD) has a built-in varistor for overvoltage protection.

At a low applied voltage, such as 24 VAC, the load current is not fully 
supplied. When the Unit is switched ON, the voltage required to 
power the Unit deprives the output signal of the necessary voltage 
level and thus creates loss time. The lower the load voltage is, the 
greater the loss time is. This condition, however, will not create any 
serious problems.

For a DC or L load, a diode should be connected in parallel the load 
to absorb the counter electromotive force of the load.

When attaching a heat sink to the G3PA-(VD), in order to facilitate 
heat dissipation, apply silicone grease or equivalent heat-conductive 
grease on the heat sink. (Toshiba Silicone, Shinetsu Silicone, etc.) 

Tighten the mounting screws of the heat sink with a torque of 0.78 to 
0.98 N·m.

Noise Terminal Voltage according to 
EN55011

The G3PA-(VD) complies with EN55011 standards when a capacitor 
is connected to the load power supply as shown in the following 
circuit diagram.

Recommended Capacitor: 1 

µ

F, 250 VAC

Mounting

Loss time

SSR

Input

Load

Load power 
supply

G3PA-(VD)

Output

Load

Input

DIN track

G3PA

G3PA

Panel

DIN track

Panel

The rated ambient 
temperature is 
40

°

C. (30

°

C for 

400 V.)

Vertical mounting

Close mounting

Horizontal mounting

• 

Screw or DIN track mounting is possible.

• 

Vertical mounting should usually be used.

• 

Close mounting cannot be used if the SSR is used at a 100% load 

current. Leave a gap of at least 10 mm on the left and right of each 
Unit.

• 

Close mounting can be used under the following conditions: 

1. Close mounting can be performed with no more than three SSRs 

(For four or more SSRs, leave a gap of at least 10 mm.)  

2. Use a load current of 80% or less (90% or less for the 

G3PA-210B-VD, G3PA-220B-VD, or G3PA-240B-VD).

3. Leave a gap of at least 80 mm above and below the SSR.
4. Leave a gap of at least 60 mm from wiring ducts to the top of the 

SSR and at least 30 mm from wiring ducts to the bottom of the SSR.

• 

With vertical mounting, reduce the load current by 30%. 
(Refer to the 

Load Current vs. Ambient Temperature

 graph.)

80 mm

Note:

 Leave a distance of 60 mm min. between SSRs and ducts (especially above the SSR).

V

er

tical

V

er

tical

V

er

tical

Summary of Contents for G3PA

Page 1: ...nd VDE reinforced insulation Refer to Safety Precautions for All Solid State Relays For the most recent information on models that have been certified for safety standards refer to your OMRON website...

Page 2: ...430B VD 2 30 A at 200 to 480 VAC G3PA 450B VD 2 50 A at 200 to 480 VAC Name Carry current Load voltage range Model Applicable SSR VDE certification Power Device Cartridge 10 A 19 to 264 VAC G32A A10 V...

Page 3: ...1 VDC min G3PA 430B VD G3PA 420B VD 2 G3PA 430B VD 2 G3PA 450B VD 2 Model Rated load voltage Load voltage range Load current Inrush current VDRM reference value G3PA 210B L VD 24 to 240 VAC 50 60 Hz...

Page 4: ...s 1 800 A2 s 1 800 A2 s Insulation resistance 100 M min at 500 VDC Dielectric strength 4 000 VAC 50 60 Hz for 1 min Vibration resistance Destruction 10 to 55 to 10 Hz 0 375 mm single amplitude Mounted...

Page 5: ...the temperature indicator will not turn red Be sure to turn OFF the power supply when replacing the Cartridge Supplying power with the Cartridge removed may result in malfunction To remove or replace...

Page 6: ...he letters on the cartridge and those on the G3PA are in the same direction and side A and side B are even 4 Attach the terminal cover 5 Switch on the power and check the G3PA to be sure it works prop...

Page 7: ...ert the linking terminal securely into the center of the screw and tighten the screw SSR G32A Unit SSR G32A Unit The cover will not fit if the terminal protrudes 1 When SSR are close mounted loosen th...

Page 8: ...0 20 30 60 40 25 20 80 Panel Ground Ambient temperature C Ambient temperature C Ambient temperature C Load current A Load current A Load current A Vertical Mounting G3PA 240B L VD G3PA 260B L VD G3PA...

Page 9: ...Input impedance k Input impedance k 40 60 80 100 20 0 20 30 60 40 42 20 3 5 11 28 15 11 14 18 20 10 5 5 5 10 7 Panel Ground Horizontal Mounting Ambient temperature C Ambient temperature C Ambient tem...

Page 10: ...430B VD 2 Load current A Ambient temperature C Load current A G3PA 420B VD G3PA 420B VD 2 DIN track Panel Ground Close Mounting Up to Three Ambient temperature C Ambient temperature C Ambient temperat...

Page 11: ...e rated value if it occurs repetitively G3PA 210B L VD G3PA 220B L VD G3PA 420B VD G3PA 420B VD 2 G3PA 240B L VD 260B L VD G3PA 430B VD G3PA 430B VD 2 G3PA 450B VD 2 Inrush current A Peak Energized ti...

Page 12: ...ircuit Two 4 5 dia or M4 holes 4 6 dia Two M4 100 max G3PA 220B L VD Mounting Holes Without Terminal Cover With Terminal Cover Linking terminal B1 Two M3 5 Linking terminal B2 4 6 x 5 6 elliptical hol...

Page 13: ...5 4 6 dia 37 max 4 5 x 5 6 elliptic hole 100 max G3PA 420B VD G3PA 420B VD 2 Mounting Holes Terminal Arrangement Internal Connections Trigger circuit Input circuit 100 max Linking terminal B2 Linking...

Page 14: ...age according to EN55011 The G3PA VD complies with EN55011 standards when a capacitor is connected to the load power supply as shown in the following circuit diagram Recommended Capacitor 1 F 250 VAC...

Page 15: ...rrents of 20 A 0 31 x 10 3 1 Thus 4 fans would be required Size of fans 92 mm2 Air volume 0 7 m3 min Ambient temperature of control panel 30 C If there are other instruments that generate heat in the...

Page 16: ...products Outdoor use uses involving potential chemical contamination or electrical interference or conditions or uses not described in this catalog Nuclear energy control systems combustion systems r...

Reviews: