Section 2 Wiring and Mounting
B-23
Check the F3SN-B operations with the machine stopped.
1. A test rod is not deformed.
(note 1)
2. Nothing is present in the detection zone.
The power indicator and all of the light intensity level indicators are lit within one second after the F3SN-B is
turned ON.
3. A test rod can be detected at any position in the detection zone. In
other words, all the light intensity level indicators go off and the OFF-state
indicator remains lit as long as the test rod is present in the detection zone.
Guide the test rod through detection zone as shown in the figure.
[Note1]:
Test rod is not supplied with the F3SN-B
P70 series.
4. In case the external test function is used:
When the test input line is short-circuited to the 9DC to24V line, the
OFF-state indicator is lit.
5. In case the EDM function is used:
When the light curtain is interrupted and the EDM input line becomes open,
the light curtain enters the lockout condition.
6. In case the start/restart interlock function is used:
Even if the light curtain receives light after turning power ON, the OFF-state indicator remains lit. If the reset
input is applied, the ON-state indicator is lit.
When the light curtain is interrupted, then go back to the light receiving condition, the OFF-state indicator
remains lit. If the reset input is applied, the ON-state indicator is lit.
Operate the machine and check to see if a hazardous part stops under the conditions below.
1. The hazardous part immediately stops when a test rod is intruded in the detection zone at 3 points:
directly in front of the emitter, directly in front of the receiver, midway between the emitter and receiver. (Use
correct test rod as described in Step 3.)
2. The hazardous part remains stopped as long as the test rod is present in the detection zone.
3. The hazardous part stops when the F3SN-B power supply is turned OFF.
4. The overall measured machine response time is less than the calculated time.
Start
Stop
Summary of Contents for F3SN-B P Series
Page 10: ...A 3 1 2 4 b b OFF 300ms 1 b 9V Vs 2 4 1 2 5 2 1 mm...
Page 14: ...A 7 2 1 2 1 1 F3SN B F3SN B...
Page 17: ...A 10 2 1 3 D 0 2 3m 0 27m 3m L 2 tan10 L 0 087 m 2 1 4 F3SN B 2 F3SN B L D D L D 10 10...
Page 18: ...A 11 0 2 3m 0 54m 3m L tan10 L 0 18 m L D D 10 10...
Page 21: ...A 14 2 3 2 3 1 F3SN B R36 mm 52mm R 3 6 R 3 6 R 3 6 80mm 80mm...
Page 23: ...A 16 1 2 3 2...
Page 30: ...A 23 1 2 F3SN B 1 3 5 OFF 1 F3SN B P70 4 9 24V OFF 5 6 1 3 3 2 3 F3SN B 4...
Page 31: ...A 24 2 2 8 1 4 1 5 6 5 6 7 3 24V 2 3 1 4 1 2 2 2 0V RS 485 B RS 485 A 7 1 24V 2 2 4 2 NO...
Page 32: ...A 25 OFF OFF OFF ON OFF 25 s 160 200 s OFF OFF ON ON OFF 130 s ON...