background image

Digital Temperature Controllers

 

E5GN

17

Precautions for Safe Use

Be sure to observe the following precautions to prevent malfunction 
or adverse affects on the performance or functionality of the product. 
Not doing so may occasionally result in faulty operation.

1.

This product is specifically designed for indoor use only. 
Do not use this product in the following places:

• Places directly subject to heat radiated from heating equipment.
• Places subject to splashing liquid or oil atmosphere.
• Places subject to direct sunlight.

• Places subject to dust or corrosive gas (in particular, sulfide gas 

and ammonia gas).

• Places subject to intense temperature change.

• Places subject to icing and condensation.

• Places subject to vibration and large shocks.

2.

Use and store the product within the rated ambient temperature 
and humidity.
Gang-mounting two or more Temperature Controllers, or 
mounting Temperature Controllers above each other may cause 
heat to build up inside the Temperature Controllers, which will 
shorten their service life. In such a case, use forced cooling by 
fans or other means of air ventilation to cool down the 
Temperature Controllers.

3.

To allow heat to escape, do not block the area around the 
product. Do not block the ventilation holes on the product.

4.

Be sure to wire properly with correct polarity of terminals.

5.

Use the specified size (M3.5, width 7.2 mm or less) crimped 
terminals for wiring. To connect bare wires to the terminal block, 
use stranded or solid copper wires with a gage of AWG24 to 
AWG14 (equal to a cross-sectional area of 0.205 to 2.081 mm

2

). 

(The stripping length is 5 to 6 mm.) Up to two wires or two crimp 
terminals can be inserted into a single terminal.

6.

Do not wire the terminals that are not used.

7.

To avoid inductive noise, keep the wiring for the product’s 
terminal block away from power cables carry high voltages or 
large currents. Also, do not wire power lines together with or 
parallel to product wiring. Using shielded cables and using 
separate conduits or ducts is recommended.
Attach a surge suppressor or noise filter to peripheral devices 
that generate noise (in particular, motors, transformers, 
solenoids, magnetic coils, or other equipment that have an 
inductance component).
When a noise filter is used at the power supply, first check the 
voltage or current, and attach the noise filter as close as possible 
to the product.
Allow as much space as possible between the product and 
devices that generate powerful high frequencies (high-frequency 
welders, high-frequency sewing machines, etc.) or surge.

8.

Use this product within the rated load and power supply.

9.

Make sure that the rated voltage is attained within two seconds 
of turning ON the power using a switch or relay contact. If the 
voltage is applied gradually, the power may not be reset or output 
malfunctions may occur.

10. Make sure that the Temperature Controller has 30 minutes or 

more to warm up after turning ON the power before starting 
actual control operations to ensure the correct temperature 
display.

11. When executing self-tuning, turn ON power to the load (e.g., 

heater) at the same time as or before supplying power to the 
product. If power is turned ON to the product before turning ON 
power to the load, self-tuning will not be performed properly and 
optimum control will not be achieved.

12. A switch or circuit breaker must be provided close to the product. 

The switch or circuit breaker must be within easy reach of the 
operator, and must be marked as a disconnecting means for this 
unit.

13. Always turn OFF the power supply before pulling out the interior 

of the product, and never touch nor apply shock to the terminals 
or electronic components. When inserting the interior of the 
product, do not allow the electronic components to touch the 
case.

14. Do not use paint thinner or similar chemical to clean with. Use 

standard grade alcohol.

15. Design the system (e.g., control panel) considering the 2 

seconds of delay that the product's output to be set after power 
ON.

16. The output may turn OFF when shifting to certain levels. Take 

this into consideration when performing control.

17. The EEPROM has a limited write life. When overwriting data 

frequently, e.g., via communications, use RAM Mode.

Precautions for Correct Use 

Service Life 

1. Use the product within the following temperature and humidity 

ranges:

Temperature: 

10 to 55

°

C (with no icing or condensation)

Humidity: 25% to 85%
If the product is installed inside a control board, the ambient 
temperature must be kept to under 55

°

C, including the 

temperature around the product. 

2. The service life of electronic devices like Temperature Controllers 

is determined not only by the number of times the relay is 
switched but also by the service life of internal electronic 
components. Component service life is affected by the ambient 
temperature: the higher the temperature, the shorter the service 
life and, the lower the temperature, the longer the service life. 
Therefore, the service life can be extended by lowering the 
temperature of the Temperature Controller. 

3. When two or more Temperature Controllers are mounted 

horizontally close to each other or vertically next to one another, 
the internal temperature will increase due to heat radiated by the 
Temperature Controllers and the service life will decrease. In such 
a case, use forced cooling by fans or other means of air 
ventilation to cool down the Temperature Controllers. When 
providing forced cooling, however, be careful not to cool down the 
terminals sections alone to avoid measurement errors.

Measurement Accuracy 

1. When extending or connecting the thermocouple lead wire, be 

sure to use compensating wires that match the thermocouple 
types. 

2. When extending or connecting the lead wire of the platinum 

resistance thermometer, be sure to use wires that have low 
resistance and keep the resistance of the three lead wires the 
same. 

3. Mount the product so that it is horizontally level. 
4. If the measurement accuracy is low, check to see if input shift has 

been set correctly. 

Waterproofing

The degree of protection is as shown below. Sections without any 
specification on their degree of protection or those with IP

@

0 are not 

waterproof.

Front panel: NEMA4X for indoor use (equivalent to IP66)
Rear case: IP20, Terminal section: IP00

Operating Precautions

1. It takes approximately two seconds for the outputs to turn ON 

from after the power supply is turned ON. Due consideration must 
be given to this time when incorporating Temperature Controllers 
in a sequence circuit. 

2. When using self-tuning, turn ON power for the load (e.g., heater) 

at the same time as or before supplying power to the Temperature 
Controller. If power is turned ON for the Temperature Controller 
before turning ON power for the load, self-tuning will not be 
performed properly and optimum control will not be achieved. 

3. When starting operation after the Temperature Controller has 

warmed up, turn OFF the power and then turn it ON again at the 
same time as turning ON power for the load. (Instead of turning 
the Temperature Controller OFF and ON again, switching from 
STOP mode to RUN mode can also be used.) 

Summary of Contents for E5GN

Page 1: ...At the end of this document you will find links to products related to this catalog You can go directly to our shop by clicking HERE HERE ...

Page 2: ...ations Blank No communications function 03 RS 485 4 Input type TC Thermocouple P Platinum resistance thermometer 5 CompoWay F serial communications Blank Not available FLK CompoWay F serial communications Ordering Information Standard Models Note 1 If the heating cooling function is used ALM1 will be used for control output and so alarm output will not be available 2 Control output 2 for heating c...

Page 3: ...R S B Platinum resistance thermometer Pt100 JPt100 Infrared temperature sensor 10 to 70 C 60 to 120 C 115 to 165 C 140 to 260 C Voltage input 0 to 50 mV Control output Relay output SPST NO 250 VAC 2 A resistive load electrical life 100 000 operations Voltage output 12 VDC PNP max load current 21 mA with short circuit protection circuit Alarm output SPST NO 250 VAC 1 A resistive load electrical lif...

Page 4: ...0 0 1700 0 1800 100 70 0 120 0 165 0 260 0 0 17 400 0 199 9 18 400 0 199 9 Pt100 JPt100 Input type Platinum resistance thermometer input Platinum resistance thermometer Name Set value Thermocouple Thermocouple input Analog input 0 to 50 mV Input type Name Set value Temperature range Temperature range Applicable standards by input type are as follows K J T E N R S B JIS C1602 1995 L Fe CuNi DIN 437...

Page 5: ...gative 0 Alarm function OFF Output OFF 1 1 Upper and lower limit deviation 2 2 Upper limit deviation 3 Lower limit deviation 4 1 Upper and lower limit range deviation 3 5 1 Upper and lower limit with standby se quence deviation 4 6 Upper limit with standby sequence de viation 7 Lower limit with standby sequence de viation 8 Absolute value upper limit 9 Absolute value lower limit 10 Absolute value ...

Page 6: ...iod 500 ms Insulation resistance 20 MΩ min at 500 VDC megger Dielectric strength 2000 VAC 50 or 60 Hz for 1 min between different charging terminals Vibration resistance 10 to 55 Hz 10 m s2 for 2 hours each in X Y and Z directions Shock resistance 300 m s2 3 times each in 3 axes 6 directions relay 100 m s2 Weight Approx 90 g Mounting bracket approx 10 g Degree of protection Front panel NEMA4X for ...

Page 7: ...mission path connection Multiple points Communications method RS 485 two wire half duplex Synchronization method Start stop synchronization Baud rate 1 200 2 400 4 800 9 600 19 200 bps Transmission code ASCII Data bit length see note 7 or 8 bits Stop bit length see note 1 or 2 bits Error detection Vertical parity none even odd Frame check sequence FCS with SYSWAY Block check character BCC with Com...

Page 8: ...ads still attached Insert the Controller through the hole in the panel from the front and push the adapter on from the rear Push the adapter up to the back of the panel ensuring that the controller is pushed all the way in removing any gap between the Controller panel and adapter Finally use the two screws on the adapter to secure the unit in place To mount the E5GN so that it is waterproof insert...

Page 9: ...displayed when the dis play unit parameter is set to a temperature In dication is determined by the currently selected temperature unit parameter set value When this parameter is set to C c is displayed and when set to F f is displayed Displays the set point manipulated variable or set value setup of the parameter Each press of this key increases values displayed on the No 2 display Holding down t...

Page 10: ...l cannot be modified Communications Setting Level To select this level press the key once for less than one second in the initial setting level When the communications function is used set the communications conditions in this level Communicating with a personal computer host computer allows set points to be read and written and manipulated variables to be monitored Advanced Function Setting Level...

Page 11: ...nt level Less than 1 second 1 second min Less than 1 second 1 second min Calibration level Protect level key 1 second min key key key key key key key Control in progress Control stopped Level change 3 seconds min Initial setting level Communica tions setting level Password input set value 169 Advanced function setting level Password input set value 1201 Display flashes when key pressed 3 seconds m...

Page 12: ...to 1700 C 0 to 3000 F B 11 100 to 1800 C 300 to 3200 F Infrared temperature sensor ES1B 10 to 70 C 12 0 to 90 C 0 to 190 F 60 to 120 C 13 0 to 120 C 0 to 240 F 115 to 165 C 14 0 to 165 C 0 to 320 F 140 to 260 C 15 0 to 260 C 0 to 500 F Analog input 0 to 50 mV 16 One of following ranges depending on the re sults of scaling 1999 to 9999 199 9 to 999 9 Input Type Specifications Set Value Input Temper...

Page 13: ...ff prlt 3 sero off cjc on O O c c u no 1 bps 9 6 len 7 sbit 2 prty e en ST stable range Input error output Cold junction compensation method MB command logic switching Move to calibration level Initial Setting Level Input type Temperature unit C F SP upper limit Scaling upper limit PID ON OFF Scaling lower limit Decimal point Standard or heating cooling Moved by setting password 169 Communications...

Page 14: ... for at least 1 s Press the O M keys for at least 3 s Display flashes Protect Level Operation adjustment protection Restricts displaying and modifying menus in operation adjustment and manual control levels Initial setting communications protection This protect level restricts movement to the initial setting communications setting and advanced function setting levels Setting change protection Prot...

Page 15: ...mperature measured by sensor Temperature display 0 no shift 100 C 100 C 10 shifted 10 C 100 C 110 C 10 shifted 10 C 100 C 90 C Level Set value 0 1 2 3 Operation level PV PV SP Other X X Adjustment level X X X Set value Initial setting level Communication s setting level Advanced function setting level 0 1 X 2 X X X Operation adjustment protection Initial setting communications protection Setting c...

Page 16: ...stop bit to 1 or 2 Communications Parity prty Use this parameter to set the communications parity to None Even or Odd Troubleshooting When an error occurs an error code will be displayed on the No 1 display Check the contents of an error and take appropriate countermeasures Note 1 If the input is within the range for which control is possible but outside the displayable range 1999 199 9 to 9999 99...

Page 17: ...imited energy See note 1 d Caution To reduce the risk of fire or electric shock do not interconnect the outputs of different Class 2 circuits See note 2 If the output relays are used past their life expectancy contact fusing or burning may occasionally occur Always consider the application conditions and use the output relays within their rated load and electrical life expectancy The life expectan...

Page 18: ...nd must be marked as a disconnecting means for this unit 13 Always turn OFF the power supply before pulling out the interior of the product and never touch nor apply shock to the terminals or electronic components When inserting the interior of the product do not allow the electronic components to touch the case 14 Do not use paint thinner or similar chemical to clean with Use standard grade alcoh...

Page 19: ...e The E5GN can be replaced by removing the terminal plate 1 Press down hard on the fasteners on both sides of the terminals to unlock the terminal plate and pull upwards 2 Draw out the terminal plate as it is 3 Before you insert the terminal plate again make sure that the pins match the positions of the holes in the terminal plate Wiring Precautions Connect the terminals as specified below The exp...

Page 20: ...Digital Temperature Controllers E5GN 19 ...

Page 21: ...codes or regulations that apply to the combination of products in the customer s application or use of the products Take all necessary steps to determine the suitability of the product for the systems machines and equipment with which it will be used Know and observe all prohibitions of use applicable to this product NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPE...

Page 22: ...and datasheets of all products Estimated delivery time enquiry in real time Logistics systems for the shipment of materials almost anywhere in the world Purchasing management order record and tracking of shipments To access the product click on the green button Product Code Reference Product link Industrial Career Final Push buttons Decade 113802 NRT C Buy on EAN ...

Reviews: