10
Digital Temperature Controllers
E5GN
Specification Setting after Turning ON Power
Initial Setting Level
This level is used for setting basic specifications of the Temperature
Controller. Using this level, set the input type for selecting the input to
be connected such as the thermocouple or platinum resistance ther-
mometer and set the range of set point and the alarm mode.
The move from the operation level to the initial setting level, press
key for three seconds or more.
The initial setting level is not displayed when “initial/communications
protection” is set to “2.” This initial setting level can be used when
“initial setting/communications protection” is set to “0” or “1.”
The “scaling upper limit,” “scaling lower limit,” and “decimal point”
parameters are displayed when an analog voltage input is selected
as the input type.
To return to the operation level, press the
key for longer than one
second.
Power ON
Operation level
Adjustment level
Less than 1 second
1 second min.
Less than 1 second
1 second min.
Calibration level
Protect level
key
+
1 second min.
key
key
key
key
key
key
+
key
+
Control in progress
Control stopped
Level change
3 seconds
min.
Initial setting
level
Communica-
tions setting
level
Password input
set value "
−
169"
Advanced function
setting level
Password input
set value "1201"
Display flashes
when key pressed.
3 seconds
min.
The time taken to move
to the protect level can
be adjusted by changing
the "Move to protect lev-
el time" setting.
25
100
Control stops.
25
100
in-t
0
in-h
100
in-l
0
dp
0
d-u
c
sl-h
1300
sl-l
-200
cntl
onof
st
on
cp
20
ore?
or-r
alt1
2
c-cp
20
amo?
0
c
c
s-hc
stnd
Initial Setting Level
Input type
Scaling upper limit
Scaling lower limit
Decimal point
SP upper limit
Limit the set point.
SP lower limit
PID ON/OFF
Temperature unit
°
C,
°
F
Standard or
heating/cooling
ST
For input type of temperature,
standard, or PID
Control period (heating)
Control period (cooling)
Direct/reverse operation
Alarm 1 type
Move to advanced
function setting level
Set the pulse output cycle.
Displayed when initial setting/
communications protection is set to 0