Digital Temperature Controllers
E5GN
Input Shift
All points in the sensor range are shifted by the value set as the tem-
perature input shift value.
Example
Protect Level
Operation/Adjustment Protection
The following table shows the relationship between set values and
the range of protection.
When this parameter is set to “0,” parameters are not protected.
Initial Setting/Communications Protection
This protect level restricts movement to the initial setting level, com-
munications setting level and advanced function setting level.
Default setting: 1
: Move to other levels possible
X: Move to other levels not possible
Setting Change Protection
This protect level protects setup from being changed by operating
the keys on the front panel.
Default setting: OFF
Input shift setting
Temperature
measured by
sensor
Temperature
display
0 (no shift)
100
°
C
100
°
C
10 (s10
°
C)
100
°
C
110
°
C
−
10 (shifted
−
10
°
C) 100
°
C
90
°
C
Level
Set value
0
1
2
3
Operation level
PV
PV/SP
Other
X
X
Adjustment level
X
X
X
Set
value
Initial setting level Communication
s setting level
Advanced
function setting
level
0
1
X
2
X
X
X
Operation/adjustment protection
Initial setting/communications protection
Setting change protection
Restricts displaying and modifying menus in operation,
adjustment, and manual control levels.
This protect level restricts movement to the initial setting,
communications setting, and advanced function setting
levels.
Protects changes to setups by operating the front panel
keys.
oapt
0
icpt
1
wtpt
off
Default setting: 0
:
Can be displayed and changed
: Can be displayed
X : Cannot be displayed and move to other levels not possible
Set value
Description
OFF
Setup can be changed by key operation.
ON
Setup cannot be changed by key operation.
(The protect level, can be changed.)