background image

Digital Temperature Controllers

 

E5GN

15

Communications Setting Level

Set the E5GN communications specifications in the communications setting level. For setting communications parameters, use the E5GN panel.
The communications parameters and their settings are listed in the following table.

Note: The highlighted values indicate default settings.

Before executing communications with the E5GN, set the communi-
cations unit No., baud rate, etc., through key operations as described
below. As for other operations, refer to relevant Operation Manual.

1. Press the 

 key for at least three seconds in the “operation

level.” The level moves to the “initial setting level.”

2. Press the 

 key for less than one second. The “initial setting

level” moves to the “communications setting level.”

3. Pressing the 

 key advances the parameters as shown in the

following figure.

4. Press the 

 or 

 keys to change the parameter setups.

Note: On the E5GN, the 

 Key is the 

 Key.

Set each communications parameter to match those of the communi-
cating personal computer.

Communications Unit No. (

u-no

)

When communicating with the host computer, the unit number must
be set in each Temperature Controller so that the host computer can
identify each Temperature Controller. The number can be set in a
range from 0 to 99 in increments of 1. The default setting is 1. When
using more than one Unit, be careful not to use the same number
twice. Duplicate settings will cause malfunction. This value becomes
valid when the power is turned OFF and ON again.

Baud Rate (

bps

)

Use this parameter to set the speed of communications with the host
computer. It can be set to one of the following values; 1.2 (1200 bps),
2.4 (2400 bps), 4.8 (4800 bps), 9.6 (9600 bps), and 19.2
(19200 bps).
This setting becomes valid when the power is turned OFF and ON
again.

Data Bits (

len

)

Use this parameter to change the communications data bit length to
7 bits or 8 bits.

Stop Bits (

sbit

)

Use this parameter to change the communications stop bit to 1 or 2.

Communications Parity (

prty

)

Use this parameter to set the communications parity to None, Even,
or Odd.

Troubleshooting

When an error occurs, an error code will be displayed on the No. 1 display. Check the contents of an error and take appropriate countermeasures.

Note 1. If the input is within the range for which control is possible but outside the displayable range (

1999 (

199.9) to 9999 (999.9)), 

 will

be displayed if the value is less than 

1999 (

199.9), and 

 will be displayed if it is greater than 9999 (999.9). Control output and alarm

output will operate normally for either of these displays. Refer to the relevant User’s Manual for details on the ranges for which control is
possible.

2. These errors are displayed only when the Controller is set to display the present value or the present value and the set value. They are not

displayed in other statuses.

Parameter

Displayed characters

Set (monitor) value

Set value

Communications unit No.

u-no

0 to 99

Baud rate

bps

1.2/2.4/4.8/9.6/19.2 (kbps)

Data bits

len

7/8 (bit)

Stop bits

sbit

1/2

Parity

prty

None, even, odd

0.

1

 to 99

1.2/2.4/4.8/

9.6

/19.2

7

/8 (bit)

1/

2

 (bit)

none

/

eVen

/

odd

Baud rate

Data bits

Stop bits

Communications  
parity

Communications 
unit No.

u-no

1

bps

9.6

len

7

sbit

2

prty

e?en

No.1 display

Contents

Countermeasure

Output status

Control output

Alarm output

s.err

 (S. Err)

Input error (See note.)

Check that the input wiring is correct, that there is no discon-
nection or short-circuit, and that the input type is correct. 
(Thermocouple input short-circuits cannot be detected.)

OFF

Handled as ab-
normally high 
temperature

A/D converter error
(See note.)

After noting the error, reset the power. If the display does not 
change, replacement is necessary. If the error is removed, it 
is possible that the original error was caused by noise. Check 
that there are no possible sources of noise.

OFF

OFF

e111

 (E111)

Memory error

Reset the power. If the display does not change, replacement 
is necessary. If the error is removed, it is possible that the 
original error was caused by noise. Check that there are no 
possible sources of noise.

OFF

OFF

h.err

 (H. Err)

HB error (See note.)

OFF

OFF

cccc

cccc

Summary of Contents for E5GN

Page 1: ...At the end of this document you will find links to products related to this catalog You can go directly to our shop by clicking HERE HERE ...

Page 2: ...ations Blank No communications function 03 RS 485 4 Input type TC Thermocouple P Platinum resistance thermometer 5 CompoWay F serial communications Blank Not available FLK CompoWay F serial communications Ordering Information Standard Models Note 1 If the heating cooling function is used ALM1 will be used for control output and so alarm output will not be available 2 Control output 2 for heating c...

Page 3: ...R S B Platinum resistance thermometer Pt100 JPt100 Infrared temperature sensor 10 to 70 C 60 to 120 C 115 to 165 C 140 to 260 C Voltage input 0 to 50 mV Control output Relay output SPST NO 250 VAC 2 A resistive load electrical life 100 000 operations Voltage output 12 VDC PNP max load current 21 mA with short circuit protection circuit Alarm output SPST NO 250 VAC 1 A resistive load electrical lif...

Page 4: ...0 0 1700 0 1800 100 70 0 120 0 165 0 260 0 0 17 400 0 199 9 18 400 0 199 9 Pt100 JPt100 Input type Platinum resistance thermometer input Platinum resistance thermometer Name Set value Thermocouple Thermocouple input Analog input 0 to 50 mV Input type Name Set value Temperature range Temperature range Applicable standards by input type are as follows K J T E N R S B JIS C1602 1995 L Fe CuNi DIN 437...

Page 5: ...gative 0 Alarm function OFF Output OFF 1 1 Upper and lower limit deviation 2 2 Upper limit deviation 3 Lower limit deviation 4 1 Upper and lower limit range deviation 3 5 1 Upper and lower limit with standby se quence deviation 4 6 Upper limit with standby sequence de viation 7 Lower limit with standby sequence de viation 8 Absolute value upper limit 9 Absolute value lower limit 10 Absolute value ...

Page 6: ...iod 500 ms Insulation resistance 20 MΩ min at 500 VDC megger Dielectric strength 2000 VAC 50 or 60 Hz for 1 min between different charging terminals Vibration resistance 10 to 55 Hz 10 m s2 for 2 hours each in X Y and Z directions Shock resistance 300 m s2 3 times each in 3 axes 6 directions relay 100 m s2 Weight Approx 90 g Mounting bracket approx 10 g Degree of protection Front panel NEMA4X for ...

Page 7: ...mission path connection Multiple points Communications method RS 485 two wire half duplex Synchronization method Start stop synchronization Baud rate 1 200 2 400 4 800 9 600 19 200 bps Transmission code ASCII Data bit length see note 7 or 8 bits Stop bit length see note 1 or 2 bits Error detection Vertical parity none even odd Frame check sequence FCS with SYSWAY Block check character BCC with Com...

Page 8: ...ads still attached Insert the Controller through the hole in the panel from the front and push the adapter on from the rear Push the adapter up to the back of the panel ensuring that the controller is pushed all the way in removing any gap between the Controller panel and adapter Finally use the two screws on the adapter to secure the unit in place To mount the E5GN so that it is waterproof insert...

Page 9: ...displayed when the dis play unit parameter is set to a temperature In dication is determined by the currently selected temperature unit parameter set value When this parameter is set to C c is displayed and when set to F f is displayed Displays the set point manipulated variable or set value setup of the parameter Each press of this key increases values displayed on the No 2 display Holding down t...

Page 10: ...l cannot be modified Communications Setting Level To select this level press the key once for less than one second in the initial setting level When the communications function is used set the communications conditions in this level Communicating with a personal computer host computer allows set points to be read and written and manipulated variables to be monitored Advanced Function Setting Level...

Page 11: ...nt level Less than 1 second 1 second min Less than 1 second 1 second min Calibration level Protect level key 1 second min key key key key key key key Control in progress Control stopped Level change 3 seconds min Initial setting level Communica tions setting level Password input set value 169 Advanced function setting level Password input set value 1201 Display flashes when key pressed 3 seconds m...

Page 12: ...to 1700 C 0 to 3000 F B 11 100 to 1800 C 300 to 3200 F Infrared temperature sensor ES1B 10 to 70 C 12 0 to 90 C 0 to 190 F 60 to 120 C 13 0 to 120 C 0 to 240 F 115 to 165 C 14 0 to 165 C 0 to 320 F 140 to 260 C 15 0 to 260 C 0 to 500 F Analog input 0 to 50 mV 16 One of following ranges depending on the re sults of scaling 1999 to 9999 199 9 to 999 9 Input Type Specifications Set Value Input Temper...

Page 13: ...ff prlt 3 sero off cjc on O O c c u no 1 bps 9 6 len 7 sbit 2 prty e en ST stable range Input error output Cold junction compensation method MB command logic switching Move to calibration level Initial Setting Level Input type Temperature unit C F SP upper limit Scaling upper limit PID ON OFF Scaling lower limit Decimal point Standard or heating cooling Moved by setting password 169 Communications...

Page 14: ... for at least 1 s Press the O M keys for at least 3 s Display flashes Protect Level Operation adjustment protection Restricts displaying and modifying menus in operation adjustment and manual control levels Initial setting communications protection This protect level restricts movement to the initial setting communications setting and advanced function setting levels Setting change protection Prot...

Page 15: ...mperature measured by sensor Temperature display 0 no shift 100 C 100 C 10 shifted 10 C 100 C 110 C 10 shifted 10 C 100 C 90 C Level Set value 0 1 2 3 Operation level PV PV SP Other X X Adjustment level X X X Set value Initial setting level Communication s setting level Advanced function setting level 0 1 X 2 X X X Operation adjustment protection Initial setting communications protection Setting c...

Page 16: ...stop bit to 1 or 2 Communications Parity prty Use this parameter to set the communications parity to None Even or Odd Troubleshooting When an error occurs an error code will be displayed on the No 1 display Check the contents of an error and take appropriate countermeasures Note 1 If the input is within the range for which control is possible but outside the displayable range 1999 199 9 to 9999 99...

Page 17: ...imited energy See note 1 d Caution To reduce the risk of fire or electric shock do not interconnect the outputs of different Class 2 circuits See note 2 If the output relays are used past their life expectancy contact fusing or burning may occasionally occur Always consider the application conditions and use the output relays within their rated load and electrical life expectancy The life expectan...

Page 18: ...nd must be marked as a disconnecting means for this unit 13 Always turn OFF the power supply before pulling out the interior of the product and never touch nor apply shock to the terminals or electronic components When inserting the interior of the product do not allow the electronic components to touch the case 14 Do not use paint thinner or similar chemical to clean with Use standard grade alcoh...

Page 19: ...e The E5GN can be replaced by removing the terminal plate 1 Press down hard on the fasteners on both sides of the terminals to unlock the terminal plate and pull upwards 2 Draw out the terminal plate as it is 3 Before you insert the terminal plate again make sure that the pins match the positions of the holes in the terminal plate Wiring Precautions Connect the terminals as specified below The exp...

Page 20: ...Digital Temperature Controllers E5GN 19 ...

Page 21: ...codes or regulations that apply to the combination of products in the customer s application or use of the products Take all necessary steps to determine the suitability of the product for the systems machines and equipment with which it will be used Know and observe all prohibitions of use applicable to this product NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPE...

Page 22: ...and datasheets of all products Estimated delivery time enquiry in real time Logistics systems for the shipment of materials almost anywhere in the world Purchasing management order record and tracking of shipments To access the product click on the green button Product Code Reference Product link Industrial Career Final Push buttons Decade 113802 NRT C Buy on EAN ...

Reviews: