![background image](http://html.mh-extra.com/html/omron/e5gn/e5gn_manual_742661012.webp)
Digital Temperature Controllers
E5GN
11
Input Type
When using a thermocouple input type, follow the specifications listed in the following table.
Note: The initial settings are: 0:
−
200 to 1300
°
C/
−
300 to 2300
°
F.
When using the platinum resistance thermometer input type, follow the specifications listed in the following table.
Note: The initial settings are: 0: Pt100
−
200 to 850
°
C/
−
300 to 1500
°
F.
Parameters
Parameters related to setting items for each level are marked in
boxes in the flowcharts and brief descriptions are given as required.
At the end of each setting item, press the mode key to return to the
beginning of each level.
Input Type
Specifications
Set Value
Input Temperature Range
Thermocouple input type
Thermocouple
K
0
−
200 to 1300 (
°
C)
/
−
300 to 2300 (
°
F)
1
−
20.0 to 500.0 (
°
C)
/0.0 to 900.0 (
°
F)
J
2
−
100 to 850 (
°
C)
/
−
100 to 1500 (
°
F)
3
−
20.0 to 400.0 (
°
C)
/0.0 to 750.0 (
°
F)
T
4
−
200 to 400 (
°
C)
/
−
300 to 700 (
°
F)
17
−
199.9 to 400.0 (
°
C) /
−
199.9 to 700 (
°
F)
E
5
0 to 600 (
°
C)
/0 to 1100 (
°
F)
L
6
−
100 to 850 (
°
C)
/
−
100 to 1500 (
°
F)
U
7
−
200 to 400 (
°
C)
/
−
300 to 700 (
°
F)
18
−
199.9 to 400.0 (
°
C) /
−
199.9 to 700 (
°
F)
N
8
−
200 to 1300 (
°
C)
/
−
300 to 2300 (
°
F)
R
9
0 to 1700 (
°
C)
/0 to 3000 (
°
F)
S
10
0 to 1700 (
°
C)
/0 to 3000 (
°
F)
B
11
100 to 1800 (
°
C)
/300 to 3200 (
°
F)
Infrared temperature sensor
ES1B
10 to 70
°
C
12
0 to 90 (
°
C)
/0 to 190 (
°
F)
60 to 120
°
C
13
0 to 120 (
°
C)
/0 to 240 (
°
F)
115 to 165
°
C
14
0 to 165 (
°
C)
/0 to 320 (
°
F)
140 to 260
°
C
15
0 to 260 (
°
C)
/0 to 500 (
°
F)
Analog input
0 to 50 mV
16
One of following ranges depending on the re-
sults of scaling: 1999 to 9999, 199.9 to 999.9
Input Type
Specifications
Set Value
Input Temperature Range
Platinum resistance thermom-
eter input type
Platinum resistance thermom-
eter
Pt100
0
−
200 to 850 (
°
C)
/
−
300 to 1500 (
°
F)
1
−
199.9 to 500.0 (
°
C) /
−
199.9 to 900.0 (
°
F)
2
0.0 to 100.0 (
°
C)
/0.0 to 210.0 (
°
F)
JPt100
3
−
199.9 to 500.0 (
°
C) /
−
199.9 to 900.0 (
°
F)
4
0.0 to 100.0 (
°
C)
/0.0 to 210.0 (
°
F)
Calibration level
Control stops.
Initial setting level
Less than 1 second
Power ON
Operation level
Protect level
Control in progress
Control stopped
Adjustment level
Level change
Less than 1 second
key
key
key
key
key
+ key
+ key
+ key
+ key
1 second
min.
3 seconds
min.
1 second
min.
Display flashes when key held
down for more than 1 second
.
Communica-
tions setting
level
Password input
set value "
−
169"
Advanced function
setting level
Password input
set value "1201"
Display flashes
when key pressed.
3 seconds
min.
The time taken to
move to the protect
level can be adjusted
by changing the "Move
to protect level time"
setting.
1 second
min.
25
100
25
100