4
E5CJ (Simple and Standard Models)
48 X 48mm
Type
Simple model type
Standard model
type
Alarm
---
2 replay output points with the same
common. (see note 1)
Heater burnout alarm
---
Yes (see note)
Event input
---
1 point (set point
selection)
Model
Control output
Relay output
E5CJ-R
E5CJ-R2
E5CJ-R2HB
Voltage output
E5CJ-Q
E5CJ-Q2
E5CJ-Q2HB
Current output
E5CJ-C
E5CJ-C2
E5CJ-C2B
Note No heater burnout alarm is output if a current control output is used.
Communications
RS-232C
RS-422
RS-485
Model
E53-J01
E53-J02
E53-J03
Note For details, refer to the
E5AJ/E5EJ Communications Manual (Z102).
1-3
Specifications
1-3-1 Ratings
E5
J
Item
Specification
Supply voltage
100 to 240 VAC, 50 or 60 Hz
24 V AC/DC,
50 or 60 Hz
Operating voltage range
85 to 110% of supply voltage
Power consumption
E5AJ
10 VA (at 100 VAC) to
14 VA (at 240 VAC)
10 VA (at 24 VAC)
6 W (at 24 VDC)
E5EJ
10 VA (at 100 VAC) to
14 VA (at 240 VAC)
6
(at
C)
E5CJ
10 VA (at 100 VAC) to
12 VA (at 240 VAC)
Input
Thermocouples (K, J, T, L, U, and N) and platinum
resistance thermometers (JPt100 and Pt100)
CT input
Dedicated CT (E54-CT1 or E54-CT3)
Control output
E5AJ/E5EJ
Replaceable Output Unit (sold separately)
E5CJ
Relay output
SPST-NO, 3 A at 250 VAC (resistive load)
Voltage output
20 mA at 12 VDC (with short-circuit protection)
Current output
4 to 20 mA DC with a load of 600
Ω
max. and a
resolution of approx. 2600
Control mode
ON/OFF or advanced PID with fuzzy self-tuning and
auto-tuning
Alarm output
E5AJ/E5EJ
2 SPST-NO relay output points, 3 A at 250 VAC
(resistive load)
E5CJ
2 SPST-NO relay output points (with the same common),
1 A at 250 VAC (resistive load)
Setting method
Digital setting with Up Key and Down Key
Communications Boards
Specifications
Section 1-3