56
9-1
Engineering Level
To go to engineering level, set pin 4 of the internal function switch of the E5
J to
ON before turning the E5
J on. After this setting, set pin 4 of the internal func-
tion switch to OFF.
Set pin 4 of the
function switch to
ON.
This display will appear.
Turn on the E5
J.
9-2
Engineering Level Parameter List
The following is a list of engineering level parameters.
Display
Name
Setting range
Setting before
shipping
User’s remarks
d-U
°
C/
°
F selection
c
:
°
C
f
:
°
F
c
LEn
Data bit length
7: Data length of 7 bits
8: Data length of 8 bits
7
PrtY
Parity check
none
: No parity
eUen
: Even
odd
: Odd
eUen
Sbit
Stop bit length
1: 1 bit
2: 2 bits
2
15.0
S.t-b
Stable range
0.1 to 999.9
°
C/
°
F
15.0 (27.0)
ALFA
Alpha
0.00 to 1.00
0.65
rEt
Automatic return of
display mode
0 to 99 s
0: No automatic return
0
rESt
Standby sequence reset
method
0: Reset method 0
1: Reset method 1
0
in-S
Input shift display
off
: Not displayed
on
: Displayed
off
ALH1
Alarm 1 hysteresis
0.1 to 999.9
°
C/
°
F
0.2 (0.4)
ALH2
Alarm 2 hysteresis
0.1 to 999.9
°
C/
°
F
0.2 (0.4)
SL-L
Set point lower limit
value
Set range lower limit to
set point upper limit
value (see note 1).
(
°
C/
°
F)
–200 (–300)
Engineering Level Parameter List
Section 9-2