6
1-3-2 Characteristics
E5
J
Item
Specification
Indication accuracy
±
0.5% or
±
1
°
C whichever is larger
±
1 digit max.
Thermocouple K, T, or N at a temperature of –100
°
C; thermocouple U at
±
2
°
C
±
1
digit max.
Hysteresis (for ON/OFF control)
0.1 to 999.9
°
C/
°
F (in units of 0.1
°
C/
°
F)
Proportional band
0.1 to 999.9
°
C/
°
F (in units of 0.1
°
C/
°
F)
Integral time
0 to 3999 s (in units of 1 s)
Derivative time
0 to 3999 s (in units of 1 s)
Control period
Relay or voltage output:1 to 99 s (in units of 1 s)
Manual reset value (I = 0)
0.0 to 100.0% (in units of 0.1%)
Alarm setting range
With K, J, L, or N input: –1999 to 9999
°
C/
°
F (in units of 1
°
C/
°
F)
With JPt100, Pt100, T, or U input: –199.9 to 999.9
°
C/
°
F (in units of 0.1
°
C/
°
F)
Sampling period
500 ms
Output refresh period
500 ms
Display refresh period
500 ms
Insulation resistance
20 M
Ω
min. at 500 VDC (measured with an Output Unit)
Dielectric strength
2000 VAC, 50/60 Hz for 1 min. between charged terminals different from each other
in polarity
Vibration
i
Malfunction
10 to 55 Hz, 9.8 m/s
2
(1G) 10 min. in X, Y, and Z directions
resistance
Destruction
10 to 55 Hz, 19.6 m/s
2
(2G) 2 hr. in X, Y, and Z directions
Shock resistance
Malfunction
196 m/s
2
(20G) 3 times each in 3-axis 6 directions (98 m/s
2
(10G) for the relay)
Destruction
294 m/s
2
(30G) 3 times each in 3-axis 6 directions
Weight
E5AJ
Approx. 360 g; mounting bracket: approx. 65 g
E5EJ
Approx. 280 g; mounting bracket: approx. 65 g
E5CJ
Approx. 170 g; adapter: approx. 10 g
Enclosure rating
Front panel:
E5AJ/E5EJ: IEC standard IP54
E5CJ: IEC standard IP50 (see note 1)
Rear case:
IEC standard IP20
Terminals:
IEC standard IP00
Memory Protection
Non-volatile memory
EMC
Emission Enclosure:
EN55011 Group 1 class A
Emission AC Mains:
EN55011 Group 1 class A
Immunity ESD:
EN61000-4-2: 4 kV contact discharge (level 2)
8 kV air discharge (level 3)
Immunity RF-interference:
ENV50140:
10 V/m (amplitude modulated,
80 MHz to 1 GHz) (level 3)
10 V/m (pulse modulated,
900 MHz)
Immunity Conducted Disturbance:
ENV50141:
10 V (0.15 to 80 MHz) (level 3)
Immunity Burst:
EN61000-4-4: 2 kV power-line (level 3)
2 kV I/O signal-line (level 4)
Approved standards
UL1092, CSA C22.2 No. 142
Conforms to EN50081-2, EN50082-2, EN61010-1 (IEC1010-1) (see note 2)
Conforms to VDE0106/part 100 (Finger Protection), when the separately-ordered
terminal cover is mounted.
Note
1. The model numbers of the exclusive watertight covers conforming to IP66,
NEMA4 are as follows:
For E5AJ: Y92A-96N; For E5CJ: Y92A-48N; For E5EJ: Y92A-49N
2. Basic insulation is between the input and output.
Specifications