Setup Mode
Section 4-5
39
4-5-3-3
Set_Permanent_Configuration
Function
Store the ID code and I/O code for a projected slave as permanent
configuration data in the master’s non-volatile memory.
Command Code
3 (
0011
)
Command Argument 1
Slave address (2 digits BCD)
Permanent Configuration Data for slave [Command Argument 1].
1 byte hexadecimal code, representing I/O Code and ID Code.
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
Command Argument 2
IR m+1
I/O
ID
ID Code
I/O Code
See Appendix B, AS-Interface Slave Profiles, for a list of ID codes and I/O
codes.
Command Status
1
Command processed.
2
Error in processing the command
(invalid argument value or EEPROM write error).
other
Master is busy
Command Return Value
Not applicable (set to 00)
Example
Define the projected configuration data for the slave with address 23 as a
standard 2-input, 2-output slave. (I/O Code 3, ID Code 0)
Command
IR101 IR100
Response
IR001
X X X D Master in Setup Mode
Send ’No_Command’
-
-
-
-
-
-
0 2
(X = previous data)
0 0 0 D Master Ready
Send Command
-
-
3 0
2 3 3 2
0 0 1 D OK
Summary of Contents for CQM1-ARM21
Page 1: ...CQM1 ARM21 AS Interface Master Unit OPERATION MANUAL Cat No W357 E1 1...
Page 2: ......
Page 3: ...CQM1 ARM21 AS Interface Master Unit Operation Manual Produced April 1999...
Page 4: ...iv...
Page 6: ...vi...
Page 8: ...viii...
Page 10: ...x...
Page 30: ...AS Interface Network Installation Section 2 3 16...
Page 38: ...Performance Section 3 3 24...
Page 62: ...Setup Mode Section 4 5 48...
Page 76: ...62...
Page 80: ...66...
Page 84: ......