Overall Specifications
Section 3-1
18
3-1 Overall Specifications
Model code
CQM1-ARM21
Max. number of units per CPU
One
Master Unit mounting position
Recommended
: rightmost I/O unit position of the CQM1 system
Settings
Switches:
: IR channel allocation
Operation Mode (Protected/Configuration)
Store Configuration
Displays
Unit status
: RUN
(green LED)
Startup, Normal operation
ERR
(red LED)
Failure, illegal operation
Network status
: APF
(red LED)
AS-Interface Power Fail
CER
(red LED)
Configuration Error
AUP
(yellow LED)
Auto-programming available
CM
(yellow LED)
Configuration Mode
Slave status
: 0~15, +16
(yellow LEDs)
Slave configured / active
External connectors
2 x ASI+, 2 x ASI-, M3 screw terminals, detachable terminal block.
No. of DM settings
1 words of unit setup information (DM 6604)
No. of IR words
Switch selectable.
Minimum: 3 words in + 3 words out
Maximum: 8 words in + 8 words out
Max. No. of Slaves per Master
Unit
Switch selectable.
With minimum IR words : 11 slaves
With maximum IR words : 31 slaves
Status information in PLC
Operation Mode flag
System Error flag
Normal Operation flag
Configuration OK flag
Communication specification
European Standard EN 50295.
AS-Interface Complete Specification V 2.04.
AS-Interface Master Profiles V 1.5, profile M0.
Prüfungsordnung für AS-Interface Master V 1.1.
Certification No. 22701
Network configuration
Built-in configurator functions:
•
Get_Permanent_Configuration
•
Set_Permanent_Configuration
•
Read_Actual_Configuration
•
Change_Slave_Address
•
Get_Permanent_Parameter
•
Set_Permanent_Parameter
•
Read_Parameter
•
Write_Parameter
Current consumption
maximum 300 mA at 5 V DC (from the PLC power supply)
maximum 100 mA at 30.5 V DC (from the AS-Interface line)
Storage temperature
-20 to +75
°
C
Operating temperature
0 to +55
°
C
Operating humidity
10% to 90% (non-condensing)
Conformance to EMC- and
environmental standards
EN 50081-2
EN 61131-2
Weight
Approx. 200 g including front cover and terminal block
Summary of Contents for CQM1-ARM21
Page 1: ...CQM1 ARM21 AS Interface Master Unit OPERATION MANUAL Cat No W357 E1 1...
Page 2: ......
Page 3: ...CQM1 ARM21 AS Interface Master Unit Operation Manual Produced April 1999...
Page 4: ...iv...
Page 6: ...vi...
Page 8: ...viii...
Page 10: ...x...
Page 30: ...AS Interface Network Installation Section 2 3 16...
Page 38: ...Performance Section 3 3 24...
Page 62: ...Setup Mode Section 4 5 48...
Page 76: ...62...
Page 80: ...66...
Page 84: ......