![Omron CJ1W-PRT21 Operation Manual Download Page 91](http://html1.mh-extra.com/html/omron/cj1w-prt21/cj1w-prt21_operation-manual_742353091.webp)
3-23
3 Data Exchange with the CPU Unit
CJ-series PROFIBUS Slave Unit Operation Manual for NJ-series CPU Unit (W510)
3-
7 Device V
ariable
s for C
J-series U
n
it
(Co
n
fig
u
rat
ion)
3
3-
7-2 Slave Ou
tput Dat
a
(*_SlvOutS
ta
)
Name of Device Variable for CJ-
series Unit
Type
R/W
Description
Function
*_SlvOutAreaCode
USINT
R
Output area
code
Output area code (data from Master to Slave
CPU). Indicates the area to which the unit will
write PROFIBUS output data received from its
master.
00: No assignment made
01: CIO area (CIOxxxx)
03: DM area (Dxxxxx)
04: Work area (Wxxx)
05: Holding area (Hxxx)
08: EM bank 0 (E0-xxxxx)
09: EM bank 1 (E1-xxxxx)
10: EM bank 2 (E2-xxxxx)
11: EM bank 3 (E3-xxxxx)
12: EM bank 4 (E4-xxxxx)
13: EM bank 5 (E5-xxxxx)
14: EM bank 6 (E6-xxxxx)
15: EM bank 7 (E7-xxxxx)
16: EM bank 8 (E8-xxxxx)
17: EM bank 9 (E9-xxxxx)
18: EM bank A (EA-xxxxx)
19: EM bank B (EB-xxxxx)
20: EM bank C (EC-xxxxx)
*_SlvOutHoldBusErr
BOOL
R
Data hold on
PROFIBUS fail
FALSE: Clear data to Host CPU
TRUE: Hold data to Host CPU
Indicates how the slave will behave on the Host
CPU I/O bus in the event the PROFIBUS data
exchange communication fails (e.g. comm.
watchdog timeout).
*_SlvOutIntelMd
BOOL
R
Outputs Intel
mode
FALSE: Motorola (high byte first)
TRUE: Intel (low byte first)
Outputs Motorola/Intel mode
Indicates how the data bytes of a PROFIBUS
data exchange telegram are mapped to Host
CPU data words.
The values in
*_SlvOutSta
are provided by the
PROFIBUS master's Set_Prm telegram, and
indicated in
*_SlvOutSta
after both the Set_Prm
and Chk_Cfg telegrams have been accepted.
15 14 13 12 11 10
9
8
7
6
5
4
3
2
1
0
*_SlvOutSta
*_SlvOutStartAdr