![Omron CJ1W-PRT21 Operation Manual Download Page 60](http://html1.mh-extra.com/html/omron/cj1w-prt21/cj1w-prt21_operation-manual_742353060.webp)
2 Nomenclature and Installation
2-4
CJ-series PROFIBUS Slave Unit Operation Manual for NJ-series CPU Unit (W510)
The fieldbus connector is a 9-pin female sub-D connector, as recommended in the PROFIBUS stan-
dard EN50170 Vol.2.
Data Signal
The PROFIBUS User Group recommends the following color coding for the data signal lines:
A-line = Green B-line = Red
These data signal lines must be connected to the corresponding signal terminals or pins at the mas-
ter unit and other stations (i.e. A to A, B to B). For detailed PROFIBUS-DP cable requirements (see
).
RTS
The signal RTS (TTL signal relative to DGND) is meant for the direction control of repeaters in case
repeaters without self control capability are used
VP, DGND
The signals VP and DGND are meant to power an externally
mounted bus terminator.
The powering of the 220
termination resistor ensures a
defined idle state potential on the data lines. To ensure proper
functioning up to the highest baud rate, each bus segment has
to be terminated at both ends of the cable.
2-1-4
PROFIBUS Connector
Pin No.
Signal
Description
1
Shield
Shield / functional ground
2
-
-
3
B-line
Data signal
4
RTS
Direction control signal for repeaters (TTL)
5
DGND
Data ground
6
VP
Supply voltage for terminator resistance (+5 VDC)
7
-
-
8
A-line
Data signal
9
-
-
B-line
A-line
DGND
390
220
390
VP