![Omron CJ1W-PRT21 Operation Manual Download Page 114](http://html1.mh-extra.com/html/omron/cj1w-prt21/cj1w-prt21_operation-manual_742353114.webp)
Appendices
A-6
CJ-series PROFIBUS Slave Unit Operation Manual for NJ-series CPU Unit (W510)
DM + 5 to DM + 7 (Slave Input Settings)
The device variable for CJ-series Unit that corresponds to all bits of the words in DM+5 to DM + 7
are as follows:
The device variables for CJ-series Units that correspond to bits 0 to 15 of a each word in DM + 5 to
DM + 7 are as follows:
DM + 4
0 to 15
*_SlvOutDatLen
Output data length
CJ-series I/O memory address
NJ-series device variables for CJ-series Unit
Word address
Bit
Variable name
Description
DM + 5 to DM + 7
0 to 15 for each
word
*_SlvInSta
Slave Input Settings
CJ-series I/O memory address
NJ-series device variables for CJ-series Unit
Word address
Bit
Variable name
Description
DM + 5
0 to 7
*_SlvInAreaCode
Input area code
8
*_SlvInProgCont
Continue in PROGRAM mode
9
*_SlvInProgExit
Exit in PROGRAM mode
10
*_SlvInFatlCont
Continue on fatal error
11
*_SlvInFatlExit
Exit on fatal error
12
*_SlvInIntelMd
Inputs Intel mode
13 and 14
Undefined
Reserved by system
15
*_SlvInclPLCSta
Include PLC status in input data
DM + 6
0 to 15
*_SlvInStartAdr
Input start address
DM + 7
0 to 15
*_SlvInDatLen
Input data length
CJ-series I/O memory address
NJ-series device variables for CJ-series Unit
Word address
Bit
Variable name
Description