CJ-series PROFIBUS Slave Unit Operation Manual for NJ-series CPU Unit (W510)
4-3 Eve
n
t L
o
g
s
4
4-
3-2 Er
ror
Table
Event code
Event name
Meaning
Assumed cause
Level
Maj Prt Min Obs Info
38180000 hex
Parame-
ter/Configu-
ration Error
The Slave has
received incorrect
parameter and/or
configuration mes-
sages from a Mas-
ter Unit.
Parameter Error can be caused by:
•
Invalid standard parameter settings (valid
settings are described in the PROFIBUS
standard).
•
Invalid user parameter settings (allowed
settings are described in the GSD file of
the Unit).
•
Incorrect start addresses for I/O data in
the host CPU system. If one of them is
invalid, parameter error is indicated, plus
*_StartAdrInErr
and/or
*_StartAdrOutErr
will be set.
Configuration Error can be caused by:
•
Input - or output length > 100 words
•
Input + output length > 180 words
•
Input length < 2 words while CPU status
should be included.
•
Input - or output length causing errors
indicated by
*_EndAdrInErr,
*_EndAdrOutErr
X