CJ-series PROFIBUS Slave Unit Operation Manual for NJ-series CPU Unit (W510)
; (0991860-9A).
Software_Release = "V2.0" ; Software revision 2.0.
;
Bitmap_Device = "OC0602_R" ; Bitmap RUNNING
Bitmap_Diag = "OC0602_D" ; Bitmap DIAGNOSTIC
Bitmap_SF = "OC0602_S" ; Bitmap SPECIAL
;
; Specific implementation information *****************************************/
;
Implementation_type = "SPC3" ; DP protocol.
; handled by SPC3.
Redundancy = 0 ; Redundancy NOT supported.
Repeater_Ctrl_Sig = 2 ; Supported, TTL level
24V_Pins = 0 ; No external 24 Volt input.
;
Set_Slave_Add_supp = 0 ; Station address is set
; through hardware address
; selectors.
; Media access information ****************************************************/
; Automatic baud rate select
Auto_Baud_supp = 1 ; (SPC3 specific feature).
; Supported baud rates:
9.6_supp = 1 ; 9600 Baud
19.2_supp = 1 ; 19.2 kBaud
45.45_supp = 1 ; 45.45 kBaud
93.75_supp = 1 ; 93.75 kBaud
187.5_supp = 1 ; 187.5 kBaud
500_supp = 1 ; 500 kBaud
1.5M_supp = 1 ; 1.5 MBaud
3M_supp = 1 ; 3 MBaud
6M_supp = 1 ; 6 MBaud
12M_supp = 1 ; 12 MBaud
; Max. response times:
MaxTsdr_9.6 = 60 ; 60 Tbit = 6.25 msec.
MaxTsdr_19.2 = 60 ; 60 Tbit = 3.125 msec.
MaxTsdr_45.45 = 60 ; 60 Tbit = 1.32 msec.
MaxTsdr_93.75 = 60 ; 60 Tbit = 640 usec.
MaxTsdr_187.5 = 60 ; 60 Tbit = 320 usec.
MaxTsdr_500 = 100 ; 100 Tbit = 200 usec.
MaxTsdr_1.5M = 150 ; 150 Tbit = 100 usec.
MaxTsdr_3M = 250 ; 250 Tbit = 83 usec.
MaxTsdr_6M = 450 ; 450 Tbit = 75 usec.
MaxTsdr_12M = 800 ; 800 Tbit = 67 usec.
;
Min_Slave_Intervall = 5 ; Minimum slave interval =
; 0.5 msec.
;
; DP-slave information ********************************************************/
;
Freeze_Mode_supp = 1 ; Freeze mode supported.
Sync_Mode_supp = 1 ; Sync mode supported.
Fail_Safe = 1 ; Fail safe supported.
;