Appendices
A-14
CJ-series PROFIBUS Slave Unit Operation Manual for NJ-series CPU Unit (W510)
A-3
Parameterization by the PROFIBUS
Master Unit
The parameterisation of the passive stations by the master is first done in the start-up phase of the
PROFIBUS-DP system and is also possible in the data exchange mode. The first 10 bytes of parameter
data are defined by the PROFIBUS standard the additional 9 bytes are device specific. The format of
the parameters is depicted in the following table.
Although the Unit does not support PROFIBUS-DP/V1 functionality, the three DPV1 status bytes are
reserved in the Set_Prm message. Only the 2 indicated bits can be set by the user.
Byte
Bit Position
Designation
7
6
5
4
3
2
1
0
0
Lock
Req
Unlock
Req
Sync
Req
Freeze
Req
WD on
Res
Res
Res
Station status
1
00 to FF
WD_Fact_1
2
00 to FF
WD_Fact_2
3
MinTSDR
4
00 to FF
Ident_Number_High
5
00 to FF
Ident_Number_Low
6
00 to FF
Group_Ident
7
0
Fail
Safe
0
0
0
WD
1 ms
0
0
DPV1_Status_1
8
0
0
0
0
0
0
0
0
DPV1_Status_2
9
0
0
0
0
0
0
0
0
DPV1_Status_3
10
0
0
0
Motor-
ola/
Intel
0
0
0
Reset/
Hold
Output options*
11
codes to indicate CIO, H, W, D, E0 to EC
Output Area*
12
00 to 7F
Out start address High*
13
00 to FF
Out start address Low*
14
Incl. Sta-
tus
0
0
Motor-
ola/
Intel
Action Fatal Error
(Continue/Stop)
Action PRGmode
(Continue/Stop)
Input options*
15
codes to indicate CIO, H, W, D, E0-EC
Input Area*
16
00 to 7F
In start address High*
17
00 to FF
In start address Low*