2
.Installation and connection
12
Always use the support angles.
(5) Place the UPS on the support angles and push it completely into the rack
, and use the
included EIA/JIS rack fixing screws (M5) and spacers to securely fasten the ear brackets to
the server rack.
The screw hole positions are as follows.
• EIA rack : Topmost and bottommost ones on the front
• JIS rack : One at the second from the top on the front
Push completely in
Use the unit
fixing screws to
fasten
Note
The batteries for BU5002RWLG are in a separate package. Attach the batteries
to the unit before installation. For the attachment procedure, refer to "6-2
Replacing the battery".