BU
2002
RWLG/BU
3002
RWLG/BU
5002
RWLG
2
11
(3) For EIA standard-compliant installation, use the included EIA rack fixing nuts (M5) and EIA/
JIS rack fixing screws (M5) to securely fasten the front and the back of the rack rails to the
server rack.
The screw hole positions are as follows.
• EIA rack : Topmost one for the front, topmost and bottommost ones for the rear
• JIS rack : One at the second from the bottom for both front and rear
(4) Use the 8 included bracket fixing screws (M4) (2 sets of 4 screws) to securely fasten the ear
brackets and unit guide rails to the left and right sides of the UPS.
(Installation is possible without removing the handles on the sides of BU5002RWLG; do not
remove them.)
The support angles cannot be attached to special EIA/JIS racks.
(2) Adjust the length of support angles to suit the server rack, and then securely tighten the
screws that were half-tightened in step 1.
Rack fixing screws
Adjust the length to
suit the server rack
and tighten securely.