background image

UPS user manual

Utilizzo dell’UPS

 

Rev. 

Descrizione 
Description 

Data 
Date 

Emesso 

Issued 

Approvato 

Approved 

Lingua 
Language 

Pagina 
Page 

di Pag. 
of Pag. 

Revisione (VR60-14) / Revision (VR60-14)

 

15.01.15 

E. Biancucci 

F. Berti 

E/I 1 96 

 

 

 

 

 

 

 

 

 

 

Codice / Code 

 

 

 

 

 

OMD10082

 

UPS USER MANUAL 

UTILIZZO DELL’UPS 

Index / Indice 

ENGLISH LANGUAGE ............................................................................... 5

 

1

 

SCOPE ................................................................................................ 6

 

2

 

SAFETY RULES AND WARNINGS .................................................... 7

 

3

 

GENERAL UPS DESCRIPTION .......................................................... 8

 

3.1

 

TYPOLOGY ..................................................................................................................  8

 

3.2

 

SYSTEM DESCRIPTION ............................................................................................. 8

 

3.2.1

 

Rectifier ............................................................................................................... 8

 

3.2.2

 

Inverter ................................................................................................................. 9

 

3.2.3

 

Battery and battery charger ............................................................................... 9

 

3.2.4

 

Static bypass ....................................................................................................... 9

 

3.2.5

 

Manual bypass .................................................................................................... 9

 

3.3

 

OPERATING STATUS ............................................................................................... 10

 

3.3.1

 

Normal operation .............................................................................................. 10

 

3.3.2

 

Bypass operation .............................................................................................. 10

 

3.3.3

 

Battery operation .............................................................................................. 11

 

3.3.4

 

Manual bypass .................................................................................................. 12

 

3.4

 

CONTROL AND OPERATION DEVICES .................................................................. 13

 

3.4.1

 

Isolators (DC input and AC output) ................................................................. 13

 

3.4.2

 

Emergency power off button (EPO) ................................................................ 13

 

3.4.3

 

Normal/Bypass selector (SW1) ........................................................................ 14

 

3.4.4

 

LCD control panel ............................................................................................. 14

 

4

 

FRONT PANEL .................................................................................. 15

 

4.1

 

FUNCTION BUTTONS ............................................................................................... 15

 

Summary of Contents for ASD10

Page 1: ...ARNINGS 7 3 GENERAL UPS DESCRIPTION 8 3 1 TYPOLOGY 8 3 2 SYSTEM DESCRIPTION 8 3 2 1 Rectifier 8 3 2 2 Inverter 9 3 2 3 Battery and battery charger 9 3 2 4 Static bypass 9 3 2 5 Manual bypass 9 3 3 OPERATING STATUS 10 3 3 1 Normal operation 10 3 3 2 Bypass operation 10 3 3 3 Battery operation 11 3 3 4 Manual bypass 12 3 4 CONTROL AND OPERATION DEVICES 13 3 4 1 Isolators DC input and AC output 13 3 ...

Page 2: ... 6 5 SETTING THE MODBUS PARAMETERS 28 6 6 UPS TEST 28 6 7 BATTERY TEST 29 6 8 SYSTEM RESET 29 6 9 ALARMS HISTORY RESET 30 7 SYSTEM INFORMATION 31 7 1 PARALLEL OPERATION INFORMATION 32 7 1 1 UPS position 32 7 1 2 Master Slave priority 32 7 1 3 Communication bus monitoring 33 7 1 4 Parallel type 33 7 1 5 Message statistics 34 7 2 SERVICE INFORMATION 34 8 FAULTS AND ALARMS 35 8 1 OPERATING STATUS DEF...

Page 3: ...ndo LCD 60 4 PANNELLO FRONTALE 61 4 1 TASTI FUNZIONE 61 4 2 FUNZIONE DEI LED DEL SINOTTICO 61 5 GESTIONE DEL PANNELLO LCD 63 5 1 MENU PRINCIPALI 63 5 2 VISUALIZZAZIONE DELLE MISURE 64 5 3 DIAGNOSTICA DI BASE 66 5 3 1 Visualizzazione dello storico allarmi 67 5 3 2 Lista degli allarmi e degli stati 68 6 IMPOSTAZIONI E OPERAZIONI AVANZATE 70 6 1 IMPOSTAZIONE DI DATA E ORA 72 6 2 IMPOSTAZIONE LINGUA D...

Page 4: ... Picture 5 Manual bypass 12 Picture 6 UPS front panel 15 Picture 7 UPS mimic panel 15 Picture 8 Structure of MEASURES menu 1 of 2 18 Picture 9 Structure of MEASURES menu 2 of 2 19 Picture 10 Structure of ALARMS menu 20 Picture 11 Structure of SPECIAL menu 24 Picture 12 Structure of INFO menu 31 Figura 1 Schema a blocchi 54 Figura 2 Funzionamento normale 56 Figura 3 Carico alimentato da bypass 56 F...

Page 5: ...UPS user manual Utilizzo dell UPS OMD10082 REV F 5 ENGLISH LANGUAGE ...

Page 6: ... ASD38 B9000FXS 300kVA ASD39 B9600FXS 400kVA ASD40 B9600FXS 500kVA ASD41 B9600FXS 600kVA ASD42 B9600FXS 800kVA Storing documentation This manual and any other supporting technical documentation relating to the product must be stored and made accessible to personnel in the immediate vicinity of the UPS Further information In the event that the information provided in this manual is not sufficiently...

Page 7: ...s must be strictly followed Injury hazard due to device failure Potentially hazardous situations may arise in case of UPS failure Do not use the device if visibly damaged Maintain the device regularly to identify possible failure Possible device damage Whenever work is carried out on the device make sure all actions are taken in order to avoid electrostatic discharges which might damage the electr...

Page 8: ...ptions and from excessive mains variations and prevents damage to critical loads Computer Instrumentation Scientific equipment etc Output voltage present The line connected to the UPS output is energized even during mains failure therefore in compliance with the prescriptions of IEC EN62040 1 2 the installer will have to identify the line or the plugs supplied by the UPS making the User aware of t...

Page 9: ...e rectifier s control electronics The battery is charged according to the DIN 41773 Standard every time it has been partially or completely discharged When its full capacity is restored it is kept floating so as to compensate for any autodischarge 3 2 4 Static bypass The Static Bypass allows to transfer the load between Inverter and Emergency Mains and vice versa in a very short time and uses SCR ...

Page 10: ...s voltage as well as load variations keeping the DC voltage constant At the same time it keeps the battery charged floating or boost charge depending on the battery type The inverter converts the DC voltage into an AC sine wave with stabilized voltage and frequency and also supplies the load via its static switch SSI Picture 2 Normal operation 3 3 2 Bypass operation The load can be switched to byp...

Page 11: ...ds supply is interrupted as soon as the battery reaches the discharge limit threshold black out As soon as the supply is restored the rectifier will recharge the battery In the standard configuration the loads are supplied again via static switch SSB when mains is available again The inverter is restarted when the battery has partially restored its capacity The system restart from the black out co...

Page 12: ...he load is directly supplied by the bypass line Follow the procedures contained in the manual The sequence of manual bypass switching and return must be carried out with respect to the procedure indicated in the installation and start up section The manufacturer cannot accept responsibility for damages arising from incorrect operation External manual bypass In the UPS systems of the B9600FXS line ...

Page 13: ...tput The isolators provided on the UPS are used to isolate the power components of the device from the AC supply line from the storage battery and from the loads Voltage present on terminals The isolators do not isolate the UPS completely where the AC line and battery voltages are still present on the terminals Before carrying out any maintenance on the unit Isolate the device completely by operat...

Page 14: ...Normal Bypass selector is installed in the control panel and is only accessible by opening the front door It is generally used during the manual bypass procedure when it is necessary to isolate the UPS for maintenance or repair Follow the procedures contained in the manual The Normal Bypass selector shall only be operated in accordance with the procedures specified in the installation and start up...

Page 15: ...PS front panel 4 1 FUNCTION BUTTONS The front panel of the UPS is provided with 5 buttons whose functions are indicated in the following table Button Assigned functions Scrolls up the menus Increases the values by one unit Selects a value Scrolls down the menus Decreases the values by one unit Selects a value Selects a menu Confirms changes Silences the buzzer activated due to an alarm or a failur...

Page 16: ...ging or under TEST ORANGE Circuit breaker BCB open RED Battery fault following a battery test OFF Battery not available LED 5 GREEN Inverter voltage within tolerance and static switch closed GREEN Inverter overload or short circuit OFF Inverter off or voltage out of tolerance LED 6 ORANGE Re transfer blocked ORANGE Static bypass switch closed OFF Static bypass switch open LED 7 GREEN Output circui...

Page 17: ...creen nominal power of the UPS xxx kVA UPS NAME UPS measures regarding basic parameters voltage current etc MEASURES UPS NAME UPS operating status possible alarms present and alarms history ALARMS UPS NAME Setting of parameters and special functions SPECIAL UPS NAME General information regarding the UPS INFO ...

Page 18: ...UPS user manual Utilizzo dell UPS 18 OMD10082 REV F 5 2 MEASURE DISPLAY The MEASURES menu is structured as follows Picture 8 Structure of MEASURES menu 1 of 2 ...

Page 19: ...cy 0 1 Hz Active power 1 kW Apparent power 1 kVA Load percentage 1 BYPASS Voltage 1 2 1 V Frequency 0 1 Hz INVERTER Voltage 1 2 1 V Frequency 0 1 Hz AC DC Rectifier output voltage 1 V BATTERY Voltage and current 1 V 1 A Nominal capacity 1 Ah Residual autonomy 1 min 1 1 The voltage measures are always referred to the phase to neutral value 2 The three voltages are displayed in one screen as xxx yyy...

Page 20: ...tomatically whenever an alarm occurs The audible indicator if enabled is activated to show the occurred failure The audible alarm is silenced pressing the key BUZZER UPS STATUS Display of the first alarm present if no alarm is present the operating status is displayed alarm status no 1 UPS STATUS Press the key to browse the menu and to go to the next alarm status in alphabetical order Last alarm s...

Page 21: ...t The quantity of stored events is displayed on the first line xxx yyy which contains the data currently displayed position in the list and the total number of stored data maximum number equal to 250 respectively An asterisk indicates the automatic reset of the alarm HISTORY 001 015 Latest event stored in order of time E g automatic reset of alarm A3 BOOSTER STOPPED A3 26 10 10 20 05 HISTORY 002 0...

Page 22: ...D A11 SHORT CIRCUIT A39 INV ERROR LOOP A12 STOP TIMEOUT SC A40 SSI FAULT A13 INV OUT OF TOL A41 RECT ERROR LOOP A14 BYPASS WR SEQ A42 INP FUSES BLOWN A15 BYPASS FAULT A43 CURR ERROR LOOP A16 BYPASS LOAD A44 DESAT IGBT INV A17 RETRANSFER BLOCK A45 HIGH TEMP SSW A18 MBCB CLOSED A46 PAR LOST REDUND A19 OCB OPEN A47 SEND PARAM ERROR A20 OVERLOAD A48 RCV PARAM ERROR A21 THERMAL IMAGE A49 TEST MODE ERRO...

Page 23: ...e statuses are always displayed in ascending order when the ALARMS STATUSES menu is entered The alarms are shown when they are present and must be silenced with the buzzer The alarms remain displayed whilst they are present and they are automatically stored in the event log with date and time Description of alarms and statuses For a more detailed description of the alarms and statuses see the Faul...

Page 24: ...nual Utilizzo dell UPS 24 OMD10082 REV F 6 SETTINGS AND ADVANCED OPERATIONS Some operating parameters of the UPS can be set via the SPECIAL menu which is structured as follows Picture 11 Structure of SPECIAL menu ...

Page 25: ...NEW BATTERY INSTALL Sets autonomy to 100 RESET HISTORY Event log reset MODBUS MODBUS address of device RESET RUNNING HOURS Reset the hour counter related to the UPS running time Password protected access The SETTINGS menu is protected by a password set by the factory in order to prevent access to unauthorized personnel We recommend minimum disclosure of the access password Changes to the operating...

Page 26: ...hanged via the arrow buttons to increase the digits and the button is used to confirm the entry 6 3 NEW BATTERY INSTALLATION The NEW BATTERY INSTALLATION menu is used in case battery circuit breaker BCB is not closed when requested in the start up phase In this case the system will start considering the battery completely discharged and activating the alarm A10 BATTERY FAULT To set the battery aut...

Page 27: ...meter set YES BAT RECHAR CURR SET The single digits can be modified via the arrow keys and confirmed by pressing ENTER 18 CONFIRM RECHAR CURR Confirmation screen of the parameter set YES AUTONOMY BAT SETTING The single digits can be modified via the arrow keys and confirmed by pressing ENTER 0020 CONFIRM AUTON BATT Confirmation screen of the parameter set YES SAVE BATT SETTINGS Confirmation screen...

Page 28: ...he arrow keys and confirmed by pressing ENTER 202 Parameter Standard Range MODBUS ADDRESS 1 1 247 6 6 UPS TEST The UPS TEST menu allows to carry out a switching test of the inverter The inverter is switched off and the load is transferred to the bypass supply The inverter supply is automatically restored after a few seconds UPS TEST The value on the second line is ready to be changed NO 1x UPS TES...

Page 29: ...pply This test can affect the continuity of supply to the loads if the battery is not fully charged 6 8 SYSTEM RESET The UPS is equipped with internal protections which block the system or some of its sections The alarm can be cleared and normal operation can be resumed via the RESET menu In case the failure persists the UPS will return to the previous failure condition In some cases the RESET is ...

Page 30: ...arm A43 Static switch blocked alarm A50 Booster shutdown due to the operation of the load symmetry sensor alarm A33 Activation of the battery fault alarm alarm A10 Scheduled maintenance request alarm A29 For a description of the UPS status in each of the failure conditions listed above please refer to the Faults and alarms section 6 9 ALARMS HISTORY RESET Access the RESET HISTORY menu RESET HISTOR...

Page 31: ...ing the UPS based on the structure indicated below Picture 12 Structure of INFO menu All data shown in the various sections are set by the factory via a special interface software and cannot be altered except by personnel authorized by the manufacturer The only adjustable parameters are the MODBUS settings see SPECIAL menu ...

Page 32: ...ice RUNNING HOUR Dates related to hours number of UPS running time 1 the menu is only active if the UPS belongs to a Parallel or Load Sync system 7 1 PARALLEL OPERATION INFORMATION The PARALLEL menu is only active if the UPS belongs to a parallel or load sync system 7 1 1 UPS position PARALLEL 2 6 The first number on the second line identifies the position of that specific UPS within the parallel ...

Page 33: ...currently the MASTER UPS we are checking the data communication on UPS3 UPS4 is not communicating The menu will be as shown below PARALLEL 1 S 2 M 3 S 4 In case there are more than four paralleled devices the menu will be as follows PARALLEL 1 S 2 M 3 S The dots indicate the presence of a further menu which shows the status of the other UPS units in the system 7 1 4 Parallel type PARALLEL REDUNDAN...

Page 34: ...entage of reception accuracy regarding the synchronism signals The messages are sent by the MASTER UPS therefore the number will only increase on the SLAVE UPS units STATIST CAN INV MSG RX 9277 99 9 Number of messages received and percentage of reception accuracy regarding the status of the system The messages are exchanged between all the UPS units therefore the number will increase on all of the...

Page 35: ... UPS STATUS The other alarms present are displayed by scrolling the menu A30 COMMON ALARM UPS STATUS After the last alarm present the operating statuses are displayed S1 BOOSTER OK Injury hazard due to electric shock Before carrying out any operation on the UPS make sure that all the safety precautions are adhered to Any work on the unit must be carried out by qualified personnel Internal componen...

Page 36: ... is ready to feed the load Status S4 INVERTER LOAD Description The inverter feeds the load Operating condition The load is fed via the static inverter switch Status S5 INV BYPASS SYNC Description The inverter is synchronized with the bypass Operating condition The synchronization between the inverter and the bypass is locked and the static switch can change over from one source to the other Status...

Page 37: ...rectifier is charging the battery with a higher voltage The return to FLOATING charge mode is automatic Status S9 INV MASTER SYNC Description The inverter is synchronized with the MASTER UPS Operating condition This status is only present on the SLAVE UPS units and shows that the inverter is synchronized with the signal sent by the MASTER UPS ...

Page 38: ... 2 If the alarm persists contact our Technical Support Service Alarm A3 BOOSTER STOPPED Description The rectifier has been temporarily disconnected and the inverter is fed by the battery Possible causes Instability of the AC line voltage or frequency Possible fault in the rectifier control circuit Solutions 1 Check the parameters of the AC line voltage 2 Restart the device 3 If the alarm persists ...

Page 39: ...ssible causes A battery test has been started automatically if set or manually by the user Solutions 1 Wait for the test to end and check possible battery faults Alarm A7 BCB OPEN Description The battery isolator is open Possible causes Battery isolator open Solutions 1 Check the status of the battery isolator 2 Check the functionality of the auxiliary contact of the isolator 3 Check the connectio...

Page 40: ...e system 3 If the alarm persists contact our Technical Support Service Alarm A11 SHORT CIRCUIT Description The current sensor has detected a short circuit at the output Possible causes Load problem Measuring circuit failure Solutions 1 Check the loads connected to the UPS output 2 If the alarm persists contact our Technical Support Service Alarm A12 STOP TIMEOUT SC Description Inverter shutdown du...

Page 41: ...lutions 1 Check the phase rotation 2 If the alarm persists contact our Technical Support Service Alarm A15 BYPASS FAULT Description The voltage or frequency of the bypass line are out of tolerance Possible causes Bypass line instability or failure Wrong phase rotation Solutions 1 Check the connections to the mains 2 Check the stability of mains voltage 3 If the alarm persists contact our Technical...

Page 42: ...tor 2 Check the functionality of the auxiliary contact of the isolator 3 If the alarm persists contact our Technical Support Service Alarm A19 OCB OPEN Description The output isolator is open Possible causes Output isolator open Solutions 1 Check the status of the output isolator 2 Check the functionality of the auxiliary contact of the isolator 3 If the alarm persists contact our Technical Suppor...

Page 43: ...ervice Alarm A23 EPO PRESSED Description The system is blocked due to the activation of the emergency power off button Possible causes Activation of the local or remote emergency power off button Solutions 1 Release the emergency power off button and reset the alarm 2 If the alarm persists contact our Technical Support Service Alarm A24 HITMP INV DC FUS Description High temperature of the heat sin...

Page 44: ...tected an error in the parameters stored in E2 PROM Possible causes Wrong parameters entered during programming Solutions 1 Contact our Technical Support Service Alarm A28 CRITICAL FAULT Description An alarm has been activated which causes the shutdown of part of the UPS rectifier inverter static switch Possible causes System failure Solutions 1 Check which alarms are present and carry out the ind...

Page 45: ... system is blocked due to the activation of the emergency power off button Possible causes Activation of the local or remote emergency power off button Solutions 1 Release the emergency power off button and reset the alarm 2 If the alarm persists contact our Technical Support Service Alarm A33 ASYMMETRIC LOAD Description The positive and negative voltages measured on the DC capacitors towards the ...

Page 46: ...ry fault Solutions 1 Check the battery 2 Reset the system 3 If the alarm persists contact our Technical Support Service Alarm A37 HIGH TEMP RECT Description High temperature of the rectifier heat sink Possible causes Fault of the heat sink cooling fans The room temperature or cooling air temperature is too high Solutions 1 Check the fans operation 2 Clean the ventilation grids and the air filters ...

Page 47: ... the loads and the presence of DC components if any on AC current 2 If the alarm persists contact our Technical Support Service Alarm A41 RECT ERROR LOOP Description The control is not able to regulate the rectifier output voltage precisely Possible causes Regulation system failure Solutions 1 Reset the system 2 If the alarm persists contact our Technical Support Service Alarm A42 INP FUSES BLOWN ...

Page 48: ...HIGH TEMP SSW Description High temperature of the static switch heat sink Possible causes Fault of the heat sink cooling fans The room temperature or cooling air temperature is too high Solutions 1 Check the fans operation 2 Clean the ventilation grids and the air filters if any 3 Check the air conditioning system if present 4 If the alarm persists contact our Technical Support Service Alarm A46 P...

Page 49: ...Solutions 1 Contact our Technical Support Service Alarm A50 SSW BLOCKED Description The static switch is blocked The load is no longer supplied Possible causes Loads failure Possible UPS fault Solutions 1 Check the loads for possible failures 2 Reset the system 3 If the alarm persists contact our Technical Support Service Alarm A51 BATT TEMPERATURE Description The battery temperature is out of tol...

Page 50: ...utions 1 Check the connection of cable 2 Contact our Technical Support Service Alarm A56 MAINS UNBALANCE Description The rectifier input voltage is unbalanced Possible causes Problems on the LV or MV distribution network Defect of the measuring circuit Solutions 1 Check the input voltage 2 Contact our Technical Support Service Alarm A63 START SEQ BLOCK Description During the UPS start up a failure...

Page 51: ...UPS user manual Utilizzo dell UPS OMD10082 REV F 51 LINGUA ITALIANA ...

Page 52: ... B9000FXS 300kVA ASD39 B9600FXS 400kVA ASD40 B9600FXS 500kVA ASD41 B9600FXS 600kVA ASD42 B9600FXS 800kVA Conservazione della documentazione Questo manuale e tutta la restante documentazione tecnica di supporto al prodotto devono essere conservati e possibilmente resi accessibili al personale nelle immediate vicinanze dell UPS Informazioni aggiuntive Nel caso le informazioni riportate nel presente ...

Page 53: ...uali Pericolo di lesioni a seguito di guasti al dispositivo In caso di guasto dell UPS si possono creare situazioni potenzialmente pericolose Non utilizzare il dispositivo se presenta danni visibili Effettuare regolarmente interventi di manutenzione al fine di rilevare possibili anomalie Possibile danneggiamento del dispositivo Prima di qualsiasi intervento sul dispositivo aver cura di prendere tu...

Page 54: ...zioni e da eccessive variazioni della rete che potrebbero altrimenti danneggiare le utenze Computer Strumentazione Apparecchiature scientifiche ecc Presenza tensione in uscita La linea connessa con l uscita UPS è alimentata anche in mancanza della rete per cui in accordo alle prescrizioni della CEI EN62040 1 2 l installatore dovrà identificare la linea o le prese alimentate dall UPS richiamando l ...

Page 55: ...è integrata all interno dell elettronica di controllo del raddrizzatore La batteria viene sottoposta ad un ciclo di carica in accordo alle DIN41773 ogni volta che avviene una scarica parziale o totale Al ripristino della completa capacità viene mantenuto un livello di tensione tampone tale da compensare l auto scarica 3 2 4 Bypass statico Il Bypass Statico permette di commutare il carico fra Inver...

Page 56: ...sione di rete così come quelle di carico mantenendo la tensione DC costante Allo stesso tempo provvede a tenere la batteria in carica tampone o rapida in funzione del tipo di batteria L inverter converte la tensione DC in una sinusoide AC stabilizzata in tensione e frequenza e provvede ad alimentare il carico tramite il suo static switch SSI Figura 2 Funzionamento normale 3 3 2 Funzionamento da by...

Page 57: ...ggiunge la soglia limite di scarica black out Appena viene ripristinata l alimentazione il raddrizzatore provvede alla ricarica della batteria Nella configurazione standard l alimentazione ai carichi viene ripristinata appena la rete è nuovamente disponibile ed avviene tramite l interruttore statico SSB Il riavvio dell inverter avviene quando la batteria ha ripristinato parte della sua capacità La...

Page 58: ...è completamente spento e il carico è alimentato direttamente dalla rete di bypass Seguire le procedure riportate nel manuale La manovra di inserimento del bypass manuale e ritorno deve essere eseguita rispettando la procedura riportata nella sezione di installazione e avviamento Si declina ogni responsabilità da danni derivanti da manovre errate Bypass manuale esterno Negli UPS della linea B9600FX...

Page 59: ...ull UPS servono per isolare la parte di potenza del dispositivo dalla rete AC di alimentazione dalla batteria di accumulatori e dai carichi Presenza di tensione sui terminali I sezionatori non isolano completamente l UPS all interno del quale sono ancora presenti le tensioni della rete AC e della batteria sui terminali Prima di effettuare qualsiasi intervento di manutenzione sull apparato provvede...

Page 60: ...le Bypass SW1 Il selettore Normale Bypass è montato all interno del quadro ed è accessibile solamente aprendo la porta frontale Viene generalmente utilizzato durante la procedura di bypass manuale quando è necessario isolare l UPS per manutenzione o riparazione Seguire le procedure riportate nel manuale Il selettore Normale Bypass deve essere manovrato solamente in accordo alle procedure riportate...

Page 61: ...nnello frontale UPS 4 1 TASTI FUNZIONE Il pannello frontale dell UPS è provvisto di 5 tasti le cui funzioni sono indicate nella tabella seguente Tasto Funzioni assegnate Scorre i menu verso l alto Incrementa i valori di una unità Seleziona un valore Scorre i menu verso il basso Decrementa i valori di una unità Seleziona un valore Seleziona un menu Conferma le modifiche Silenzia il buzzer attivato ...

Page 62: ...uttore BCB aperto ROSSO Batteria guasta a seguito test di batteria OFF Batteria non presente LED 5 VERDE Tensione inverter in tolleranza e static switch chiuso VERDE Sovraccarico inverter o corto circuito OFF Inverter spento o tensione fuori tolleranza LED 6 ARANCIO Ritrasferimento bloccato ARANCIO Static switch bypass chiuso OFF Static switch bypass aperto LED 7 VERDE Interruttore di uscita OCB c...

Page 63: ...a la potenza nominale dell UPS xxx kVA NOME UPS Misure dei parametri fondamentali dell UPS tensione corrente ecc MISURE NOME UPS Stato di funzionamento dell UPS eventuali allarmi presenti e storico allarmi ALLARMI NOME UPS Impostazione parametri e funzioni speciali SPECIALE NOME UPS Informazioni generali sull UPS INFO ...

Page 64: ...UPS user manual Utilizzo dell UPS 64 OMD10082 REV F 5 2 VISUALIZZAZIONE DELLE MISURE Il menu MISURE è strutturato come segue Figura 8 Struttura menu MISURE 1 di 2 ...

Page 65: ...Potenza attiva 1 kW Potenza apparente 1 kVA Percentuale di carico 1 BYPASS Tensione 1 2 1 V Frequenza 0 1 Hz INVERTER Tensione 1 2 1 V Frequenza 0 1 Hz AC DC Tensione uscita raddrizzatore 1 V BATTERIA Tensione e corrente 1 V 1 A Capacità nominale 1 Ah Autonomia residua 1 min 1 1 Le misure di tensione sono sempre riferite tra fase e neutro 2 Le tre tensioni sono visualizzate in una schermata unica ...

Page 66: ...che si verifica un allarme il segnalatore acustico se abilitato viene attivato per indicare l avvenuta anomalia La tacitazione viene effettuata premendo il pulsante BUZZER STATO UPS Visualizzazione del primo allarme presente se non presenti allarmi visualizzazione dello stato di funzionamento Allarme stato no 1 STATO UPS Premendo il tasto si scorre il menu e si passa all allarme stato successivo i...

Page 67: ...uantità di eventi memorizzati è visualizzata sulla prima riga xxx yyy dove sono riportati rispettivamente il dato visualizzato al momento posizione nella lista e il numero totale di dati memorizzati numero massimo pari a 250 Un asterisco indica il reset automatico dell allarme STORICO 001 015 Ultimo evento memorizzato in ordine di tempo Es reset automatico allarme A3 RADD SPENTO A3 26 10 10 20 05 ...

Page 68: ...RTO CIRCUITO A39 ERRORE LOOP INV A12 STOP TIMEOUT CC A40 ANOMALIA SSI A13 INV FUORI TOL A41 ERR LOOP TEN RAD A14 ER SENSO CIC BYP A42 GUASTO FUSIB ING A15 BYPASS NON DISP A43 ERR LOOP COR RAD A16 BYP CARICO A44 DESATURAZIONE A17 RITRASF BLOC A45 ALTA TEMP SSW A18 MBCB CHIUSO A46 PERDITA RIDOND A19 OCB APERTO A47 ERR INVIO PARAM A20 SOVRACCARICO A48 ERR RIC PARAM EE A21 IMMAGINE TERMICA A49 DISCOR ...

Page 69: ...si entra nel menù ALLARMI STATI gli stati vengono visualizzati sempre in ordine crescente Gli allarmi vengono mostrati quando si presentano e devono essere tacitati con il buzzer Gli allarmi restano visibili finché sono presenti e vengono registrati automaticamente nello storico eventi con data e ora Descrizione degli allarmi e degli stati Per una descrizione più approfondita degli allarmi e degli...

Page 70: ...tilizzo dell UPS 70 OMD10082 REV F 6 IMPOSTAZIONI E OPERAZIONI AVANZATE L impostazione di alcuni parametri operativi dell UPS è possibile dal menu SPECIALE che è strutturato come segue Figura 11 Struttura menu SPECIALE ...

Page 71: ...STALL NUOVA BATT Imposta l autonomia al 100 RESET STORICO Reset dello storico eventi MODBUS Indirizzo MODBUS del dispositivo AZZERA CONTAORE Azzeramento del contaore di funzionamento della macchina Accesso protetto da password Il menu IMPOSTAZIONI è protetto da una password impostata in fabbrica per impedire l accesso a personale non autorizzato Si raccomanda la minima divulgazione della password ...

Page 72: ...a utilizzando i tasti freccia per incrementare le cifre e il tasto per confermare l inserimento 6 3 INSTALLAZIONE NUOVA BATTERIA Il menù INSTALLAZIONE NUOVA BATTERIA serve nel caso in cui durante la fase di avvio non viene chiuso l interruttore di batteria BCB quando richiesto In tal caso il sistema si avvia considerando la batteria completamente scarica e attivando l allarme A10 ANOMALIA BATT Per...

Page 73: ...ato SI CONFIG COR RICAR BAT Le singole cifre si modificano con i tasti freccia e si confermano con il tasto ENTER 18 CONF CORR RICARICA Schermata di conferma del parametro impostato SI CONFIG AUTONOMIA BAT Le singole cifre si modificano con i tasti freccia e si confermano con il tasto ENTER 0020 CONF AUTONOMIA BATT Schermata di conferma del parametro impostato SI SALVARE CONFIG BATT Schermata di c...

Page 74: ... freccia e si confermano con il tasto ENTER 202 Parametro Standard Range INDIRIZZO MODBUS 1 1 247 6 6 TEST DELL UPS Il menù UPS TEST permette di effettuare una prova di commutazione dell inverter L inverter viene spento e il carico trasferito all alimentazione di bypass L alimentazione da inverter viene ripristinata automaticamente dopo pochi secondi TEST UPS Il valore sulla seconda riga è pronto ...

Page 75: ...essere rischioso per la continuità sui carichi se la batteria non è pienamente carica 6 8 RESET DEL SISTEMA L UPS è provvisto di protezioni interne che provvedono al blocco del sistema o di alcune sue sezioni Tramite il menu RESET è possibile sbloccare l allarme e ripristinare il funzionamento normale Nel caso l anomalia persista l UPS si riporta nella condizione di blocco precedente In alcuni cas...

Page 76: ... A50 Arresto booster per intervento del sensore di simmetria del carico allarme A33 Intervento allarme di avaria batteria allarme A10 Richiesta manutenzione programmata allarme A29 Per la descrizione dello stato dell UPS in ciascuna delle condizioni di blocco elencata in precedenza fare riferimento alla sezione Guasti e allarmi 6 9 RESET STORICO ALLARMI Accedere al menu RESET STORICO RESET STORICO...

Page 77: ...tura mostrata di seguito Figura 12 Struttura menu INFO Tutti i dati mostrati all interno delle varie sezioni sono impostati in fabbrica tramite apposito software di interfaccia e non possono essere modificati tranne che da parte di personale autorizzato dal costruttore Gli unici parametri modificabili sono le impostazioni MODBUS vedi menu SPECIALE ...

Page 78: ...a tecnica CONTAORE Dati relativi al numero di ore di funzionamento della macchina 1 Il menù è attivo solamente se l UPS fa parte di un sistema Parallelo oppure Load Sync 7 1 INFORMAZIONI SUL FUNZIONAMENTO IN PARALLELO Il menù PARALLELO è attivo solamente se l UPS fa parte di un sistema parallelo oppure load sync 7 1 1 Posizione dell UPS PARALLELO 2 6 Il primo numero sulla seconda riga identifica l...

Page 79: ...icando la comunicazione dati sull UPS3 l UPS4 non comunica Il menù si presenterà come mostrato di seguito PARALLELO 1 S 2 M 3 S 4 Nel caso che i dispositivi in parallelo siano più di quattro il menù si presenta come segue PARALLELO 1 S 2 M 3 S I punti indicano la presenza di un ulteriore menù che mostra lo stato degli altri UPS del sistema 7 1 4 Tipo di parallelo PARALLELO RIDONDANTE x La stringa ...

Page 80: ... ricezione relativamente ai segnali di sincronismo I messaggi vengono inviati dall UPS MASTER quindi il numero incrementa solo sugli UPS SLAVE STATIST CAN INV MSG RX 9277 99 9 Numero di messaggi ricevuti e percentuale di accuratezza della ricezione relativamente agli stati del sistema I messaggi vengono scambiati fra tutti gli UPS quindi il numero incrementa su tutti 7 2 INFORMAZIONI RELATIVE ALL ...

Page 81: ...do il menu vengono visualizzati gli altri allarmi presenti A30 ALLARME GENERALE STATO UPS Dopo l ultimo allarme presente si passa alla visualizzazione degli stati operativi S1 BOOSTER OK Pericolo di lesioni a seguito shock elettrico Prima di effettuare qualsiasi intervento sull UPS aver cura di rispettare tutte le indicazioni relative alla sicurezza tutti i lavori sull apparato devono essere svolt...

Page 82: ...re alimentare il carico Stato S4 INV CARICO Descrizione L inverter alimenta il carico Condizione operativa Il carico è alimentato attraverso l interruttore statico di inverter Stato S5 INV BYPASS SINCRO Descrizione L inverter è sincronizzato con il bypass Condizione operativa Il sincronismo fra inverter e bypass è agganciato e l interruttore statico può effettuare commutazioni fra le due sorgenti ...

Page 83: ...drizzatore sta caricando la batteria con tensione maggiore Il ritorno alle condizioni di carica TAMPONE è automatico Stato S9 INV MASTER SINCRO Descrizione L inverter è sincronizzato con l UPS MASTER Condizione operativa Questo stato è presente solo sugli UPS SLAVE e indica che l inverter è sincronizzato con il segnale inviato dall UPS MASTER ...

Page 84: ...nso ciclico delle fasi 2 Se l allarme persiste contattare il servizio di Assistenza Tecnica Allarme A3 RADD SPENTO Descrizione Il raddrizzatore è stato momentaneamente arrestato e l inverter viene alimentato dalla batteria Possibili cause Instabilità della tensione o della frequenza della rete AC Possibile guasto del circuito di controllo del raddrizzatore Soluzioni 1 Verificare i parametri della ...

Page 85: ... cause E stato avviato un test di batteria automaticamente se impostato oppure manualmente dall operatore Soluzioni 1 Attendere la fine del test e verificare eventuali anomalie della batteria Allarme A7 BCB APERTO Descrizione Il sezionatore di batteria è aperto Possibili cause Sezionatore di batteria aperto Soluzioni 1 Verificare lo stato del sezionatore di batteria 2 Verificare la funzionalità de...

Page 86: ...l sistema 3 Se l allarme persiste contattare il servizio di Assistenza Tecnica Allarme A11 CORTO CIRCUITO Descrizione Il sensore di corrente ha rilevato un corto circuito in uscita Possibili cause Problema sui carichi Guasto del circuito di misura Soluzioni 1 Verificare i carichi connessi all uscita dell UPS 2 Se l allarme persiste contattare il servizio di Assistenza Tecnica Allarme A12 STOP TIME...

Page 87: ... delle fasi 2 Se l allarme persiste contattare il servizio di Assistenza Tecnica Allarme A15 BYPASS NON DISP Descrizione La tensione o la frequenza della rete di bypass sono fuori dal range di tolleranza Possibili cause Instabilità o mancanza della rete di bypass Errato senso ciclico delle fasi Soluzioni 1 Controllare i collegamenti di connessione alla rete 2 Verificare la stabilità della tensione...

Page 88: ...care la funzionalità del contatto ausiliario del sezionatore 3 Se l allarme persiste contattare il servizio di Assistenza Tecnica Allarme A19 OCB APERTO Descrizione Il sezionatore di uscita è aperto Possibili cause Sezionatore di uscita aperto Soluzioni 1 Verificare lo stato del sezionatore di uscita 2 Verificare la funzionalità del contatto ausiliario del sezionatore 3 Se l allarme persiste conta...

Page 89: ...Allarme A23 EPO CHIUSO Descrizione Il sistema è bloccato in seguito all azionamento del pulsante di arresto di emergenza Possibili cause Azionamento del pulsante di arresto di emergenza locale o remoto Soluzioni 1 Sbloccare l arresto di emergenza e resettare l allarme 2 Se l allarme persiste contattare il servizio di Assistenza Tecnica Allarme A24 ALT TEM INV DC F Descrizione Alta temperatura del ...

Page 90: ... un errore nei parametri memorizzati in E2 PROM Possibili cause Inserimento di parametri errati durante la programmazione Soluzioni 1 Contattare il servizio di Assistenza Tecnica Allarme A28 GUASTO CRITICO Descrizione E presente un allarme che causa l arresto di una parte dell UPS raddrizzatore inverter interruttore statico Possibili cause Guasto del sistema Soluzioni 1 Verificare quali allarmi so...

Page 91: ...ccato in seguito all azionamento del pulsante di arresto di emergenza Possibili cause Azionamento del pulsante di arresto di emergenza locale o remoto Soluzioni 1 Sbloccare l arresto di emergenza e resettare l allarme 2 Se l allarme persiste contattare il servizio di Assistenza Tecnica Allarme A33 CARICO ASIMMETR Descrizione Le tensioni misurate sui condensatori DC positiva e negativa verso punto ...

Page 92: ...re il sistema 3 Se l allarme persiste contattare il servizio di Assistenza Tecnica Allarme A37 ALTA TEMP RADD Descrizione Alta temperatura del dissipatore di calore del raddrizzatore Possibili cause Guasto dei ventilatori di raffreddamento del dissipatore Temperatura dell ambiente o dell aria di raffreddamento troppo elevata Soluzioni 1 Controllare il funzionamento dei ventilatori 2 Pulire le grig...

Page 93: ...ale presenza di componenti continue sulla corrente AC 2 Se l allarme persiste contattare il servizio di Assistenza Tecnica Allarme A41 ERR LOOP TEN RAD Descrizione Il controllo non è in grado di regolare accuratamente la tensione di uscita raddrizzatore Possibili cause Guasto del sistema di regolazione Soluzioni 1 Resettare il sistema 2 Se l allarme persiste contattare il servizio di Assistenza Te...

Page 94: ...rizione Alta temperatura del dissipatore di calore dell interruttore statico Possibili cause Guasto dei ventilatori di raffreddamento del dissipatore Temperatura dell ambiente o dell aria di raffreddamento troppo elevata Soluzioni 1 Controllare il funzionamento dei ventilatori 2 Pulire le griglie di aerazione e gli eventuali filtri aria 3 Verificare il sistema di condizionamento se presente 4 Se l...

Page 95: ...l servizio di Assistenza Tecnica Allarme A50 SSW BLOCCATO Descrizione L interruttore statico è bloccato il carico non è più alimentato Possibili cause Anomalia sui carichi Possibile guasto dell UPS Soluzioni 1 Verificare eventuali anomalie sui carichi 2 Resettare il sistema 3 Se l allarme persiste contattare il servizio di Assistenza Tecnica Allarme A51 TEMPERATURA BATT Descrizione La temperatura ...

Page 96: ...sione del cavo 2 Contattare il servizio di Assistenza Tecnica Allarme A56 TERNA SBILANCIATA Descrizione Terna d ingresso raddrizzatore sbilanciata Possibili cause La terna delle tensioni d ingresso raddrizzatore sono sbilanciate Problema sulla scheda di misura Soluzioni 1 Controllare la tensione di ingresso 2 Contattare il servizio di Assistenza Tecnica Allarme A63 SEQ AVVIO BLOCC Descrizione Dura...

Reviews: