BU
1002
RW
7
46
7-4-3. Contact signal I/O connector (female DSUB9P)
Pin assignment
Pin number
Item
5 4 3 2 1
9 8 7 6
Front view
Screw size: inch screw
#4-40 UNC
1
Battery LOW signal output (BL)
2
Trouble signal output (TR)
3
Backup stop signal input (BS)
4
NC
5
COMMON (COM)
6
Remote ON/OFF input (-)
7
Remote ON/OFF input (+)
8
Backup signal output (BU)
9
Deteriorated battery signal output (WB)
Note: The COMMON (COM) terminal (pin 5) is connected to the frame ground.
7-4-4. Remote ON/OFF port
Pin assignment
Pin number
Signal name
1 2
1
Remote ON/OFF (+)
2
Remote ON/OFF (-)
Front view
Screw size: Inch screw
#4-40 UNC
7-4-5. Contact Signal ratings
●
Signal output (BL, TR, BU, WB)
●
UPS Stop Signal input (BS)
Photo coupler ratings
Input voltage: HIGH(ON) 3 to 24 VDC
Appliable voltage: 50VDC or less
LOW(OFF) 0.5 VDC or less
Maximum current: 50 mA
●
Remote ON/OFF
Input current: 1 to 8 mA
Voltage between terminals: 5 VDC
Current when closed:
15 mA max.
Summary of Contents for BU1002RW
Page 64: ...10 52 Notes of Chinese 10 UPS UPS 1 FA OA Windows UPS...
Page 65: ...10 Notes of Chinese 53 2 FA OA 2...
Page 66: ...BU1002RW 10 54 AC 50 60Hz AC AC AC AC...
Page 67: ...10 Notes of Chinese 55 5cm 10cm UPS UPS AC AC AC200V 240V AC200 240V...
Page 68: ...BU1002RW 10 56 AC AC AC AC AC ON OFF AC INPUT PROTECTION 25 5 2 5 35 3 5mA...
Page 69: ...10 Notes of Chinese 57 AC UPS AC UPS...
Page 70: ...BU1002RW 10 58 AC AC 50 60Hz 25 25 6 40 2 AC AC...
Page 71: ...10 Notes of Chinese 59 DC250V UPS 200V http www fa omron com cn Pb AC AC 50 60Hz...