2
.Installation and connection
19
When you finish connecting the unit, confirm that the backup operation works properly.
Check that the Battery Mode is performed normally according to the following procedure.
(In this operation check, the effects of a power failure are reproduced by disconnecting the AC input
from the commercial power.)
(1) Starting the UPS and setting the LCD menu language.
Supply a commercial power source with the unit’s power switch OFF. The status indicator displays
or
.
The original LCD display language is Japanese. To select English language setting, follow the next
steps.
1) Press “Enter switch” to move to the top menu.
2) Select “
設定
” by pressing “UP/Down switch” and then press ”Enter switch”.
3) Select “
ローカル設定
” by pressing “UP/Down switch” and then press ”Enter switch”.
4) Select “
表示言語
“ by pressing UP/Down switch” and then press ”Enter switch”.
5) Select “
英語
“ by pressing UP/Down switch and then press ”Enter switch”.
6) Press “ESC switch” few times to return to the status screen.
(2) Setting output voltage and frequency.
The output voltage and the output frequency can be set with the operating panel.
1) Press ”Enter switch” to move to the top menu.
2) Select “Settings” by pressing “UP/Down switch” and then press ”Enter switch”.
3) Select “In/Out Settings” by pressing “UP/Down switch” and then press ”Enter switch”.
4) Select “Output voltage” by pressing “UP/Down switch” and then press ”Enter switch”.
5) Select an output voltage by pressing “UP/Down switch” and then press ”Enter switch”.
6) Press “ESC switch” to return to the “In/Out Settings” screen.
7) Select “Sync. Mode” by pressing “UP/Down switch” and then press “Enter switch”.
8) “Sync standard” or “Sync Wide” or “Async 50Hz “ or “Async 60Hz” can be set.
(3) Press the unit’s power switch to turn ON the power.
The beeper sounds and the current settings are displayed on the LED.
Self-diagnosis starts automatically.
When the self-diagnosis test finishes normally, the unit’s operation switches to commercial power
and the status indication below is displayed.
2-5 Checking the operation
Status indicator
Description
Power switch “ON”
Operating normally
(4) Bring all the connected devices into operation.
(Including devices connected to the AC outlet of your PC.)
The unit was charged before shipment, but it may have self-discharged during shipment, resulting in
a reduced backup time. We recommend charging the unit before use.
ON
OFF
ON, OFF, or blinking
depending on status
ESC
Summary of Contents for BU1002RW
Page 64: ...10 52 Notes of Chinese 10 UPS UPS 1 FA OA Windows UPS...
Page 65: ...10 Notes of Chinese 53 2 FA OA 2...
Page 66: ...BU1002RW 10 54 AC 50 60Hz AC AC AC AC...
Page 67: ...10 Notes of Chinese 55 5cm 10cm UPS UPS AC AC AC200V 240V AC200 240V...
Page 68: ...BU1002RW 10 56 AC AC AC AC AC ON OFF AC INPUT PROTECTION 25 5 2 5 35 3 5mA...
Page 69: ...10 Notes of Chinese 57 AC UPS AC UPS...
Page 70: ...BU1002RW 10 58 AC AC 50 60Hz 25 25 6 40 2 AC AC...
Page 71: ...10 Notes of Chinese 59 DC250V UPS 200V http www fa omron com cn Pb AC AC 50 60Hz...