H3RN

H3RN

10

Precautions

When using the H3RN in any place where the ambient temperature
is more than 50

"

C, supply 90% to 110% of the rated voltages (at

12 VDC: 95% to 110%).

Do not leave the H3RN in time-up condition for a long period of time
(for example, more than one month in any place where the ambient
temperature is high), otherwise the internal parts may become dam-
aged. Therefore, the use of the H3RN with a relay as shown in the
following circuit diagram is recommended.

G2R Relay

H3RN

The H3RN must be disconnected from the socket when setting the
DIP switch, otherwise the user may touch a terminal imposed with a
high voltage and get an electric shock.

Do not connect the H3RN as shown in the following circuit diagram
on the right hand side, otherwise the H3RN’s internal contacts differ-
ent from each other in polarity may become short-circuited.

Correct

Incorrect

Use the following safety circuit when building a self-holding circuit
with the H3RN and an auxiliary relay, such as a G2R Relay, in com-
bination.

G2R Relay

H3RN

In the case of the above circuit, the H3RN will be in pulse operation.
Therefore, if the circuit shown on page 9 is used, no auxiliary relay
will be required.

Do not use the SPDT contact in a circuit which may cause short-cir-
cuiting at three points (otherwise, short-circuiting of the power sup-
ply may occur) because the SPDT contact of H3RN-1/-11 is com-
posed of an SPST-NC contact.

Power supply
for load

Short-circuit current

3

4

2

1

5

Do not set to the minimum setting in the flicker modes, otherwise the
contact may be damaged.

Do not use the H3RN in places where there is excessive dust, corro-
sive gas, or direct sunlight.

Make sure that there is a space of 3 mm or more between any H3RN
Models next to each other. (When using the P2RF-

j

-E Socket, a

space of 3 mm or more will be secured.) If a space of 3 mm or more is
not secured, the ambient temperature must be less than 50

"

C.

The internal parts may become damaged if a supply voltage other
than the rated ones is imposed on the H3RN.

Precautions for VDE Conformance

The H3RN as a built-in timer conforms to VDE 0435/P2021 pro-
vided that the following conditions are satisfied.

Handling

Do not touch the DIP switch while power is supplied to the H3RN.

Before dismounting the H3RN from the socket, make sure that no
voltage is imposed on any terminal of the H3RN.

Wiring

Only a load with basic isolation can be connected to the output con-
tact. The H3RN is a model with basic isolation. Therefore, the H3RN
and the load will ensure reinforced isolation, thus meeting VDE
standards.

Insulation requirement: Overvoltage category II,

pollution degree 2
(with a clearance of 1.5 mm and a creep-
age distance of 2.5 mm at 240 VAC)

Summary of Contents for 70179796

Page 1: ...e model 0 1 s to 10 min Long time range model 0 1 min to 10 h 24 VAC 12 24 VDC SPDT H3RN 1 H3RN 11 12 24 VDC DPST NO H3RN 2 H3RN 21 Note Specify both the model number and supply voltage when ordering Example H3RN 1 24 VAC Supply voltage Model Number Legend H3RN jj 1 2 1 Output 1 SPDT 2 DPST NO 2 Time Range None Short time range 0 1 s to 10 min 1 Long time range 0 1 min to 10 hrs Accessories Order ...

Page 2: ...ance 100 M min at 500 VDC Dielectric strength 2 000 VAC 50 60 Hz for 1 min between operating circuit and control output or contacts of different poles 1 000 VAC 50 60 Hz for 1 min between non continuous contacts Vibration resistance Destruction 10 to 55 Hz 0 75 mm single amplitude Malfunction 10 to 55 Hz 0 5 mm single amplitude Shock resistance Destruction 300 m s2 approx 30G Malfunction 100 m s2 ...

Page 3: ... Power Output Time limit contact NC 4 2 Run Power indicator PW Output indicator OUT Power 1 5 Time limit contact NO 4 3 Power 1 8 Time limit contact NO 4 3 5 6 Run Power indicator PW Output indicator OUT Flicker OFF start Power Output Time limit contact NC 4 2 Run Power indicator PW Output indicator OUT Power 1 5 Time limit contact NO 4 3 Power 1 8 Time limit contact NO 4 3 5 6 Run Power indicator...

Page 4: ...1 s 0 1 to 1 s Yes 10 s 1 to 10 s No 1 min 0 1 to 1 min No 10 min 1 to 10 min No H3RN 11 H3RN 21 1 min 0 1 to 1 min Yes 10 min 1 to 10 min No 1 h 0 1 to 1 h No 10 h 1 to 10 h No Note The left two DIP switch pins are used to select the time ranges Operating Modes Operating mode Setting Factory set ON delay Yes Interval No Flicker OFF start No Flicker ON start No Note The right two DIP switch pins a...

Page 5: ...h 05 for SPDT or 08 for DPST NO P2RF j E P2R j7P Note 1 The value shown indicates the dimension for the P2RF 05 E with the PFP jN Mounting Rail The value is 71 5 mm when using the PFP Nj2 2 The value shown in parentheses indicates the di mension for the P2RF 08 E with the PFP jN Mounting Rail The value is 75 5 mm when using the PFP Nj2 P2RF j E Socket H3RN Series H3RN Series P2R j7P Socket 80 9 se...

Page 6: ...e as shown in the following timing charts H3RN 2 21 Note t Set time Rt Reset time Timer circuit External input Power 3 8 External short circuit 1 4 External input 1 3 Time limit contact NO 6 5 Run Power indicator PW Output indicator OUT 50 ms min Caution Be careful when connecting wires Mode Terminals Pulse operation Power supply between 3 and 8 Short circuit between 4 and 1 Input signal between b...

Page 7: ...y cause short cir cuiting at three points otherwise short circuiting of the power sup ply may occur because the SPDT contact of H3RN 1 11 is com posed of an SPST NC contact Power supply for load Short circuit current 3 4 2 1 5 Donot set totheminimum settingintheflickermodes otherwisethe contact may be damaged Donot usetheH3RNinplaces wherethereis excessive dust corro sive gas or direct sunlight Ma...

Page 8: ...H3RN H3RN 11 ...

Page 9: ...pan Phone 06 949 6012 Fax 06 949 6021 ALL DIMENSIONS SHOWN ARE IN MILLIMETERS To convert millimeters into inches multiply by 0 03937 To convert grams into ounces multiply by 0 03527 Cat No L090 E1 1B In the interest of product improvement specifications are subject to change without notice Printed in Japan 0996 2M 0296 a ...

Reviews: