Communication speed

selection

(Baud rate selection)

1138h

C071

144Bh

C071

03(2400bps)/ 04(4800bps)/

05(9600bps)/ 06(19.2kbps)/

07(38.4kbps)/ 08(57.6kbps)/

09(76.8kbps)/ 10(115.2kbps)

Communication station No.

1139h

C072

144Ch

C072

1~247

Communication parity

selection

113Bh

C074

144Eh

C074

00: No/ 01: Even/ 02: Odd

Communication stop bit

selection

113Ch

C075

144Fh

C075

1: 1 bit

2: 2 bits

Communication error

selection

113Dh

C076

1450h

C076

00: Trip

01: Trip after deceleration stop

02: Ignore

03: Free-run stop

04: Deceleration stop

Communication error

timeout

113Eh

C077

1451h

C077

0: Timeout disabled

1 to 9999

0.01[s]

Communication wait time

113Fh

C078

1452h

C078

0~1000

1[ms]

FV adjustment

1141h

C081

1455h

C081

FI adjustment

1142h

C082

1456h

C082

UP/DWN selection

1149h

C101

00︓OFF

01︓ON

-

1469h

C101

00: Not store frequency data

01: Store frequency data

-

Reset selection

114Ah

C102

00: Trip reset at power-on

01: Trip reset when the power is

OFF

02: Enabled only during trip (Reset

when the power is ON.)

-

146Ah

C102

00: Trip reset at power-on

01: Trip reset at power-off

02: Enabled only during trip (Reset

at power-on)

03: Trip reset only

-

Logic operation function A

input

1150h

C141

1492h

C142

Logic operation function B

input

1151h

C142

1493h

C143

Logic operator selection

1152h

C143

00︓AND/01︓OR/02︓XOR

-

1494h

C144

00:AND

01:OR

02:XOR

-

Output terminal P1 ON delay 1153h

C144

1486h

C130

Output terminal P1 OFF

1154h

C145

1487h

C131

Relay output ON delay

1157h

C148

1490h

C140

Relay output OFF delay

1158h

C149

1491h

C141

Motor capacity selection

1165h

H003

1503h

H003

2nd motor capacity selection 1541h

H203

2503h

H203

Motor pole number selection 1166h

H004

1504h

H004

2nd motor pole number

1542h

H204

2504h

H204

Stabilization parameter

1168h

H006

1507h

H006

2nd stabilization parameter

1544h

H206

2507h

H206

Enter command

0900h

-

Indefinite value

-

0900h

-

1

-

2/4/6/8

1[ 極 ]

00:2P/ 01:4P/ 02:6P/ 03:8P

04~23:10~48Pは設定しないでください

-

0. ~ 255.

1[%]

0~255

1[%]

0 ~ 1000

0.1[s]

0~1000

0.1[s]

-

00:0.1/ 01:0.2/ 02:0.4/ 03:0.55/

04:0.75/ 05:1.1/ 06:1.5/ 07:2.2/

08:3.0/ 09:3.7/ 10:4.0/ 11:5.5/

12:7.5/ 13:11.0/ 14:15.0/ 15:18.5

-

00︓0.2/ 02︓0.4/ 04︓0.75/ 06︓

1.5/ 07︓2.2/ 09︓3.7/ 11︓5.5/ 12︓

7.5

0 ~ 2000

0.1[%]

0~2000

0.1[%]

00︓RUN/01︓FA1/02︓FA2/03︓

OL/04︓OD/05︓AL/06︓Dc/07︓

FBV/08︓NDc/10︓ODc(使用しない で

ください)/43︓LOC

-

Same as C021 (Except 33 (LOG1) to

35 (LOG3), 63 (OPO), and 255 (no))

-

Do not change through ModBus

communication. For setting, refer to

"ModBus Setting" (4-78).

-

 

 

Please note that 3G3MX2-V1 does not provide the following functions: 

   

Register No.

Parameter No.

Overload limit source selection

10BBh

b028

2nd overload limit source selection

152Ch

b228

AM adjustment

10CFh

b080

Monitor display selection

10D8h

b089

Overvoltage LAD stop function

10F5h

b130

Overvoltage LAD stop function level setting

10F6h

b131

Ready function selection

10F9h

b151

PID FB upper limit

112Eh

C052

PID FB lower limit

112Fh

C053

Operator/ModBus selection

1137h

C070

AM offset adjustment

1145h

C086

Function name

3G3JX

 

Summary of Contents for 3G3JX

Page 1: ...Simple Compact Inverters JX series Replace Guide From 3G3JX to 3G3MX2 3G3MX2 A 3G3JX A I924 E1 01...

Page 2: ...ith respect to the use of the information contained herein Moreover because OMRON is constantly striving to improve its high quality products the information contained in this manual is subject to cha...

Page 3: ...afe use and precautions for correct use Intended Audience This guide is intended for the following personnel Personnel in charge of introducing control equipment Personnel in charge of designing contr...

Page 4: ...ity or the results from the use of Products in combination with any electrical or electronic components circuits system assemblies or any other materials or substances or environments Any advice recom...

Page 5: ...Liability Change in Specifications Product specifications and accessories may be changed at any time based on improvements and other reasons It is our practice to change part numbers when published r...

Page 6: ...derstand the manuals for all devices and equipment that will make up the system to ensure that the system is used safely Review the entire contents of these manuals including all safety precautions pr...

Page 7: ...to install and wire the inverter set parameters needed to operate the inverter and remedies to be taken and inspection methods to be used in case that problems occur 3G3MX2 Series Type V1 Multi functi...

Page 8: ...History A manual revision code appears as a suffix to the catalog number on the front and back covers of the manual Revision code Date Revised content 01 July 2019 Original production Cat No I924 E1 0...

Page 9: ...al Dimensions 13 4 Arrangement and Function of Terminal Block 17 4 1 Control Circuit Terminal Block 17 5 Functional difference 19 5 1 Dual duty rating 19 5 2 Modbus communication 19 6 Parameter List 2...

Page 10: ...10 1 Target model 1 Replaced old model 3G3JX series Compact Simplified Inverter 3G3JX 2 New model 3G3MX2 Series Type V1 Multi function Compact Inverter 3G3MX2 V1...

Page 11: ...ferences between 3G3JX and 3G3MX2 V1 in default parameter values and parameter functions refer to this guide For details of functions refer to related product user s manuals at the time of setting 6 T...

Page 12: ...140 128 170 5 0 0 4 5 A2055 180 250 169 4 164 235 6 A2055 V1 140 260 155 0 0 6 A2075 180 250 169 4 164 235 6 A2075 V1 140 260 155 0 0 6 3 phase 400 V class 3G3JX Series 3G3MX2 V1 Series Model 3G3JX D...

Page 13: ...V1 3 phase 200 V input specifications 2 When using 3G3JX AE with single phase 200 V input select from 3G3MX2 V1 single phase 200 V input specifications 3 2 External Dimensions 3G3JX Series 3G3MX2 V1 S...

Page 14: ...s Model 3G3JX D mm D1 mm D2 mm A4004 130 5 28 2 6 AE007 A2015 157 5 55 6 A2022 A4007 A4015 A4022 AE015 AE022 Model 3G3MX2 D mm D1 mm A4004 V1 143 5 28 A2015 V1 170 5 55 A2022 V1 A4007 V1 A4015 V1 A402...

Page 15: ...15 3G3JX Series 3G3MX2 V1 Series Model 3G3JX A2037 A4037 Model 3G3MX2 A2037 V1 A4040 V1...

Page 16: ...16 3G3JX Series 3G3MX2 V1 Series Model 3G3JX A2055 A2075 A4055 A4075 Model 3G3MX2 A2055 V1 A2075 V1 A4055 V1 A4075 V1...

Page 17: ...ared with the safety input When the safety function selector switch is ON S3 and S4 are automatically set to safety input GS1 GS2 S5 Multi function input S5 TH Multi function input External thermistor...

Page 18: ...1 Multi function output terminal Safety monitor terminal used in common This terminal is automatically set to P1 EDM Safety monitor signal when the EDM function selector switch is turned ON PC Output...

Page 19: ...torque during acceleration and deceleration Light load VT This mode is for a fan pump or other device that operates at the rated motor torque or lower With a load tolerance of 120 of rated torque min...

Page 20: ...rameter arrangement parameter name and default value There are some difference of Parameter name settings number date range and arrangement between 3G3JX and 3G3MX2 V1 Before setting to refer this sec...

Page 21: ...nd control 9 2CH 2 step acceleration deceleration 2CH 2 step acceleration deceleration 11 FRS free run stop FRS Free run stop 12 EXT external trip EXT External trip 13 USP USP function UPS Power recov...

Page 22: ...3MX2 V1 Data No Code Function name Code Function name 0 RUN signal during RUN RUN Signal during RUN 1 FA1 constant speed arrival signal FA1 Constant speed arrival signal 2 FA2 over set frequency arriv...

Page 23: ...008h 0008h 0007h Multi function Input 3 0009h 0009h 0008h Multi function Input 4 000Ah 000Ah 0009h Multi function Input 5 000Bh 000Bh 000Ah Operation status 1 Run 0 Stop Interlocked with d003 000Eh 00...

Page 24: ...01Ch Fault Monitor 1 Fault 001Dh Fault Monitor 1 Inverter Status 001Eh 0 40000 LOW 001Fh 0 58000 HIGH 0020h Trip monitor 2 Current 0 1 A 0020h Output Current 0 01 A 0021h Trip monitor 2 Voltage 1 V 00...

Page 25: ...1048h A038 0 999 0 01 Hz 1238h A038 Starting Frequency to 999 In the high frequency mode 10000 0 01 Hz Jogging stop selection 1049h A039 00 Free run stop 01 Deceleration stop 02 DC injection braking...

Page 26: ...rgy saving operation 126Dh A085 00 Normal operation 01 Energy saving operation Energy saving response 1073h A086 0 1000 0 1 126Eh A086 0 1000 0 1 1074h A092 MSB 1274h A092 HIGH 1075h A092 LSB 1275h A0...

Page 27: ...8 200 2000 0 1 Soft lock selection 10BCh b031 00 Data other than b031 cannot be changed when terminal SFT is ON 01 Data other than b031 and the specified frequency parameter cannot be changed when ter...

Page 28: ...restart 01 Frequency matching restart 02 Frequency pull in restart Stop selection 10DAh b091 00 Deceleration Stop 01 Free run stop 135Eh b091 00 Deceleration stop 01 Free run stop Cooling fan control...

Page 29: ...nary 3 05 CF4 Multi step speed setting binary 4 06 JG Jogging 07 DB External DC injection braking 08 SET 2nd control 09 2CH 2 step acceleration deceleration 11 FRS Free run stop 12 EXT External trip 1...

Page 30: ...4 OD 05 AL 06 Dc 07 FBV 08 NDc 09 LOG 10 ODc Do not use 43 LOC 00 RUN During RUN 01 FA1 Constant speed arrival signal 02 FA2 Set frequency exceeded signal 03 OL Overload warning 04 OD Excessive PID de...

Page 31: ...delay 1153h C144 1486h C130 Output terminal P1 OFF 1154h C145 1487h C131 Relay output ON delay 1157h C148 1490h C140 Relay output OFF delay 1158h C149 1491h C141 Motor capacity selection 1165h H003 15...

Page 32: ...2019 0919 0919 I924 E1 01 Note Do not use this document to operate the Unit...

Reviews: