Load (AC Output) Connection
14
www.sinetech.co.za
8.
Load (AC Output) Connection
CAUTION:
To prevent continued supply to the load via the inverter during any mode of
operation, an additional disconnection device (circuit breaker) must be installed.
WARNING!
It's very important for system safety and efficient operation to use
appropriate cable for AC connection. To reduce risk of injury, please use the proper
recommended cable size as below:
Model
5KW
Nominal Grid Voltage
230VAC
Conductor cross-section (mm
2
)
6
AWG no.
10
Step 1:
Remove insulation sleeve 8 mm
for three conductors. Shorten phase and neutral
conductors to 3 mm. Refer to chart 4.
Step 2: Connect wires according to polarities indicated on
terminal block. Be sure to connect PE protective
conductor (
)
first. Refer to Chart 5.
L
→
LINE (brown or black)
→
Ground (yellow-green)
N
→
Neutral (blue)
Step 3: Make sure the wires are securely
connected. The tightening torque is 0.8 N.m.
CAUTION:
Only connect load to
“AC
Output Connector
”
.
NEVER
connect the utility to “AC
Output Connector”.
CAUTION: Be sure to connect
L terminal of load to L terminal of “AC Output Connector”
and N terminal of load to N terminal of “AC Output Connector”. The G terminal of “AC
Output Connector” is connected to ground of the load. Do
NOT
swop connections.
CAUTION:
This inverter is not designed to operate in parallel. Do
NOT
parallel connect
multiple inverters as this will damage the inverter. Not covered by warranty!
L
N
Chart 4
Chart 5