[email protected] | Installation manual Omnicomm 2.0 terminals v2.2
7
.16 | 41
Umin=Imin x R=0.004
А
x 910
Ω
=3.64
V
Umax=Imax x R=0.02
А
x 910
Ω
=18.2
V
The following parameters must be preset in Omnicomm Con
fi
gurator:
Parameter
Value
Input type
Analog
Minimum value of the measured value
0 (bars)
Voltage, corresponding to the minimum value (V)
3.64
Maximum value of the measured value
10 (bars)
Voltage, corresponding to the maximum value (V)
18.2
Example 3. Impulse sensor for second engine RPM control
Purpose: control of additional engine frequency
It is necessary to control the speed of the engine that drives the working body of additional attachments and
processes data in Omnicomm Online (calculate work time, downtime, etc.). For example, for the purpose of
control, it was not possible to locate the signal, the frequency of which is proportional to engine speed, and
an additional proximity sensor, triggered by crossing of marking on the engine shaft, was identi
fi
ed; based
on the symmetry on the engine shaft, four markings were secured (Figure 52).
FIGURE 52
For sensors with N-P-N output transistor, connection must be established as shown Figure 96, and “pull-up
resistor” must be enabled in Omnicomm Terminal.
The following parameters must be preset in Omnicomm Configurator:
Parameter
Value
Input type
Impulse
Pull-up resistor
YES
Calibration coe
ffi
cient of impulse input
0.5