«Modbus function» – select the Modbus protocol function. Default
value – «0x03». Possible values:
• «0x03» – holding register reading
• «0x04» – input register reading
«Level» - the address of the register with fuel level is specified.
Default value – 40001. Possible values:
• 40001 to 49999 if Modbus function is «0x03»
• 30001 to 39999 if Modbus function is «0x04»
«Temperature» - the address of the register with sensor temperature
is specified. Default value - 40002. Possible values:
• 40001 to 49999 if Modbus function is «0x03»
• 30001 to 39999 if Modbus function is «0x04»
Installation and Connection
Put the mounting gasket on to the Omnicomm LLS-Ex 5 sensor
measuring probe.
Put the Omnicomm LLS-Ex 5 sensor in the tank and fix it:
• when securing with bolts, first put on a spacer and a spring washer
• it is possible to apply self-tapping screws for fixing at plastic tanks
with walls min 3 mm thick
Connect the Omnicomm LLS-Ex 5 as shown in the diagram (Figure 4).