Electronic version
General settings
“
Automatic adaptation
”
–
turn on for automatic adaptation of
measurements when dielectric permittivity of fuel is changed.
When
switching the automatic adjustment on, changes in level caused by
fuel expanding under temperature impact will also be reflected, i.e.
fuel level will be shown taking into account the current temperature.
“Network address” (1 to 254) – set the network address for the
Omnicomm LLS fuel level sensor. When several sensors are
connected to one external device, they should have unique network
addresses.
«Minimum level» (from 0 to 4094) - select the minimum reading for
the Omnicomm LLS-Ex 5 sensor. Default value – 0.
«Maximum level» (from 0 to 4095) - select the maximum reading for
the Omnicomm LLS-Ex 5 sensor. Default value – 4095.
“Filtration” – set the output signal filtration parameters:
For automatic adjustment of Omnicomm LLS-Ex 5 sensor calibration
values, the fuel tank shall be filled in up to the top during the VH
operation. In case of full refueling of the tank, maximum length of
the measuring part not emerged into the fuel shall not exceed 10 cm
from the sensor flange.
When operating the VH with insufficient fuel level in the tank,
automatic adjustment cannot be carried out.