22 | 

P a g e

 

 

 

5.4

 

Outputs 

Two output signals are available which may be configured for ON/OFF or PWM outputs through the Output Configuration 

registers 0x0124 and 0x0126 (Modbus 0xf092 and 0xf093).  

Note: 

The Output Drive Type (Open Drain, inverting driver) is fixed. 

 

Outputs 

7

 

Output Driver 

Open Drain, Non 

inverting Driver 

Open Drain, Inverting 

Driver 

 

 

Open Drain, 

Inverting Driver 

 

 

Active State 

LOW 

HIGH 

 

 

 

PWM Rate 

100 Hz 

10 Hz 

1 Hz 

0.1 Hz 

 

15 

14 

13 

12 

11  10 

 

 

 

 

Output Type 

Null 

ON/OFF 

PWM 

Reserved 

 

5.4.1

 

PWM Rate 

The SP-005 probe outputs support the following PWM frequencies: 

 

PWM Rate

 

Name 

Description 

100 Hz  PWM signal has constant 100 Hertz frequency (10 

msec repetition rate) with 0 – 100 % duty cycle

 

10 Hz  PWM signal has constant 10 Hertz frequency (100 

msec repetition rate) with 0 – 100 % duty cycle 

1 Hz 

PWM signal has constant 1 Hertz frequency (1 second 

repetition rate) with 0 – 100 % duty cycle 

0.1 Hz  PWM signal has constant 0.1 Hertz frequency (10 

second repetition rate) with 0 – 100 % duty cycle 

5.4.2

 

Active State 

The SP-005 probe outputs may be configured as Active HIGH or Active LOW. When set to 1 (Active HIGH), the output 

will be high impedance when active. When set to 0 (Active LOW), the output will be low impedance when active. The 

Factory reset value is 0.

 

5.4.3

 

Output Drive 

The Output Drive is permanently set to 3, indicating that the output is configured as an Open Drain driver, allowing 

the DIN signal to override and read back the state of the output signal.

 

5.4.4

 

Output Type 

The SP-005 probe supports NULL (0), ON/OFF (1) or PWM (2) outputs. When set to NULL the output signal will be left 

in a high impedance state. When set to ON/OFF the Rate information has no affect. 

 

 

Summary of Contents for SP-005

Page 1: ...1 P a g e TM User sGuide Shop online at omega com e mail info omega com For latest product manuals www omegamanual info SP 005 Thermocouple and RTD Smart Probe...

Page 2: ...nly Customer Service 1 800 622 2378 USA Canada only Engineering Service 1 800 872 9436 USA Canada only U S A Headquarters Tel 203 359 1660 e mail info omega com Fax 203 359 7700 The information contai...

Page 3: ...Calibrate 14 5 1 2 3 Sensor Writeable 14 5 1 2 4 Smart Sensor 14 5 1 3 Thermocouple Configuration 14 5 1 3 1 Sensor Type Range 14 5 1 3 2 Apply Scaling 14 5 1 3 3 Lock 15 5 1 3 4 Assigned 15 5 1 3 5...

Page 4: ...Writeable 19 5 3 1 6 Smart Sensor 19 5 3 2 DIO Input Configuration 19 5 3 2 1 Lock 19 5 3 2 2 Apply Scaling 19 5 3 2 3 Assigned 19 5 3 2 4 Available 19 5 3 3 DIO Device Configuration 20 5 3 4 DIO IPSO...

Page 5: ...vice as it contains important information relating to safety and EMC Failure to follow all the safety precautions may result in injury and or damage to your equipment The following labels identify inf...

Page 6: ...to 2 thermocouple inputs or a single 2 3 or 4 wire RTD input The Layer N SP 005 features 2 configurable digital I O pins These can be used for a myriad of applications including driving relays physic...

Page 7: ...to the SP 005 If you are connecting wire directly to the SP 005 view the wiring diagrams provided below Pin Name Function Pin 1 DIO 0 Discrete I O Signal 0 Pin 2 INTR Interrupt Signal Pin 3 SCL I2C Cl...

Page 8: ...ot automatically detect your device follow these instructions to manually connect it Step 1 Click on the icon located on the top left of the SYNC interface Step 2 Proceed through the Add Device Wizard...

Page 9: ...checking correctness of character by adding an extra bit to the character and setting the value based on all the other bits in the character StopBits The number of bits used to indicate the end of the...

Page 10: ...be performed as described below Step 1 Ensure your thermocouple has been configured in the previous section and click Calibration beneath the input interface Step 2 Insert the probe into 0 C 32 F refe...

Page 11: ...wn Step 2 Click the input you wish to configure and select your RTD type from the Device Range Type dropdown Step 3 Click the Wire dropdown and choose your wiring configuration 4 5 Setting Alarms Alar...

Page 12: ...he Output Configuration Tab in SYNC and click on the icon located to the right of the available outputs Clicking the icon will open Define ON OFF Control dialog box as seen below Choose the input with...

Page 13: ...nformation is provided in sensor specific IPSO object descriptions which include extended measurement type precision and tracking of minimum maximum readings Each enumerated Sensor has a Descriptor Ba...

Page 14: ...s set the sensor value may be overwritten with a preset value This capability is useful in sensors such as up down counters where a preset or possibly a zero value must be written to the sensor value...

Page 15: ...PSO object type information The Range information is Thermocouple Type dependent Offset Name Value Description 0x00 Sensor Type 3303 Temperature oC 0x02 Precision 1 Provides reading of xxx x 0x04 Sens...

Page 16: ...The RTD interface provides a measurement of Temperature in C Sensor Type SI Derived Units Measurement 0x21 C RTD Temperature 5 2 2 RTD Input Data Type Format The SP 005 supports extended configuration...

Page 17: ...will be used to adjust the sensor reading Result Raw Reading Gain Offset 5 2 3 3 Lock If set the user specified units of measure string 4 character maximum will be used in place of the default units...

Page 18: ...the IPSO min max values Sensor Trigger Function 7 6 5 4 3 2 1 0 0 0 0 0 0 0 0 Reset Min Max 15 14 13 12 11 10 9 8 0 0 0 0 0 0 0 0 5 3 Digital Input Output Interface The DIO Interface provides 2 digita...

Page 19: ...t or possibly a zero value must be written to the sensor value 5 3 1 6 Smart Sensor Refer to the Smart Sensor Device Interface documentation 5 3 2 DIO Input Configuration DIO Input Configuration 7 6 5...

Page 20: ...PSO object type information The SP 010 DIO IPSO definition is at base address 0x08a8 Offset Name Value Description 0x00 Sensor Type 3349 Bit Mapped Digital 0x02 Precision 0 Provides reading of xxx 0x0...

Page 21: ...he output LOW When the state of the DIO input signal is to be read the processor applies 3 0 VDC to the Input Bias signal and reads the level detected at the Input Sense If the output is inactive an e...

Page 22: ...10 Hz PWM signal has constant 10 Hertz frequency 100 msec repetition rate with 0 100 duty cycle 2 1 Hz PWM signal has constant 1 Hertz frequency 1 second repetition rate with 0 100 duty cycle 3 0 1 H...

Page 23: ...Compatible with OEG SYNC configuration software Layer N Cloud and Modbus Networks THERMOCOUPLE ACCURACY TABLE Type Range Accuracy J 210 C to 1200 C 0 4 C K 160 C to 1372 C 0 4 C T 190 C to 400 C 0 4 C...

Page 24: ...A if the unit is found to be defective it will be repaired or replaced at no charge OMEGA s WARRANTY does not apply to defects resulting from any action of the purchaser including but not limited to m...

Page 25: ...s M U Turbine Paddlewheel Systems M U Totalizers Batch Controllers pH CONDUCTIVITY M U pH Electrodes Testers Accessories M U Benchtop Laboratory Meters M U Controllers Calibrators Simulators Pumps M U...

Reviews: