11 |
P a g e
4.4
RTD Interface
The SP-005 supports 100, 500, and 1000 ohm Platinum RTD sensors in 2, 3, and 4-wire configurations. To use these
features, follow these steps:
Note:
A single RTD connection is supported.
Step 1:
Click the
Inputs Configuration Tab
on SYNC and choose your input type from the
Type
dropdown.
Step 2:
Click the input you wish to configure and select your RTD type from the
Device Range/Type
dropdown.
Step 3:
Click the
Wire
dropdown and choose your wiring configuration.
4.5
Setting Alarms
Alarms are set by clicking the
icon in SYNC on the desired input signal found in the
Inputs Configuration Tab
. Setup
the threshold and alarm type in the
Condition
section and then select which output to turn on in the
Action
section. The
alarm can be set to be latching or non-latching in the
Recovery
section.