7.10
Digital Output Configuration
Two output signals are available which may be configured for ON/OFF, PWM or SERVO outputs through the Output
Configuration registers (0x0124 and 0x0126). The remaining outputs are assigned as phantom devices which are
non-configurable. The highlighted entries show typical default configurations.
Digital Output Configuration
7
6
5
4
3
2
1
0
Output Configuration
Servo Range
1.0
–
2.0
0
0.5
–
2.5
1
Active State
LOW
0
HIGH
1
Rate
100 Hz
0 0 0
10 Hz
0 0 1
1 Hz
0 1 0
0.1 Hz
0 1 1
50 Hz
1 0 0
33 Hz
1 0 1
25 Hz
1 1 0
20 Hz
1 1 1
15
14
13
12
11 10
9
8
Output Type
Sensor Mapping
No Mapping
0
-
-
Sensor 0
1
0
0
Sensor 1
1
0
1
Sensor 2
1
1
0
Sensor 3
1
1
1
Mapping Enable
Not
Enabled
0
Enabled 1
Output Type
Null
0
0
0
0
ON/OFF
0
0
0
1
PWM
0
0
1
0
Servo
0
0
1
1
Rate
The Rate determines the repetition rate, or frequency, of the Digital Output. For On/Off outputs the rate
field is ignored.
PWM Rate
The SP-003/SP-004 supports the following PWM frequencies:
PWM Rate
Name
Description
0
100 Hz
PWM signal has constant 100 Hertz frequency (10 msec repetition
rate) with 0
–
100 % duty cycle
1
10 Hz
PWM signal has constant 10 Hertz frequency (100 msec repetition
rate) with 0
–
100 % duty cycle
2
1 Hz
PWM signal has constant 1 Hertz frequency (1 sec repetition rate)
with 0
–
100 % duty cycle
3
0.1 Hz
PWM signal has constant 0.1 Hertz frequency (10 second
repetition rate) with 0
–
100 % duty cycle