Appendix: SP-003/SP-004 Registers
The following Appendix provides the registers and list index for the Omega Link SP-003/SP-004 Environmental
Monitoring Smart Probe. This information is intended to aid users who will be making configurations and adjustments
to their Omega Link SP-003/SP-004 Environmental Monitoring Smart Probe through the Command Line Interface or
other custom interfaces.
Smart Probe devices share a common platform architecture that provides extensive monitoring and control
capabilities through a set of platform generic registers. These registers may be accessed using I2C based commands
directly to the Smart Probe devices or through a set of Modbus based registers when using Omega Interface devices.
Refer to the
Smart Sensor Device Interface
manual for further information.
When powered on or after a device reset each Smart Sensor based device will enumerate 1 or more sensor instances
which are described by the device specific Sensor Descriptors which include configuration options, measurement type
and units of measure for the corresponding sensor values. Additional sensor information is provided in sensor specific
IPSO object descriptions which include extended measurement type, precision and tracking of minimum/maximum
readings. Sensors are always enumerated in the order Apparent Heat (EH), Dewpoint (D), Temperature (T), Relative
Humidity (RH), Barometric Pressure (P) and DIO. Each enumerated Sensor has a Descriptor Base address location and
a Sensor IPSO / Configuration structure address location based on the sensor mix selected.
Sensor
Descriptor Base
IPSO/Configuration
Enumerated Sensor Mix
0
0x0060 (0xf030)
0x08a8 (0xf454)
T
T
T
D
EH
1
0x0068 (0xf034)
0x09a8 (0xf4d4)
DIO
RH
RH
T
D
2
0x0070 (0xf038)
0x0aa8 (0xf554)
DIO
B
RH
T
3
0x0078 (0xf03c)
0x0ba8 (0xf5d4)
DIO
B
RH
7.1
Sensor Values
Sensors use
float
values which represent the measured value in the indicated units of measure.
Sensor
Name
Modbus
Address
I2C
Address
Size
Description
0
Sensor 0 Data
0xf01e
0x003c
float Sensor Reading
1
Sensor 1 Data
0xf020
0x0040
float Sensor Reading
2
Sensor 2 Data
0xf022
0x0044
float Sensor Reading
3
Sensor 3 Data
0xf024
0x0048
float Sensor Reading
7.2
Sensor Names
Each sensor has a name. The default names for the outputs are
created based on the value being measured
. The
default names may be overwritten, such as ‘
Room_Temp
’ or ‘
Oven_Temp
’. Names are restricted to 16 characters.
Output
Name
Modbus
Address
I2C
Address
Size
Description
0
Sensor 0 Name
0xf700
0x0e00
char[16] Defaults depends on Sensor
1
Sensor 1 Name
0xf708
0x0e10
char[16] Defaults depends on Sensor
2
Sensor 2 Name
0xf710
0x0e20
char[16] Defaults depends on Sensor
3
Sensor 3 Name
0xf718
0x0e30
char[16] Defaults depends on Sensor
The Sensor names are retained until a factory reset occurs. It is strongly recommended that:
1)
Spaces within the name should be replaced with the ‘_’ character.