background image

4

M E C H A N I C A L   I N S TA L L AT I O N

Standard, Food Grade and Stub Probe Mounting:  

(See Figures 3 & 4)

1)

Select a mounting location in accordance with the Pre-
Installation Recommendations.

2)

If using a welded fitting, cut a hole into the side/top of the 
vessel corresponding to the mounting connection (1-1/4” 
NPT or 3/4” NPT).  If using a mounting plate, cut a 2-1/2 inch
(64 mm) center hole and six 11/32 inch(9mm) mounting 
holes (for 5/16” bolts) on a 7 inch (178 mm)bolt circle.  Use
mounting plate as a template.

3)

Weld fitting or attach mounting plate to vessel wall.  

4)

Insert probe through fitting.  Do not use sealant tapes (e.g. 
Teflon tape) or putties.  When using the 1-1/4” NPT 
connection, grease threads with anti-seize then thread unit 
tightly into place by gripping and rotating housing.  When 
using the 3/4” NPT connection, thread unit tightly into place
by gripping and rotating 15/16 inch (24 mm) wrench flats 
provided on fitting.  Continuity between sensor mounting 
point and vessel wall must be maintained to assure proper 
probe operation.

Figure 4

Figure 3

DIMENSIONS ARE SHOWN IN INCHES WITH MILLIMETER EQUIVALENT IN BRACKETS

Factory Wiring:

The LV800 probe wires are connected to the backside of the
PCB.    DO NOT alter this connection.  Doing will likely cause
improper operation of the sensor.

Permanently Connected Equipment:

Disconnecting devices shall by included in the system installa-
tion.  In installations were multiple circuits are used (i.e. inde-
pendent circuits for power input and output relay), individual
disconnects are required.  The disconnects shall be within
close proximity of the equipment, accessible to operators, and
marked appropriately as the disconnect for the associated cir-
cuit.  Assure the disconnect ratings are appropriately sized for
the circuit protected (See Specifications).

Circuit Separation:

Two cable entry locations are provided to aid in maintaining
separation of "hazardous live" (typically mains voltages such as
115VAC and 230VAC) and limited circuits (typically control
voltages less than 30Vrms or 42.4VDC).  However, since the
LV800 single wiring compartment can not absolutely protect
against physical contact between multiple circuits, it is required
that all wiring used must have an insulation rating of 300V min-
imum, and a temperature rating of 80˚ C (176˚ F) minimum.

Protective Earthing:

Each LV800 is provided with a "protective conductor terminal"
which shall be terminated to the local earth ground potential to
eliminate shock hazard in the unlikely event of internal insula-
tion breakdown.  Select wire size that can carry in excess of the
sum of all circuit's maximum amperage.

E L E C T R I C A L   I N S TA L L AT I O N

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Summary of Contents for LV800 SERIES

Page 1: ...omega com e mail info omega com For latest product manuals omegamanual info LV800 SERIES Capacitance Point Level Sensors Shop online at User sGuide...

Page 2: ...8280 Guyancourt France TEL 33 0 1 61 37 2900 FAX 33 0 1 30 57 5427 Toll Free in France 0800 466 342 e mail sales omega fr Germany Austria Daimlerstrasse 26 D 75392 Deckenpfronn Germany TEL 49 0 7056 9...

Page 3: ...of this manual pertaining to SAFETY Doing so will ensure proper oper ation of the equipment and the safety of all personnel Before discarding shipping container please inspect it thoroughly and verify...

Page 4: ...for at least 8 to 12 inches 203 305 mm of probe coverage When sensing highly conductive materials or those with a high dielectric constant the LV800 can perform as a tip sensitive sensor 2 Vessel Con...

Page 5: ...tion Doing will likely cause improper operation of the sensor Permanently Connected Equipment Disconnecting devices shall by included in the system installa tion In installations were multiple circuit...

Page 6: ...th utilize the simple 2 Step Calibration procedure One procedure sets the sensitivity with the probe being exposed to the material while the second pro cedure exposes the probe to free air only Since...

Page 7: ...tions are reversed when no material is sensed and high fail safe is selected Relay is energized Figure 7 LV800 Indicators See Figure 9 1 Yellow LED Its status describes the sensing condition of the LV...

Page 8: ...nd when no material is sensed If Fail safe High mode is used the designations are reversed Swap wire terminations of N O and N C if necessary Changing the fail safe selection is not recommended Fuse R...

Page 9: ...8 MECHANICALS Standard Probe Stub Probe DIMENSIONS ARE SHOWN IN INCHES WITH MILLIMETER EQUIVALENT IN BRACKETS...

Page 10: ...essential that all instructions in this manual be followed to ensure proper operation of the equipment and safety of operating person nel Use of equipment not specified herein may impair protection p...

Page 11: ...erwise shall not exceed the purchase price of the component upon which liability is based In no event shall OMEGA be liable for consequential incidental or special damages CONDITIONS Equipment sold by...

Page 12: ...bine Paddlewheel Systems M U Totalizers Batch Controllers pH CONDUCTIVITY M U pH Electrodes Testers Accessories M U Benchtop Laboratory Meters M U Controllers Calibrators Simulators Pumps M U Industri...

Reviews: