FP90 Series Flow Transmitter Instructions
Adjust the LCD contrast for best viewing. A setting of 1 is lower contrast, 5 is higher.
Select lower contrast if the display is in warmer ambient surroundings.
Set the decimal to the best resolution for your application. The display will automatically
scale up to this restriction.
Select *****., ****.*, ***.**, **.*** or *.****
Set the totalizer decimal to the best resolution for your application.
Select ********., *******.*, or ******.**
OFF provides the quickest output response to changes in ow.
Options are 8 seconds, 20 seconds, 50 seconds or 120 seconds.
Longer averaging produces more stable display and output response.
Locked: The Key Code must be entered to reset the resettable totalizer.
Unlocked: No key code required to reset the resettable totalizer.
Adjust the minimum and maximum current output. The display value represents the
precise current output.
Adjustment limits:
• 3.80 mA < 4.00 mA > 5.00 mA
• 19.00 mA < 20.00 mA > 21.00 ma
Use this setting to match the system output to any external device
Press UP and DOWN keys to manually order any output current value from 3.6 mA to
21.00 mA to test the output loop.
Press UP and DOWN keys to manually toggle the state of relay 1.
Repeat for relay 2.
Options Menu for FP90-2
Display
(Factory settings shown)
Description
Contrast:
3
>
Flow Decimal:
***.**
>
Total Decimal:
********.
>
Averaging:
Off
>
Total
Reset:
Lock
Off
>
Loop
Adjust:
4.00 mA >
Loop
Adjust:
20.00 mA >
Test
Loop:
>
Test Relay 1:
>