 FP90 Series Flow Transmitter Instructions

•   Remove power to unit before wiring input and 

output connections.

•   Follow instructions carefully to avoid personal 

injury.

Omega FP90 Series Flow Transmitter Instructions

Contents

1. Installation
2. Speci 

cations

3. Electrical Connections
4. Menu Functions

• 

Update rate: 100 ms

• 

Loop accuracy: ±0.03 mA

Open-collector output: Hi, Lo, Frequency, Pulse Programmable  
• 

Optically isolated, 50 mA max. sink, 30 VDC max. pull-up 
voltage.

• 

Maximum pulse rate:   

300 pulses per minute

• Hysteresis: 

  

Adjustable

Relay outputs (2 sets mechanical SPDT contacts):
• 

Hi, Lo, Frequency, Pulse Programmable (300 pulses/min max)

• 

Maximum voltage rating:  5 A @ 30 VDC, 5 A @ 250 VAC 
resistive load

• 

Hysteresis:  User adjustable

Environmental

• 

Operating temperature:  -10 to 70°C (14 to 158°F)

• 

Storage temperature:  

-15 to 80°C (5 to 176°F)

• 

Relative humidity: 

0 to 95%, non-condensing

• 

Maximum altitude: 

2000 m (6562 ft)

• Insulation 

category: 

II

• Pollution 

degree: 

2

Standards and Approvals

• CE
• Immunity:  EN50082-2
• Emissions:  EN55011
• Safety: 

EN61010

• 

Manufactured under ISO 9001 and ISO 14001

Specifi cations

General

Accuracy:  

 

±0.5 Hz

Enclosure:
• 

Rating: 

 

NEMA 4X/IP65 front

• Case: 

 

PBT

• 

Panel case gasket: 

Neoprene

• 

Window: 

 

Polyurethane coated polycarbonate

• 

Keypad: 

 

Sealed 4-key silicone rubber

• 

Weight: 

 

Approx. 325g (12 oz.)

Display:
• 

Alphanumeric 2 x 16 LCD

• 

Update rate:    

1 second

• 

Contrast:  

 

User selected, 5 levels

• 

Thermal sensitivity shift:   ±0.005% of reading per °C

Electrical

• 

Power:  

 

12 to 24 VDC ±10%, regulated,

 

  

 

21 mA max current

Sensor Input: 
• 

Range:  

 

0.5 to 1500 Hz

• 

Sensor power: 

2-wire: 1.5 mA @ 5 VDC ± 1%

 

  

 

 3 or 4 wire: 20 mA @ 5 VDC ± 1%

• 

Optically isolated from current loop

• 

Short circuit protected

Current output: 
• 

4 to 20 mA, isolated, fully adjustable and reversible

• 

Max loop impedance: 

50  max. @ 12 V

 

  

 

325  max. @ 18 V

 

  

 

600  max. @ 24V

Installation

FP90 series transmitters are available in two styles: panel mount and  eld mount. The panel mount is supplied with the necessary 
hardware to install the transmitter. This manual includes complete panel mounting instructions.
Field mounting requires one of two separate mounting kits. The FP90IM integral kit joins the sensor and instrument together into a 
single package. The FP90UM Universal kit enables the transmitter to be installed virtually anywhere.
Detailed instructions for integral mounting or other  eld installation options are included with the FP90IM Integral kit or the 
FP90UM Universal kit.

Panel Installation 

  1.  The panel mount transmitter is designed for installation using a 1/4 DIN Punch. For manual panel cutout, an adhesive 

template is provided as an installation guide. Recommended clearance on all sides between instruments is 1 inch.

  2.  Place gasket on instrument, and install in panel.
  3.  Slide mounting bracket over back of instrument until quick-clips snap into latches on side of instrument.
  4.  To remove, secure instrument temporarily with tape from front or grip from rear of instrument. DO NOT RELEASE.
 

 

Press quick-clips outward and remove.

Flow 6.25 GPM

Total 1234567.8>

WARNING

92 mm
(3.6 in.)

97 mm

(3.8 in.)

56 mm 
(2.2 in.)

41 mm 
(1.6 in.

)

Optional
Rear
Cover

Panel Mount

SIDE VIEW

FRONT VIEW

96 mm

(3.8 in.)

96 mm
(3.8 in.)

Field Mount &

Panel Mount

SIDE VIEW

Field Mount w/
Integral kit

102 mm 

(4.0 in.)

96 mm

(3.8 in.)

quick-clip

gasket on

front side

of panel

panel

mounting

bracket

4

3

2

1

9

8

7

6

5

Summary of Contents for FP90 Series

Page 1: ...IES Flow Transmitters Flow6 25GPM Total1234567 8 www omega com e mail info omega com Shop online at ISO9002 CERTIFIED CORPORATEQUALITY MANCHESTER UK ISO9001 CERTIFIED CORPORATE QUALITY STAMFORD CT Use...

Page 2: ...C OMEGA Customer Service 1 800 622 2378 1 800 622 BEST Engineering Service 1 800 872 9436 1 800 USA WHEN TELEX 996404 EASYLINK 62968934 CABLE OMEGA Mexico En Espa ol 001 203 359 7803 e mail espanol om...

Page 3: ...mA 5 VDC 1 3 or 4 wire 20 mA 5 VDC 1 Optically isolated from current loop Short circuit protected Current output 4 to 20 mA isolated fully adjustable and reversible Max loop impedance 50 max 12 V 325...

Page 4: ...ble length is 200 ft for FP5100 FP5200 FP5300 FP6000 and any sinusoidal ow signal Maximum cable length is 1000 ft for FP 5600 FP8501 FP2540 FP3 1500 FMG 3000 and FMG 550 and any square wave ow signal...

Page 5: ...r AUX Power System Pwr Loop System Pwr Loop AUX Power AUX Power 4 3 2 1 4 3 2 1 Transmitter 2 Terminals 4 3 2 1 PLC Terminals Loop Input 4 20 mA Transmitter Terminals System Pwr Loop System Pwr Loop A...

Page 6: ...r Terminals Power Supply 12 24 VDC Connection to a PLC with built in power supply Internal PLC Connection Connection to a PLC Recorder separate supply Example Two transmitters connected to PLC Recorde...

Page 7: ...on no current loop used Trans mitter Terminals Power S upply 12 24 VDC Connection to a PLC with built in power supply Internal PLC Connection Connection to a PLC Recorder separate supply Example Two t...

Page 8: ...n the ow rate moves above the setpoint plus the hysteresis value High Open Collector or Relay output Output triggers when the ow rate is greater than the setpoint The output will deenergize when the o...

Page 9: ...VIEW displays below are temporary The permanent display will return after ten minutes Flow1 123 4 GPM Flow2 567 8 GPM Delta Flow 10 5 GPM Tot1 1234567 8 Tot2 123456 78 Perm1 1234567 8 Gallons Perm2 12...

Page 10: ...Key Code is UP UP UP DOWN keys in sequence After entering the Key Code the display will show the rst item in the selected menu Step 3 Scroll menu with UP or DOWN arrow keys Step 4 Press RIGHT ARROW k...

Page 11: ...or different by x10 or x100 Limits 0 0001 to 99999 The K factor cannot be set to 0 Select the minimum and maximum values for the 4 20 mA Current loop output The FP90 will allow any values from 0 0000...

Page 12: ...epresents the precise current output Adjustment limits 3 80 mA 4 00 mA 5 00 mA 19 00 mA 20 00 mA 21 00 ma Use this setting to match the system output to any external device Active HIGH This setting is...

Page 13: ...ection upper or lower case This setting tells the transmitter how to convert the input frequency from the ow sensor into a volumetric total It also is used as the basis for the volumetric Pulse mode T...

Page 14: ...d output response Locked The Key Code must be entered to reset the resettable totalizer Unlocked No key code required to reset the resettable totalizer Adjust the minimum and maximum current output Th...

Page 15: ...alues for the Current loop output 1 The FP90 will allow any values from 0 0000 to 99999 Select the input source for Open Collector output 1 Flow sensor 1 Flow sensor 2 or Delta Flow Select the mode of...

Page 16: ...s Longer averaging produces more stable display and output response Lock Off No key code required to reset the resettable totalizer Lock On The Key Code must be entered to reset the resettable totaliz...

Page 17: ...t Volume setting Decrease pulse width setting Reduce system ow rate Enter K factor between 0 0001 to 99999 Reset the hysteresis value Flow rate exceeds display capability Relay or Open Collector pulse...

Page 18: ...page 16 OMEGA FP90 Series Flow Transmitter Instructions Notes...

Page 19: ...t liability or otherwise shall not exceed the purchase price of the component upon which liability is based In no event shall OMEGA be liable for consequential incidental or special damages CONDITIONS...

Page 20: ...rs Air Velocity Indicators Turbine Paddlewheel Systems Totalizers Batch Controllers pH CONDUCTIVITY pH Electrodes Testers Accessories Benchtop Laboratory Meters Controllers Calibrators Simulators Pump...