FP90 Series Flow Transmitter Instructions
• Remove power to unit before wiring input and
output connections.
• Follow instructions carefully to avoid personal
injury.
Omega FP90 Series Flow Transmitter Instructions
Contents
1. Installation
2. Speci
cations
3. Electrical Connections
4. Menu Functions
•
Update rate: 100 ms
•
Loop accuracy: ±0.03 mA
Open-collector output: Hi, Lo, Frequency, Pulse Programmable
•
Optically isolated, 50 mA max. sink, 30 VDC max. pull-up
voltage.
•
Maximum pulse rate:
300 pulses per minute
• Hysteresis:
Adjustable
Relay outputs (2 sets mechanical SPDT contacts):
•
Hi, Lo, Frequency, Pulse Programmable (300 pulses/min max)
•
Maximum voltage rating: 5 A @ 30 VDC, 5 A @ 250 VAC
resistive load
•
Hysteresis: User adjustable
Environmental
•
Operating temperature: -10 to 70°C (14 to 158°F)
•
Storage temperature:
-15 to 80°C (5 to 176°F)
•
Relative humidity:
0 to 95%, non-condensing
•
Maximum altitude:
2000 m (6562 ft)
• Insulation
category:
II
• Pollution
degree:
2
Standards and Approvals
• CE
• Immunity: EN50082-2
• Emissions: EN55011
• Safety:
EN61010
•
Manufactured under ISO 9001 and ISO 14001
Specifi cations
General
Accuracy:
±0.5 Hz
Enclosure:
•
Rating:
NEMA 4X/IP65 front
• Case:
PBT
•
Panel case gasket:
Neoprene
•
Window:
Polyurethane coated polycarbonate
•
Keypad:
Sealed 4-key silicone rubber
•
Weight:
Approx. 325g (12 oz.)
Display:
•
Alphanumeric 2 x 16 LCD
•
Update rate:
1 second
•
Contrast:
User selected, 5 levels
•
Thermal sensitivity shift: ±0.005% of reading per °C
Electrical
•
Power:
12 to 24 VDC ±10%, regulated,
21 mA max current
Sensor Input:
•
Range:
0.5 to 1500 Hz
•
Sensor power:
2-wire: 1.5 mA @ 5 VDC ± 1%
3 or 4 wire: 20 mA @ 5 VDC ± 1%
•
Optically isolated from current loop
•
Short circuit protected
Current output:
•
4 to 20 mA, isolated, fully adjustable and reversible
•
Max loop impedance:
50 max. @ 12 V
325 max. @ 18 V
600 max. @ 24V
Installation
FP90 series transmitters are available in two styles: panel mount and eld mount. The panel mount is supplied with the necessary
hardware to install the transmitter. This manual includes complete panel mounting instructions.
Field mounting requires one of two separate mounting kits. The FP90IM integral kit joins the sensor and instrument together into a
single package. The FP90UM Universal kit enables the transmitter to be installed virtually anywhere.
Detailed instructions for integral mounting or other eld installation options are included with the FP90IM Integral kit or the
FP90UM Universal kit.
Panel Installation
1. The panel mount transmitter is designed for installation using a 1/4 DIN Punch. For manual panel cutout, an adhesive
template is provided as an installation guide. Recommended clearance on all sides between instruments is 1 inch.
2. Place gasket on instrument, and install in panel.
3. Slide mounting bracket over back of instrument until quick-clips snap into latches on side of instrument.
4. To remove, secure instrument temporarily with tape from front or grip from rear of instrument. DO NOT RELEASE.
Press quick-clips outward and remove.
Flow 6.25 GPM
Total 1234567.8>
WARNING
92 mm
(3.6 in.)
97 mm
(3.8 in.)
56 mm
(2.2 in.)
41 mm
(1.6 in.
)
Optional
Rear
Cover
Panel Mount
SIDE VIEW
FRONT VIEW
96 mm
(3.8 in.)
96 mm
(3.8 in.)
Field Mount &
Panel Mount
SIDE VIEW
Field Mount w/
Integral kit
102 mm
(4.0 in.)
96 mm
(3.8 in.)
quick-clip
gasket on
front side
of panel
panel
mounting
bracket
4
3
2
1
9
8
7
6
5