 FP90 Series Flow Transmitter Instructions

All functions labeled "1" will repeat for channel 2.

Calibrate Menu for FP90-3 

Display

(Factory settings shown)

Description

The  rst two characters set the Flow Rate units of measure. They have no effect on calculations.
They may be any alpha or numeric character, upper or lower case.
The last character sets the Flow rate Timebase. Select S (seconds, M (minutes, H (hours) or D (days) 
 

 

 

This setting tells the transmitter how to convert the input frequency from the  ow sensor into a  ow rate. 
The K-factor is unique to the sensor model and to the pipe size and schedule.  Refer to data in the sensor 
manual for the correct value.  Limits:  0.0001 to 99999. (The K-factor cannot be set to 0)
 

 

 

 

 

 

This setting identi es the Totalizer units. It has no effect on any calculation. It serves as a label only. Each 
character can be any alpha or numerical selection, upper or lower case.
 

 

 

 

 

 

This setting tells the transmitter how to convert the   ow sensor signal into a volumetric total.  It also is 
used as the basis for the Open Collector pulse mode.
The setting is usually the same as the Flow K-factor, or different by x10 or x100.
Limits:  0.0001 to 99999. (The K-factor cannot be set to 0) 
  

 

 

 

 

 

Select the input source to be associated with Loop output #1:
Flow sensor #1, Flow sensor #2, or Delta Flow   

 

 

 

 

Select the minimum and maximum values for the Current loop output #1.
The FP90 will allow any values from 0.0000 to 99999. 

 

 

 

 

 

Select the input source for Open Collector output #1: Flow sensor #1, Flow sensor #2, or Delta Flow  

 

 

 

 

Select the mode of operation for Open Collector output #1.
Options available are High, Low, Pulse (volumetric), or Frequency (based on rate).
The signal may be disabled if not in use. 

 

 

 

 

 

In Low or High Mode, this Open Collector output will be activated when the Flow rate reaches this value.  
Be sure to modify this setting if you change the Flow Units.  
 

 

 

 

The Open Collector output will be deactivated at Setpoint ± Hysteresis, depending on High or Low 
Setpoint selection. 

 

 

 

 

 

In Pulse mode, Open collector output #1 will generate one pulse when this volume of  ow passes the 
sensor. (The measurement is based on the Total1 K-factor)
The FP90 will allow any value from 0.0000 to 99999. 

 

 

 

 

 

In Pulse mode, this setting de nes the duration of Open Collector output pulse #1.  The FP90 allows any 
value from 0.1 seconds to 999.9 seconds. 
 

 

 

 

 

 

In Frequency mode, Open Collector output #1 will simulate the sensor frequency, divided by this value.
The FP90 allows any value from ÷1  to ÷254.
 

 

 

 

 

 

Use this “notepad” to record important dates, such as annual recerti cation or scheduled maintenance.  
 

Flow1 Units:   

 GPM  > 

 

Flow1 K-Factor: 

 

 60.000  > 

 

 

Total1 Units:   

 Gallons  > 

 

 

Total1 K-Factor 

 

 60.00  > 

 

 

Loop1 Source: 

 

 Flow1  > 

 

 

Loop1 Range: GPM 

 

 

000.00 > 100.00 

 

 

Output1 Source: 

 

 Flow1  > 

 

 

Output1 Mode: 

 

 Low  > 

 

 

Output1 Setpoint 

 

 10.0 

GPM  > 

 

 

Output1 Hys:   

 5.0 

GPM  > 

 

 

Output1 Volume: 

 

 100.00 

Gallons  > 

 

 

Output1 Pulsewdth: 

 

 0.1 

Seconds  > 

 

 

Output1 Freq.: 

 

 

Divide by 1 

 

 

Last Cal 

 

 6-16-09  > 

Summary of Contents for FP90 Series

Page 1: ...IES Flow Transmitters Flow6 25GPM Total1234567 8 www omega com e mail info omega com Shop online at ISO9002 CERTIFIED CORPORATEQUALITY MANCHESTER UK ISO9001 CERTIFIED CORPORATE QUALITY STAMFORD CT Use...

Page 2: ...C OMEGA Customer Service 1 800 622 2378 1 800 622 BEST Engineering Service 1 800 872 9436 1 800 USA WHEN TELEX 996404 EASYLINK 62968934 CABLE OMEGA Mexico En Espa ol 001 203 359 7803 e mail espanol om...

Page 3: ...mA 5 VDC 1 3 or 4 wire 20 mA 5 VDC 1 Optically isolated from current loop Short circuit protected Current output 4 to 20 mA isolated fully adjustable and reversible Max loop impedance 50 max 12 V 325...

Page 4: ...ble length is 200 ft for FP5100 FP5200 FP5300 FP6000 and any sinusoidal ow signal Maximum cable length is 1000 ft for FP 5600 FP8501 FP2540 FP3 1500 FMG 3000 and FMG 550 and any square wave ow signal...

Page 5: ...r AUX Power System Pwr Loop System Pwr Loop AUX Power AUX Power 4 3 2 1 4 3 2 1 Transmitter 2 Terminals 4 3 2 1 PLC Terminals Loop Input 4 20 mA Transmitter Terminals System Pwr Loop System Pwr Loop A...

Page 6: ...r Terminals Power Supply 12 24 VDC Connection to a PLC with built in power supply Internal PLC Connection Connection to a PLC Recorder separate supply Example Two transmitters connected to PLC Recorde...

Page 7: ...on no current loop used Trans mitter Terminals Power S upply 12 24 VDC Connection to a PLC with built in power supply Internal PLC Connection Connection to a PLC Recorder separate supply Example Two t...

Page 8: ...n the ow rate moves above the setpoint plus the hysteresis value High Open Collector or Relay output Output triggers when the ow rate is greater than the setpoint The output will deenergize when the o...

Page 9: ...VIEW displays below are temporary The permanent display will return after ten minutes Flow1 123 4 GPM Flow2 567 8 GPM Delta Flow 10 5 GPM Tot1 1234567 8 Tot2 123456 78 Perm1 1234567 8 Gallons Perm2 12...

Page 10: ...Key Code is UP UP UP DOWN keys in sequence After entering the Key Code the display will show the rst item in the selected menu Step 3 Scroll menu with UP or DOWN arrow keys Step 4 Press RIGHT ARROW k...

Page 11: ...or different by x10 or x100 Limits 0 0001 to 99999 The K factor cannot be set to 0 Select the minimum and maximum values for the 4 20 mA Current loop output The FP90 will allow any values from 0 0000...

Page 12: ...epresents the precise current output Adjustment limits 3 80 mA 4 00 mA 5 00 mA 19 00 mA 20 00 mA 21 00 ma Use this setting to match the system output to any external device Active HIGH This setting is...

Page 13: ...ection upper or lower case This setting tells the transmitter how to convert the input frequency from the ow sensor into a volumetric total It also is used as the basis for the volumetric Pulse mode T...

Page 14: ...d output response Locked The Key Code must be entered to reset the resettable totalizer Unlocked No key code required to reset the resettable totalizer Adjust the minimum and maximum current output Th...

Page 15: ...alues for the Current loop output 1 The FP90 will allow any values from 0 0000 to 99999 Select the input source for Open Collector output 1 Flow sensor 1 Flow sensor 2 or Delta Flow Select the mode of...

Page 16: ...s Longer averaging produces more stable display and output response Lock Off No key code required to reset the resettable totalizer Lock On The Key Code must be entered to reset the resettable totaliz...

Page 17: ...t Volume setting Decrease pulse width setting Reduce system ow rate Enter K factor between 0 0001 to 99999 Reset the hysteresis value Flow rate exceeds display capability Relay or Open Collector pulse...

Page 18: ...page 16 OMEGA FP90 Series Flow Transmitter Instructions Notes...

Page 19: ...t liability or otherwise shall not exceed the purchase price of the component upon which liability is based In no event shall OMEGA be liable for consequential incidental or special damages CONDITIONS...

Page 20: ...rs Air Velocity Indicators Turbine Paddlewheel Systems Totalizers Batch Controllers pH CONDUCTIVITY pH Electrodes Testers Accessories Benchtop Laboratory Meters Controllers Calibrators Simulators Pump...

Reviews: