CALIBRATION

Once the transducer has been mounted, and air supply connections finished, the unit’s calibration must be checked before

placing into service.

Note: input percentage refers to the following examples:

M4110/

 IP211, EP211 SERIES

0519

A

5

If 4 to 20 mA

If 0 to 10 VDC

If 0 to 5 VDC

If 1 to 5 VDC

0% = 4 mA

0% = 0.00 VDC 

0% = 0.00 VDC 

0% = 1.00 VDC

25% = 8 mA

25% = 2.50 VDC 

25% = 1.25 VDC 

25% = 2.00 VDC

50% = 12 mA

50% = 5.00 VDC 

50% = 2.50 VDC 

50% = 3.00 VDC

75% = 16 mA

75% = 7.50 VDC 

75% = 3.75 VDC 

75% = 4.00 VDC

100% = 20 mA

100% = 10.00 VDC 

100% = 5.00 VDC 

100% = 5.00 VDC

Forward Acting

1.  Apply the 0% input signal to unit and adjust the “Zero” adjusting screw to the low setpoint output. Turn screw counter-

clockwise to increase output. If there is no change in output, keep turning adjustment screw counter-clockwise until

output begins to rise. It is imperative that the output pressure be closely monitored as turning the zero screw excessive-
ly could damage the flexure.

2.  Apply the 100% signal to unit and adjust “Span” adjusting screw until output is at the high setpoint.
3. 

IMPORTANT: 

On I/P (Current) input models, turn the “Span” adjusting screw counter-clockwise to increase output. On

E/P (Voltage) input models, turn the “Span” adjusting screw clockwise to increase the output pressure.

4.  Repeat steps 1& 2 until unit is calibrated.

Reverse Acting

1.  Apply the 0% input signal to unit and adjust "Zero" adjusting screw until output reaches the high output pressure set-

point. Turn counter-clockwise to increase.

2.  Apply the 100% input signal to unit and adjust "Span" adjustment until output pressure is at the low setpoint.

IMPORTANT:

On I/P (Current) input models, turn the “Span” adjusting screw clockwise to increase output. On E/P

(Voltage) input models, turn the “Span” adjusting screw counter-clockwise to increase the output pressure.

3.  Repeat steps 1& 2 until unit is calibrated.

Summary of Contents for EP211 Series

Page 1: ...e mail info omega com For latest product manuals www omegamanual info Shop online at omega com User sGuide IP211 EP211 SERIES ELECTROPNEUMATIC CONVERTERS...

Page 2: ...h America U S A Omega Engineering Inc Headquarters Toll Free 1 800 826 6342 USA Canada only Customer Service 1 800 622 2378 USA Canada only Engineering Service 1 800 872 9436 USA Canada only Tel 203 3...

Page 3: ...free location or such that the vibration is isolated to the X and Z axis as shown in Figure 3 Pipe Due to its light weight the transducer may be sup ported by the piping used for the supply and output...

Page 4: ...ntBody EN 50081 1 1992 Test results confirmed that no precautions need to be observed during installation regarding electro magneticemissionsfromtheI P E P211Transducers EN 50082 1 1992 The following...

Page 5: ...erative that the output pressure be closely monitored as turning the zero screw excessive ly could damage the flexure 2 Apply the 100 signal to unit and adjust Span adjusting screw until output is at...

Page 6: ...0 25 C COIL 300 J2 J1 I P SCHEMATIC RT1 R1 68 FIGURE 2 BLACK WHITE RV1 121 R1 100 25 C COIL 300 J2 J1 E P SCHEMATIC The input impedance will vary depending upon the potentiometer setting of the SPAN R...

Page 7: ...put pressure increases then follow calibration procedure 2 Electrical connection has opened or wrong type of signal applied 2 Check electrical connections to insure that there is a correct input signa...

Page 8: ...M4110 0519 IP211 EP211 SERIES A 8 Figure 3...

Page 9: ...oisture or vibration improper specification misapplication misuse or other operating conditions outside of OMEGA s control Components in which wear is not warranted include but are not limited to cont...

Page 10: ...Air Velocity Indicators Turbine Paddlewheel Systems Totalizers Batch Controllers pH CONDUCTIVITY pH Electrodes Testers Accessories Benchtop Laboratory Meters Controllers Calibrators Simulators Pumps I...

Reviews: