background image

SIGNAL IMPEDANCE

M4110/0519 IP211, EP211 SERIES

A

6

INPUT SIGNAL

OUTPUT RANGE

NOMINAL IMPEDANCE

(OHMS)

POTENTIOMETER RV1 SIZE

(OHMS)

4-20mA 

3-15 PSIG 

180 

1000

4-20mA 

3-27 PSIG 

215 

1000

4-20mA 

3-120 PSIG 

260 

1000

4-20mA 

2-60 PSIG 

225 

1000

0-5 VDC

3-15 PSIG 

615 

500

0-5 VDC 

3-27 PSIG 

530 

500

0-10 VDC 

3-120 PSIG 

800 

1000

0-5 VDC

2-60 PSIG

500

1000

4-20mA

6-30 PSIG

215

1000

BLACK

WHITE

RV1

121 Ω

R2

100   @ 25°C

Ω

COIL
300 Ω

J2

J1

I / P SCHEMATIC

RT1

R1

68 Ω

FIGURE 2

BLACK

WHITE

RV1

121 Ω

R1

100 Ω @ 25°C

COIL
300 Ω

J2

J1

E / P SCHEMATIC

The input impedance will vary depending upon the potentiometer setting of the “SPAN (RV1)”, (

SEE FIG. 2

). The I/P circuit design 

consists of a resistor and potentiometer in parallel with the coil/flexure. The E/P circuit utilizes a potentiometer in series with the 
coil/flexure. The following are some of the nominal impedences that would be measured across the signal leads of the average 
calibrated transducer. These values are helpful when determining power requirements and for trouble-shooting.

Summary of Contents for EP211 Series

Page 1: ...e mail info omega com For latest product manuals www omegamanual info Shop online at omega com User sGuide IP211 EP211 SERIES ELECTROPNEUMATIC CONVERTERS...

Page 2: ...h America U S A Omega Engineering Inc Headquarters Toll Free 1 800 826 6342 USA Canada only Customer Service 1 800 622 2378 USA Canada only Engineering Service 1 800 872 9436 USA Canada only Tel 203 3...

Page 3: ...free location or such that the vibration is isolated to the X and Z axis as shown in Figure 3 Pipe Due to its light weight the transducer may be sup ported by the piping used for the supply and output...

Page 4: ...ntBody EN 50081 1 1992 Test results confirmed that no precautions need to be observed during installation regarding electro magneticemissionsfromtheI P E P211Transducers EN 50082 1 1992 The following...

Page 5: ...erative that the output pressure be closely monitored as turning the zero screw excessive ly could damage the flexure 2 Apply the 100 signal to unit and adjust Span adjusting screw until output is at...

Page 6: ...0 25 C COIL 300 J2 J1 I P SCHEMATIC RT1 R1 68 FIGURE 2 BLACK WHITE RV1 121 R1 100 25 C COIL 300 J2 J1 E P SCHEMATIC The input impedance will vary depending upon the potentiometer setting of the SPAN R...

Page 7: ...put pressure increases then follow calibration procedure 2 Electrical connection has opened or wrong type of signal applied 2 Check electrical connections to insure that there is a correct input signa...

Page 8: ...M4110 0519 IP211 EP211 SERIES A 8 Figure 3...

Page 9: ...oisture or vibration improper specification misapplication misuse or other operating conditions outside of OMEGA s control Components in which wear is not warranted include but are not limited to cont...