Output Configuration Menu
20
20.2
Ot.SC.OF
Enter OUTPUT SCALE & OFFSET CONFIGURATION SUBMENU:
READING 1
Press ‘
RESET/ENTER
’
10) Display shows
"
REAd 1
"
Reading 1 menu.
Press ‘
RESET/ENTER
’
11) Display flashes 1st digit of previous
"
REAd 1
"
value.
Press ‘
䊱
/MAX
’ & ‘
䊳
/MIN
’ 12) Enter
"
REAd 1
"
value. (Example 000000).
Press ‘
RESET/ENTER
’
13) Display advances to
"
OUt 1
"
Output 1 menu.
OUTPUT 1
Press ‘
RESET/ENTER
’
14) Display flashes 1st digit of previous
"
OUt 1
"
value.
Press ‘
䊱
/MAX
’ & ‘
䊳
/MIN
’ 15) Enter
"
OUt 1
"
value. (Example 0000.00).
Press ‘
RESET/ENTER
’
16) Display advances to
"
REAd 2
"
Reading 2 menu.
READING 2
Press ‘
RESET/ENTER
’
17) Display flashes 1st digit of previous
"
REAd 2
"
value.
Press ‘
䊱
/MAX
’ & ‘
䊳
/MIN
’ 18) Enter
"
REAd 2
”
value. (Example 999999).
Press ‘
RESET/ENTER
’
19) Display advances to
"
OUt 2
"
Output 2 menu.
OUTPUT 2
Press ‘
RESET/ENTER
’
20) Display flashes 1st digit of previous
"
OUt 2
"
value.
Press ‘
䊱
/MAX
’ & ‘
䊳
/MIN
’ 21) Enter
"
OUt 2
"
value. (Example
0010.00
).
Press ‘
RESET/ENTER
’
22) Display Display shows
"
StOREd
"
stored message momentarily and
then advances to the
"
SP CNF
"
SetPoint Configuration menu.
The above example is for 0-10 V of the entire range of the process input and analog
output. For 0-20mA output you need to set
"
MOdE
"
to
"
CURRNt
"
DC-Current output and
"
OUt 2
"
to
0020.00
.
Ot.SC.OF
(Output Scale & Offset)
REAd 1
value
OUt 1
value
REAd 2
value
OUt 2
value