16
Input Configuration Menu
60
16.2
Ad.RAtE
Enter ANALOG TO DIGITAL RATE SUBMENU:
Press ‘
RESET/ENTER
’
7) Display flashes
"
0
"
or previous selection.
Press ‘
䊱
/MAX
’
8) Scroll through the 6 available selections as
0
,
1
,
2
,
3
,
4
, and
5
for
your choice of selection. Refer to below Table for your specific application
conversion speed. Only Rate 0 and 1 can reject 60 Hz / 50 Hz noise.
Refer to
Table 33-1
in Specification Section for different input and outputs types.
Rate
0
1
2
3
4
5
Time for 60hz(ms)
134.9 68.2
34.9
18.2
9.9
5.7
Time for 50Hz(ms)
161.9 81.9
41.9
21.9
11.9
6.9
Table 16-1. A/D (Analog to Digital) Rate Option Table
Press ‘
RESET/ENTER
’
9) Display advances to
"
MOdE
"
Input Mode Configuration Submenu. If a
change was made, the controller will also show
"
StOREd
"
stored
message momentarily.
16.3
MOdE
Enter INPUT MODE CONFIGURATION SUBMENU:
This submenu is only accessible if
"
tC
"
Thermocouple or
"
bRIdGE
"
Bridge is your selection of input type.
dISAbL
ENAbLE
IN.SC.OF
(Input Scale & Offset)
MOdE
Ad.RAtE
(Analog to Digital Rate)
0 1 2 3 4 5
LIN.FRE
(Line Frequency & Hz)
INP.CNF
(Input Configuration )
SP1.L.2.H
NORMAL
RAtIO
(Strain Ratio)
bRdG.LM
(Bridge Limit)
dISAbL
ENAbLE
C.JUN.OF
ENAbLE
CAL 0
(Field Calib.)
DISAbL
tC.CO.JC
(Thermocouple
Cold Junction)
50
60
Accessible IF
your INPUT selection:
bRIdGE
No
Accessible IF
your INPUT selection:
TC
SP1 value > lower overload limit.
SP2 value < upper overload limit.
Yes
No
Yes