53
Reading Configuration Menu
14
2.Cd In
READING SCALE & OFFSET 2-COORDINATE FORMAT MENU:
Input voltage or current can be converted or scaled into values appropriate for the process or signal
being measured. A reading may be displayed, for example, in units of weight or velocity instead of in
amperes and volts. The controller determines scale and offset values based on two user-provided input
values entered with the corresponding readings.
There are two methods to scale this meter to display readings in engineering units.
• The first method
"
ON.L INE
"
is to scale with known loads. Do this by applying known loads to a
transducer connected to a meter, or by simulating the output of the transducer with voltage or
current simulator.
• The second method
"
MANUAL
"
is to scale without known inputs. Do this by calculating input
values based on transducer specifications and manually entering them through the keyboard.
Press ‘
RESET/ENTER
’
17) Display shows
"
2.Cd INt
"
(2-coordinate format) and stops flashing if
display was prompted
"
2.Cd INt
"
.
If this scaling method is selected, calculate the input values to the
instrument based on the actual signal being received.
ON.L INE
Press ‘
RESET/ENTER
’
18) Display flashes
"
ON.L INE
"
On line method.
Press ‘
䊱
/MAX
’
19) Scroll between 2 available selections:
"
ON.L INE
”
or
"
MANUAL
"
for
the configuration option of your choice. If your choice of selection is
"
MANUAL
"
, skip to Step 28).
Press ‘
RESET/ENTER
’
20) Display stops flashing and shows
"
ON.L INE
"
.
Press ‘
RESET/ENTER
’
21) Display shows
"
INPUt 1
"
Item #1 of coordinate #1. Pressing
‘
RESET/ENTER
’ to sequence through:
"
INPUt 1
"
, Input 1 ’s value
"
REAd 1
"
, Read 1 ’s value
"
INPUt 2
"
, Input 2 ’s value
"
REAd 2
"
, Read 2 ’s value
headings for the desired selection to enter new value.