32
3.2.8 Alarm 2
This unit is equipped with two physical outputs that can only be configured as
follows:
Alarm 1 & Alarm 2, Alarm 1 & Output 2, Output 1 & Alarm 2, Output 1
& Output 2, Analog Out 1 & Alarm 2, Analog Out 1 & Output 2
. Analog Out
available only if Analog Output Option board is factory installed.
Alarm must be DISABLED if Ramp is ENABLED.
Figure 3.7 Flow Chart for Alarm 2
ENTER ALARM 2 MENU:
Press
a
1)
Press
a
, if necessary, until
CNFG
prompt appears.
Press
d
2)
Display advances to
INPT
Input Menu.
Press
a
3)
Press
a
, if necessary, until Display advances to
ALR2
Alarm 2 Menu.
Press
d
4)
Display advances to Alarm 2
ENBL
Enable or
DSBL
Disable
Submenu.
ALARM 2 ENABLE/DISABLE SUBMENU:
Press
d
5)
Display flashes previous selection. Press
b
until
ENBL
displays
to use Alarm 2.
Press
d
6)
Display shows
STRD
stored message momentarily and then
advances to
ABSo
only if it was changed, otherwise press
a
to
advance to
ABSo
Absolute/Deviation Submenu.
If
DSBL
Alarm 2
Disabled
was selected, all submenus of Alarm 2 will
be skipped and meter advances to
LOOP
Loop Break Time Menu. If
ENBL
Alarm 2
Enabled
was selected, Output 2 will automatically
Disabled
, and reassigned as Alarm 2.
The remaining Alarm 2 menu items are identical to Alarm 1 Menu. Modifying
Alarm Settings will not reset the instrument.