28
ALARM ENABLE/DISABLE AT POWER ON:
Press
d
15)
Display flashes previous selection. Press
b
to
ENBL
enable
or
DSBL
disable.
Press
d
16)
Display shows
STRD
stored message. momentarily and then
advances to
ALR.L
only if it was changed, otherwise press
a
to
advance to the
ALR.L
Alarm 1 Low Value Submenu.
If the alarm is enabled at Power On, the alarm will be active right after
reset. If the alarm is disabled at Power On, the alarm will become
enabled when the process value enters the non alarm area. The alarm is
not active while the process value is approaching Setpoint 1.
ALARM 1 LOW VALUE SUBMENU:
Press
d
17)
Display flashes 1
st
digit of previous value. Use
b
and
c
to
enter new value.
Press
b
&
c
18)
Use
b
and
c
to enter Alarm 1 Low Value.
Press
d
19)
Display shows
STRD
storage message momentarily and
then advances to
ALR.H
only, if it was changed, otherwise press
a
to advance to
ALR.H
Alarm 1 Hi Value Submenu.
ALARM 1 HI VALUE SUBMENU:
Press
d
20)
Display flashes 1
st
digit of previous value. Use
b
and
c
to
enter new value.
Press
b
&
c
21)
Use
b
and
c
to enter Alarm1 Hi Value.
Press
d
22)
Display shows
STRD
stored message momentarily and then
advances to the next menu only, if it was changed, otherwise
press
a
to advance to the next menu.