Abbreviated Controller Transmission Byte Format
The abbreviated response suppresses the node address and register ID
characters, leaving only the numeric part of the response. The numeric field is
5-6 characters long. If the decimal point is present, the field is 6 characters.
Negative values have a leading minus sign. The data field is right justified with
leading spaces.The end of the response string is terminated with a carriage
return <CR> and line feed <LF>. When print block transmission is finished, an
extra <SP><CR><LF> is used to provide separation between the blocks.
Byte
Description
1-6
6 byte data field, 4 bytes for number, one byte for sign, one byte
for decimal point
7
<CR>
8
<LF>
9
<SP>(Space).
This character only appears in the last line of a print
block
.
10
<CR>
This character only appears in the last line of a print block
.
11
<LF>
This character only appears in the last line of a print block
.
Example of Full Field Printout of Factory Settings
CN63300
CN63100
INP
25.0
TMP
87F
SET
0.0
SET
0F
PWR
47.8%
PWR
0.0%
PBD
100.0%
PBD
4.0%
INT
40S
INT
120S
DER
4S
DER
30S
AL1
0.0
AL1
0F
AL2
0.0
AL2
0F
DEV
25.0
DEV
87F
OFP
0.0%
OFP
0.0%
RMP
0.0R
RMP
0.0R
CRG
1.0G
CRG
1.0G
CDB
0.0
CDB
0F
OST
0000
RSP
0F
OST
0101
Troubleshooting Serial Communications
If problems are encountered when interfacing the controller(s) and host
device or printer, the following check list can be used to help find a solution.
1. Check all wiring. Proper polarity of all devices on the serial loop must be
observed. Refer to previous application examples.
2. Check the controller’s communication format in module 6-SC. Make sure
a l l d e v i c e s o n t h e s e r i a l l o o p a r e c o n f i g u r e d w i t h t h e s a me
communication format.
3. Check the requesting device constructed command string format.
4. When sending commands to the controller, an asterisk “*” or dollar sign
“$” must terminate the command. Make sure a carriage return or line feed
does not follow the command terminator.
5. Check the controller’s unit address in module 6-SC. It should be zero if the
address command is not used in the command string for single controller
configurations. In multiple controller configurations, make sure each
controller has a unique unit address.
6. Initiate transmissions from the controller by programming the User Input
for PrNt in module 1-IN for print and programming module 6-SC at PoPt
set INP (input) to YES. As long as the user input is connected to common,
controller data will be sent.
7. With two-way communications or multiple controller configurations,
make sure only one device is communicating at a time.
8. If all of the above has been done, try reversing the polarity of the serial
wires at host device or printer. Some devices have reversed polarity.