Configure Module 6 - Serial Communications (6-SC)
Controller returns to configuration access point (CnFP NO) if RS485 serial
option is not installed.
Display
Parameter
Range and Units
(Factory Setting)
Description/
Comments
bAUd
Baud rate
300 to 9600
(9600)
Baud rate of unit
must match
connected
equipment.
ConF
Character Frame
format
7O1
7E1
7n2
8n1
(7O1)
7 data, odd parity, 1
stop (was odd)
7 data, even parity, 1
stop (was even)
7 data, no parity, 2
stop (was none)
8 data, no parity, 1
stop
Addr
Controller address
0 to 99
(0)
For multiple unit
applications, each
unit must have a
unique node address.
Abrv
Abbreviated or full
transmission
yes/no
(no)
Selecting yes, the
controller does not
transmit mnemonics.
PoPt
Print options
yes/no
(no)
Selecting yes allows
print options shown
below, to be
programmed.
INP
Input
yes/no
(yes)
SEt
Setpoint
yes/no
(yes)
OPr
% Output Power
yes/no
(yes)
Pbd
% Proportional Band
yes/no
(no)
INt
Integral Time
yes/no
(no)
Display
Parameter
Range and Units
(Factory Setting)
Description/
Comments
dEr
Derivative Time
yes/no
(no)
AL1
Alarm 1 *
yes/no
(no)
AL2
Alarm 2 *
yes/no
(no)
dEv
Deviation From
Setpoint *
yes/no
(no)
OFP
% Output Power
Offset
yes/no
(no)
r-P
Setpoint Ramp Rate
yes/no
(no)
Crg
Relative Gain
yes/no
(no)
Cdb
Deadband
yes/no
(no)
OSt
Output Status
yes/no
(no)
rSP
Remote Setpoint *
yes/no
(no)
*
Model Number Dependent
-26-