Configure Module 1 - Input Parameters (1-IN) CN63300
Display
Parameter
Range and Units
(Factory Setting)
Description/
Comments
tYPE
Input Type
VOLt - Voltage
Curr - Current
(Curr)
dCPt
Decimal Point
0, 0.0, 0.00, or 0.000
(0.0)
If 0.000 is selected,
scaling points must be
a positive value.
rnd
Rounding
Increment
1, 2, 5, 10, 20, 50, or
100
(0.1)
Used in conjunction
with filtering to
stabilize the display
reading.
FLtr
Digital Input
Filtering And
Display Update
0 to 4
(1)
Increase number for
more filtering effect.
4 = 500 msec display
update rate. Adjusted
by Auto-Tune.
dSP1
Scaling Point #1
Display Value
-999 to 9999
(0.0)
Key-in display low
value.
InP1
Scaling Point #1
Input Signal
0/4-20 mA DC
0-10 VDC
0.00 to 20.00 mA
0.00 to 10.00 V
(4.00)
Press D button to
select Signal Input
method.
Value Key-in
Method
Key-in input low value.
Signal Input
Method
Apply input low value.
dSP2
Scaling Point #2
Display Value
-999 to 9999
(100.0)
Key-in display high
value.
Display
Parameter
Range and Units
(Factory Setting)
Description/
Comments
InP2
Scaling Point #2
Input Signal
0/4-20 mA DC
0-10 VDC
0.00 to 20.00 mA
0.00 to 10.00 V
(20.00)
Press D button to
select Signal
Input method.
Value Key-in
Method
Key-in input low
value.
Signal Input
Method
Apply input low
value.
SPLO
Setpoint Lower
Limit
-999 to 9999
(0.0)
Set low limit
below high limit.
SPHI
Setpoint Upper
Limit
-999 to 9999
(999.9)
Set high limit
above low limit.
SPrP
Setpoint Ramp
Rate
0 to 9999 units/minute
(0.0)
0.0 is off (no
ramping).
InPt
User Input *
PLOC - Program disable
ILOC - Integral action on/off
trnF - auto/manual select
SPrP - Setpoint ramp on/off
ALrS - Reset alarm output(s)
SP2 - Select SP1/SP2
rSP - Select
Local/Remote
PrNt - Serial block print
(PLOC)
Low = lock
Low = off
Low = manual
Low = end ramp
Low = reset
Low = SP2
Low =remote
Low =block print
*
Model Number Dependent
-21-
These tables are only used for programming the CN63300 models.
Use the tables on page 20 if you are programming a CN63100.
Summary of Contents for CN63100 Series
Page 23: ...FRONT PANEL PROGRAMMING CHART FOR CN63100 CN63300 CONTROLLERS 15 ...
Page 48: ... 40 ...
Page 62: ...PID Adjustments Cont d 54 Figure 33 Process Response Extremes ...
Page 88: ... 80 ...
Page 89: ... 81 ...
Page 90: ... 82 ...